Plan Review Details - Permit 23060549
Plan Review Stops For Permit 23060549
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-07-25 Cont ID  
Sent By cpuell Date 2023-07-25 Time 11:14 Rev Time 0.00
Received By cpuell Date 2023-07-25 Time 11:14 Sent To  
Notes
2023-07-25 11:18:47A NEW ADDRESS MAY BE REQUIRED FOR THE PROJECT BASED ON
 THE CITY???S ROAD CENTERLINES, PLEASE PROVIDE A SITE
 PLAN AND A GROUND FLOOR PLAN SHOWING WHAT WILL BE THE
 PRIMARY ENTRANCE INTO THE BUILDING. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESSING ISSUES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-27 Cont ID  
Sent By rperdomo Date 2023-07-27 Time 10:51 Rev Time 0.00
Received By rperdomo Date 2023-07-27 Time 10:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-11 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-10 Time 09:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-20 Cont ID  
Sent By ccole Date 2023-07-20 Time 15:11 Rev Time 0.00
Received By ccole Date 2023-07-19 Time 15:30 Sent To  
Notes
2023-07-20 15:12:071ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060549 FOUNDATION
 7/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-200F IMPORTANT NOTE: SEPARATE PERMITS ARE
 REQUIRED FOR THE FOLLOWING ITEMS-
  
 A) POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 B) GREASE AND SOLIDS INTERCEPTORS.
  
 C) OIL INTERCEPTOR.
  
 THE PERMIT APPLICATIONS FOR THE ITEMS LISTED ABOVE ARE
 REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL OF THIS
 PLUMBING REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO
 BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED
 BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS P-200F & P-300F: PROVIDE SIZING CALCULATIONS
 FOR THE GREASE INTERCEPTORS IN COMPLIANCE WITH SEC.
 1003.3.5.1 FBC. THE CALCULATIONS SHALL BE IN ACCORDANCE
 WITH ASME A112.14.3, ASME A112.14.4, ASME A112.14.6,
 CSA B481.3, OR PDI G101. THE CALCULATIONS CAN BE
 DEFERRED FOR THE FUTURE TENANT BUILD-OUTS HOWEVER
 INSTALLATIONS AT THIS TIME SHALL BE AT THE CONTRACTOR'S
 OWN RISK.
  
 3) P-200F, P-300F & P-503F: THE WPB UTILITIES DEPT.
 REQUIRES CLEANOUTS AT GREASE AND OIL INTERCEPTORS FOR
 WASTE SAMPLING. SHOW LOCATIONS OF THE CLEANOUTS AND
 SPECIFY MAKE AND MODEL OF HEAVY-DUTY TRAFFIC-RATED
 COVER- SEC. 107.2.1 WPB.
  
 4) P-200F & P-300F: PROVIDE VENTING FOR THE
 INTERCEPTORS- SEC. 1003.9 FBC P.
  
 5) P-200F, P-300F & P-503F: SHOW LOCATIONS OF ELEVATOR
 PIT SUMP PUMPS AND PROVIDE SUMP PIT, PUMP, AND PIPING
 INSTALLATION DETAILS- SECS. 712.1- 713.3.5 FBC P.
 PLEASE SHOW THE FORCE MAIN RUNS TO THE HUB DRAINS PER
 THE DETAIL AND VERIFY THE PUMP WILL BE THE OIL-SMART
 TYPE- SEC. 1003.4 EXCEPTION FBC P.
  
 6) P-200F & P-300F: SHOW TWO-WAY CLEANOUTS FOR THE
 SANITARY AND STORM DRAIN MAIN PIPES EXITING THE
 BUILDING AT A POINT NOT MORE THAN 30-INCHES FROM THE
 EXTERIOR WALLS- SECS. 708.1.3 & 1101.8 FBC P.
  
 7) P-200F & P-300F: PLEASE SHOW THE DFU CALCULATIONS AT
 THE 8-INCH SANITARY RISER- TABLE 710.1(1) FBC P.
  
 8) A101, P-200F & P-300F: BASED ON THE ARCHITECTURAL
 FLOOR PLAN DRAWING, THE PLUMBING FOUNDATION PLANS ARE
 MISSING NUMEROUS DRAIN AND VENT STUB-UPS FOR BATHROOMS,
 KITCHEN, AND BREAKROOM; EMERGENCY FLOOR DRAINS
 TYPICALLY LOCATED IN THE FIRE AND BOOSTER PUMP ROOMS,
 AND AT WATER HEATER LOCATIONS- SEC. 107.2.1 WPB.
  
 9) P-200F & P-300F: SHOW WATER HEATER DRAIN PIPING
 UNDERGROUND RUNS AND TERMINATION LOCATIONS (IF
 APPLICABLE TO THE SYSTEM DESIGNS)- SEC. 504.7.2 WPB.
  
 10) P-300F: CIVIL PLANS ARE REFERENCED IN THE DRAWINGS
 FOR SANITARY, STORM, AND WATER PIPE CONTINUATIONS
 HOWEVER THEY WERE NOT SUBMITTED- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2023-07-20 15:34:35PLUMBING SIGNATURES PASSED.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By ckimmerl Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***