| 2023-07-20 15:12:07 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23060549 FOUNDATION |
| | 7/20/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-200F IMPORTANT NOTE: SEPARATE PERMITS ARE |
| | REQUIRED FOR THE FOLLOWING ITEMS- |
| | |
| | A) POTABLE WATER SERVICE BACKFLOW PREVENTER. |
| | |
| | B) GREASE AND SOLIDS INTERCEPTORS. |
| | |
| | C) OIL INTERCEPTOR. |
| | |
| | THE PERMIT APPLICATIONS FOR THE ITEMS LISTED ABOVE ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL OF THIS |
| | PLUMBING REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO |
| | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| | BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEETS P-200F & P-300F: PROVIDE SIZING CALCULATIONS |
| | FOR THE GREASE INTERCEPTORS IN COMPLIANCE WITH SEC. |
| | 1003.3.5.1 FBC. THE CALCULATIONS SHALL BE IN ACCORDANCE |
| | WITH ASME A112.14.3, ASME A112.14.4, ASME A112.14.6, |
| | CSA B481.3, OR PDI G101. THE CALCULATIONS CAN BE |
| | DEFERRED FOR THE FUTURE TENANT BUILD-OUTS HOWEVER |
| | INSTALLATIONS AT THIS TIME SHALL BE AT THE CONTRACTOR'S |
| | OWN RISK. |
| | |
| | 3) P-200F, P-300F & P-503F: THE WPB UTILITIES DEPT. |
| | REQUIRES CLEANOUTS AT GREASE AND OIL INTERCEPTORS FOR |
| | WASTE SAMPLING. SHOW LOCATIONS OF THE CLEANOUTS AND |
| | SPECIFY MAKE AND MODEL OF HEAVY-DUTY TRAFFIC-RATED |
| | COVER- SEC. 107.2.1 WPB. |
| | |
| | 4) P-200F & P-300F: PROVIDE VENTING FOR THE |
| | INTERCEPTORS- SEC. 1003.9 FBC P. |
| | |
| | 5) P-200F, P-300F & P-503F: SHOW LOCATIONS OF ELEVATOR |
| | PIT SUMP PUMPS AND PROVIDE SUMP PIT, PUMP, AND PIPING |
| | INSTALLATION DETAILS- SECS. 712.1- 713.3.5 FBC P. |
| | PLEASE SHOW THE FORCE MAIN RUNS TO THE HUB DRAINS PER |
| | THE DETAIL AND VERIFY THE PUMP WILL BE THE OIL-SMART |
| | TYPE- SEC. 1003.4 EXCEPTION FBC P. |
| | |
| | 6) P-200F & P-300F: SHOW TWO-WAY CLEANOUTS FOR THE |
| | SANITARY AND STORM DRAIN MAIN PIPES EXITING THE |
| | BUILDING AT A POINT NOT MORE THAN 30-INCHES FROM THE |
| | EXTERIOR WALLS- SECS. 708.1.3 & 1101.8 FBC P. |
| | |
| | 7) P-200F & P-300F: PLEASE SHOW THE DFU CALCULATIONS AT |
| | THE 8-INCH SANITARY RISER- TABLE 710.1(1) FBC P. |
| | |
| | 8) A101, P-200F & P-300F: BASED ON THE ARCHITECTURAL |
| | FLOOR PLAN DRAWING, THE PLUMBING FOUNDATION PLANS ARE |
| | MISSING NUMEROUS DRAIN AND VENT STUB-UPS FOR BATHROOMS, |
| | KITCHEN, AND BREAKROOM; EMERGENCY FLOOR DRAINS |
| | TYPICALLY LOCATED IN THE FIRE AND BOOSTER PUMP ROOMS, |
| | AND AT WATER HEATER LOCATIONS- SEC. 107.2.1 WPB. |
| | |
| | 9) P-200F & P-300F: SHOW WATER HEATER DRAIN PIPING |
| | UNDERGROUND RUNS AND TERMINATION LOCATIONS (IF |
| | APPLICABLE TO THE SYSTEM DESIGNS)- SEC. 504.7.2 WPB. |
| | |
| | 10) P-300F: CIVIL PLANS ARE REFERENCED IN THE DRAWINGS |
| | FOR SANITARY, STORM, AND WATER PIPE CONTINUATIONS |
| | HOWEVER THEY WERE NOT SUBMITTED- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |