Plan Review Details - Permit 23060535
Plan Review Stops For Permit 23060535
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 15:11 Rev Time 0.00
Received By lbond Date 2023-07-17 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-24 Cont ID  
Sent By shill Date 2023-06-24 Time 08:35 Rev Time 0.00
Received By shill Date 2023-06-24 Time 08:35 Sent To  
Notes
2023-06-24 08:36:40SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 303.5.1, INTAKE OPENINGS ARE TO BE A NOT LESS
 THAN 10'. SUBMIT A SURVEY SHOWING LOCATION OF PROPOSED
 GENERATOR, INCLUDE DISTANCE TO OPENINGS.
  
 2. THE GENERATOR PAD IS DESIGNED FOR FBC 2010.
 GOVERNING CODE IS FBC 2020. REVISE.
  
 3. THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY OR
 ELECTRONICALLY SIGNED, FS471. UPLOAD DIGITALLY OR
 ELECTRONICALLY SIGNED ENGINEERING - SIGNATURE TO BE IN
 ACCORDANCE WITH FBPE RULES.
  
 4. THE GENERATOR PAD ENGINEERING IS FOR GENERATORS FROM
 8KW TO 22KW, A 24KW GENERATOR IS PROPOSED. DIMENSIONS
 OF GENERATOR PROPOSED ARE NOT CONSISTENT WITH THE
 DIMENSIONS/WEIGHT ON ENGINEERING.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-23 Cont ID  
Sent By jleahy Date 2023-06-23 Time 11:47 Rev Time 0.00
Received By jleahy Date 2023-06-23 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-19 Cont ID  
Sent By ecolon Date 2023-07-19 Time 15:44 Rev Time 0.00
Received By ecolon Date 2023-07-12 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-24 Cont ID  
Sent By shill Date 2023-06-24 Time 08:42 Rev Time 0.00
Received By shill Date 2023-06-12 Time 13:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 15:12 Rev Time 0.00
Received By lbond Date 2023-07-17 Time 15:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-24 Cont ID  
Sent By shill Date 2023-06-24 Time 08:42 Rev Time 0.00
Received By shill Date 2023-06-24 Time 08:42 Sent To  
Notes
2023-06-24 08:42:15SEE BUILDING

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By ecolon Date 2023-07-19 Time 15:44 Rev Time 0.00
Received By ecolon Date 2023-07-19 Time 15:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-22 Cont ID  
Sent By ecolon Date 2023-06-22 Time 16:14 Rev Time 0.00
Received By ecolon Date 2023-06-22 Time 16:11 Sent To  
Notes
2023-06-22 16:12:15PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK.
  
 PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE
 PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM
 BOUNDARY LINES
  
 ****REVIEWED BY*****
 ERIK COLON
 561-822-1398
 [email protected]