Plan Review Details - Permit 23060553
Plan Review Stops For Permit 23060553
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By eroseber Date 2023-07-07 Time 18:15 Rev Time 0.00
Received By eroseber Date 2023-07-07 Time 18:15 Sent To  
Notes
2023-07-07 18:23:07PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
 ***PRIMARY CONTACT IS EMAIL***
  
 *** NOTE *** UNABLE TO PERFORM A COMPLETE REVIEW DUE TO
 INSUFFECIENT SUBMISSION. FURTHER COMMENTS MAY NEED TO
 BE ADDRESSED.***
 1. PLEASE SUBMIT SCHEDULE/FLOOR PLAN SHOWING LOCATION,
 MRH, AND WALL ZONE FOR REPLACEMENT FENESTRATION. THIS
 IS A LISTING OF PRODUCTS DESCRIBING UNIT 1, 2....ETRC.
 FBC 107.2
 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT
 FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN
 PRESSURE TABLES HIGHLIGHTED. FBC 107.2
 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED
 IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY.
 4. PLEASE SUBMIT COST BREAKDOWN SHOWING COMPLIANCE WITH
 FBC 109.3.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By pleduc Date 2023-06-28 Time   Rev Time 0.00
Received By pleduc Date 2023-06-28 Time 12:52 Sent To  
Notes
2023-06-28 13:03:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO BUILDING FOOTPRINT PLAN SHOWING WHERE
 THE DOOR OF THE UNIT IS LOCATED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A BUILDING
 FOOTPRINT PLAN SHOWING THE LOCATION OF THE UNIT DOOR BE
 REPLACED.
  
  
  
 1A) THERE IS NO INDICATIONS OF A DOOR SCHEDULE OF THE
 DOOR HARDWARE, LOCKS OR LATACHES, NOR DOOR CLOSER.
  
 LOCKS & LATCHES SHALL COMPLY WITH NFPA 101 CH 7, MEANS
 OF EGRESS.
  
 PLEASE PROVIDE THE DOOR HARDWARE INFORMATION.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-07 Cont ID  
Sent By eroseber Date 2023-07-07 Time 18:25 Rev Time 0.00
Received By eroseber Date 2023-06-27 Time 13:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By eroseber Date 2023-07-07 Time 18:23 Rev Time 0.00
Received By eroseber Date 2023-07-07 Time 18:23 Sent To  
Notes
2023-07-07 18:24:54PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
 ***PRIMARY CONTACT IS EMAIL***
  
  
 *** NOTE *** UNABLE TO PERFORM A COMPLETE REVIEW DUE TO
 INSUFFECIENT SUBMISSION. FURTHER COMMENTS MAY NEED TO
 BE ADDRESSED.***
 1. PLEASE SUBMIT SCHEDULE/FLOOR PLAN SHOWING LOCATION,
 MRH, AND WALL ZONE FOR REPLACEMENT FENESTRATION. THIS
 IS A LISTING OF PRODUCTS DESCRIBING UNIT 1, 2....ETRC.
 FBC 107.2
 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT
 FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN
 PRESSURE TABLES HIGHLIGHTED. FBC 107.2
 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED
 IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY.