| 2023-07-14 17:41:03 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23060501 |
| | 7/14/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. GENERAL/ADMINISTRATIVE COMMENTS. |
| | |
| | 1) THE ENERGYGAUGE REPORT DOES NOT PROVIDE COMPLIANCE |
| | DATA FOR THE WATER HEATING AND PIPING SYSTEMS- SEC. |
| | C404.1 FBC EC. |
| | |
| | 2) SEPARATE PERMITS REQUIRED INCLUDE THE POTABLE WATER |
| | BACKFLOW PREVENTER, GROUND FLOOR SOLIDS INTERCEPTORS |
| | AND OIL SEPARATOR, AND 6TH FLOOR GREASE INTERCEPTOR- |
| | SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE SUBMITTED |
| | PLUMBING PLANS FOR THE BUILDING WILL NOT BE APPROVED |
| | UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED ABOVE |
| | HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS TBD |
| | (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS |
| | SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL |
| | OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 3) SEPARATE PERMITS ARE REQUIRED FOR THE PUBLIC AND |
| | PRIVATE POOLS AND SPAS HOWEVER THE PLUMBING FLOOR PLANS |
| | AND RISERS SHOW POOL WASTEWATER DRAINING INTO THE |
| | SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126 |
| | (B)(5) WPB CODE OF ORDINANCES. PLEASE NOTE THE |
| | FOLLOWING INFORMATION. |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| | STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| | - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 4) SEPARATE PERMITS ARE REQUIRED FOR THE IRRIGATION |
| | SYSTEM AND SYSTEM BACKFLOW PREVENTER. CURRENTLY NO |
| | PLANS HAVE BEEN SUBMITTED FOR REVIEW. PLANS SHALL BE |
| | SUBMITTED UNDER THE SEPARATE PERMITS- SEC. 107.2.1 WPB. |
| | |
| | 2. ARCHITECTURAL COMMENTS. |
| | |
| | 5) 4) SHEETS ALS.0.0, ALS.0.2 & ALS.0.3: PLEASE REFER |
| | TO SEC. 233 FBC ACCESSIBILITY. BASED ON SECS 233.3.1 & |
| | 233.3.1.1 AT LEAST 5% OF THE TOTAL NUMBER OF |
| | RESIDENTIAL DWELLING UNITS SHALL BE PROVIDED WITH |
| | MOBILITY FEATURES COMPLYING WITH SECS. 809.2- 809.4 AND |
| | SHALL BE ON AN ACCESSIBLE ROUTE; AND AT LEAST 2% SHALL |
| | BE PROVIDED WITH COMMUNICATION FEATURES COMPLYING WITH |
| | 809.4. THESE REQUIREMENTS ARE SEPARATE FROM COMPLIANCE |
| | WITH THE FAIR HOUSING DESIGN ACT REQUIREMENTS. REFER TO |
| | SEC. 233.3.5 DISPERSION AND PROVIDE A LIST OR SCHEDULE |
| | ON THE PLAN SHOWING THE LOCATIONS OF THE UNITS, AND |
| | REVISE THE ARCHITECTURAL AND PLUMBING PLANS WHERE |
| | REQUIRED. |
| | |
| | A) ALS.02 & ALS.0.3: THE PLANS INDICATE THE R2 CONDO |
| | UNITS ARE DESIGNED IN ACCORDANCE WITH THE FAIR HOUSING |
| | DESIGN ACT MANUAL (1998). TO HELP EXPEDITE THE REVIEW |
| | AND INSPECTION OF THE CONDO BATHROOMS PLEASE REFER TO |
| | PAGES 7.34 & 7.35 OF THE FHDA AND INDICATE WHICH DESIGN |
| | SPECIFICATION HAS BEEN CHOSEN- SPECIFICATION A OR B. |
| | PLEASE PROVIDE THE SPECIFICATION TYPE ON ALS.02, |
| | ALS.04, AND ON THE ENLARGED A, B, C & D UNIT PLANS- |
| | SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1. |
| | |
| | B) ALS.0.0, ALS.0.2 & ALS.0.3: AS NOTED THERE ARE |
| | DESIGN DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA |
| | COMPLIANT) DWELLING UNITS AND A FHDA COMPLIANT UNITS. |
| | PLEASE REFER TO SEC. 809.4 FBC ACCESSIBILITY AND |
| | PROVIDE SEPARATE ENLARGED ACCESSIBLE UNIT DRAWINGS WITH |
| | THE FOLLOWING COMPLIANCE DETAILS PER SEC. 603- 610 FBC |
| | ACCESSIBILITY. PLEASE NOTE MANY OF THESE SECTIONS HAVE |
| | EXCEPTIONS WHICH ALLOW FOR JUST GRAB BAR BACKING TO BE |
| | INSTALLED INSTEAD OF COMPLETE GRAB BARS. |
| | |
| | 1. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | |
| | 2. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | |
| | 3. TURNING SPACE DIAMETERS- SEC. 304.3. |
| | |
| | 4. CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | |
| | 5. HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | |
| | 6. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| | |
| | 7. HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3. |
| | |
| | 8. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| | 604.5.1 & 604.5.2. |
| | |
| | 9. CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | |
| | 10. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | |
| | 11. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | BATHTUBS- SEC. 607.2. |
| | |
| | 12. BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC. |
| | 607.3. |
| | |
| | 13. BATHTUB GRAB BAR DETAILS- SEC. 607.4. |
| | |
| | 14. BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6. |
| | |
| | 15. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SHOWER- SECS. 608.2.1 & 608.2.2. |
| | |
| | 16. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND |
| | 608.3.2. |
| | |
| | 17. LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS |
| | IN THE SHOWERS- SECS. 608.5.1 & 608.5.2. |
| | |
| | 18. LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING |
| | DETAILS- |
| | |
| | 6) ALS.02, ALS.0.3: PROVIDE GRAB BAR BACKING DETAILS |
| | FOR THE CONDO SHOWERS IN COMPLIANCE WITH PAGES 6.12 & |
| | 6.13 FDHA MANUAL. |
| | |
| | 7) SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1, |
| | A-9.14.1, A-9-15.1, A-9.16.1,A-17.1, A-18.1: PLEASE |
| | PROVIDE FHDA COMPLIANCE DETAILS ON THE FLOOR PLANS OR |
| | PROVIDE NOTES REFERENCING SHEETS ALS.02 & ALS.03 FOR |
| | DETAIL LOCATIONS. |
| | |
| | 8) ALS.1.1 PLUMBING FIXTURE COUNT TABLE: REQUIRED AND |
| | PROVIDED COUNTS CANNOT BE UNISEX BECAUSE SEPARATE |
| | FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE UNLESS |
| | ONLY ONE WATER CLOSET FOR EACH IS REQUIRED- SECS. 403.2 |
| | & 403.2.1 FBC P. PLEASE LABEL THE BATHROOMS ON ALL 1ST |
| | FLOOR PLANS AS EITHER MALE OR FEMALE. |
| | |
| | 9) P1.6.2A: SHOW THE WEST POOL OUTDOOR SHOWER LOCATION- |
| | SEC. 454.1.6.2 FBC B. |
| | |
| | 10) A9.1.1A: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | AND DIMENSIONS AT THE ACCESSIBLE EMPLOYEE LOUNGE SINK |
| | AND WHEEL CHAIR ACCESSIBLE DRINKING FOUNTAIN- SECS. |
| | 602.2 & 606.2 FBC ACC. A) PLEASE PROVIDE AN ELEVATION |
| | DETAIL FOR THE DRINKING FOUNTAINS SHOWING THE KNEE AND |
| | TOE CLEARANCES AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC |
| | ACC. |
| | |
| | 11) A9.1.6: SHOW THE HEIGHTS OF THE WATER CLOSET SEATS |
| | MEASURED FROM THE FINISHED FLOORS- SEC. 604.4 FBC ACC. |
| | |
| | 12) A9.1.6: SHOW THE KNEE AND TOE CLEARANCES FOR THE |
| | LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3 FBC ACC. |
| | |
| | 13) A9.7.5: PROVIDE AN ELEVATION DETAIL FOR THE |
| | DRINKING FOUNTAINS SHOWING THE KNEE AND TOE CLEARANCES |
| | AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC ACC. |
| | |
| | 14) A9.7.6, A9.7.7, & A9.7.8: MISSING FBC ACC DETAILS: |
| | |
| | A) HEIGHTS OF THE ACCESSIBLE WATER CLOSET SEATS |
| | MEASURED FROM THE FINISHED FLOORS- SEC. 604.4. |
| | |
| | B) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE |
| | LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3. |
| | |
| | C) ACCESSIBLE URINAL RIM HEIGHT FROM THE FINISHED |
| | FLOOR- SEC. 605.2. |
| | |
| | 15) A9.7.1B, A9.7.10: THE MEN'S AND WOMEN'S SHOWERS |
| | SHALL BE ACCESSIBLE AS REQUIRED BY SEC. 213.3.6 FBC |
| | ACC. PROVIDE THE FOLLOWING DETAILS FBC ACC. |
| | |
| | A) GRAB BAR LOCATIONS, LENGTHS AND MOUNTING HEIGHTS- |
| | SEC. 608.3.3. PLEASE NOTE THE SEATS WILL HAVE TO BE |
| | RELOCATED TO ALLOW INSTALLATION OF THE SIDE WALL GRAB |
| | BARS. |
| | |
| | B) THE CONTROLS, FAUCETS, AND SHOWER SPRAY SHALL BE |
| | RELOCATED TO THE SIDE WALL ADJACENT TO THE RELOCATED |
| | SEAT AT A POINT 27 INCHES MAXIMUM FROM THE SIDE WALL |
| | BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL |
| | OPPOSITE THE SEAT 15 INCHES MAXIMUM, LEFT OR RIGHT, OF |
| | THE CENTERLINE OF THE SEAT. |
| | |
| | C) SHOW THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| | SHALL BE LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN |
| | 48 INCHES ABOVE THE SHOWER FLOOR. |
| | |
| | 3. PLUMBING COMMENTS |
| | |
| | 16) P1.0.0, P1.1.1A, P1.1.1B, P1.1.1C- FLOOD HAZARD: |
| | FLOOD MAPS INDICATE PORTIONS OF THE BUILDING MAY BE |
| | CONSTRUCTED IN AN AE FLOOD HAZARD ZONE. PLEASE NOTE THE |
| | FOLLOWING. |
| | |
| | A) REFER TO SEC. 309.2 FBC P FLOOD HAZARD AND SEC. 7.3 |
| | ASCE 24-14: THE PLUMBING SYSTEMS, EQUIPMENT, FIXTURES |
| | AND OTHER COMPONENTS SYSTEM SHALL BE INSTALLED ABOVE |
| | THE DESIGN FLOOD ELEVATION HEIGHT, OR MEET THE |
| | EXCEPTION UNDER 309.2. |
| | |
| | B) UNDERGROUND PIPING AND PLUMBING SYSTEMS SHALL BE |
| | BURIED TO A DEPTH SUFFICIENT TO PREVENT MOVEMENT, |
| | SEPARATION, OR LOSS DUE TO FLOODING AND EROSION UNDER |
| | DESIGN FLOOD CONDITIONS- 7.3.1 ASCE 24-14. |
| | |
| | C) OPENINGS IN THE PLUMBING SYSTEMS BELOW THE DESIGN |
| | FLOOD ELEVATION HEIGHT SHALL BE PROTECTED WITH |
| | AUTOMATIC BACKWATER VALVES. SHOW COMPLIANCE WHERE |
| | REQUIRED WITH NOTES AND DETAILS ON THE PLANS- SEC. |
| | 714.1 FBC P. |
| | |
| | 17) P1.0.0: PROVIDE CIVIL PLANS SHOWING WATER, FIRE AND |
| | GAS SERVICE PIPING CONTINUATIONS AND CONNECTIONS TO |
| | MAINS, AND SANITARY AND STORM DRAIN CONTINUATIONS AND |
| | CONNECTIONS- SEC. 107.2.1 WPB. |
| | |
| | 18) P1.1.1A, P1.1.1B, P1.1.1C: TO HELP EXPEDITE THE |
| | REVIEW PLEASE SHOW THE DFU TOTALS AT THE SANITARY |
| | RISERS, BRANCHES, AND MAIN BUILDING DRAINS- TABLES |
| | 710.1(1) & 710.1(2) FBC P. |
| | |
| | A) SHOW THE GPM TOTALS AT STORM RISERS, BRANCHES, AND |
| | MAIN DRAINS- TABLES 1106.2, 1106.3 FBC P. |
| | |
| | B) TO HELP EXPEDITE THE REVIEW PLEASE LABEL SANITARY |
| | PIPING (S) AND STORM PIPING (ST)- SEC. 107.2.1 WPB. |
| | |
| | 19) P1.1.1B, P1.1.1C, P4.1.1: PROVIDE EQUIPMENT |
| | SCHEDULES AND SIZING CALCULATIONS FOR THE SOLIDS |
| | INTERCEPTORS, THE OIL SEPARATOR, AND THE LINT TRAP- |
| | SECS. 1003.1, 1003,4,2, & 1003.6 FBC P. |
| | |
| | A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR EACH WITH |
| | ENGINEER'S APPROVAL STAMP- SEC. 107.3.4 WPB. |
| | |
| | 20) P1.1.C & P4.1.1: IT APPEARS THE SOLIDS INTERCEPTOR |
| | IN THE TRASH ROOM IS NOT VENTED- SEC. 1003.9 FBC P. |
| | |
| | 21) P1.1.2A, P4.2.1: PLEASE PROVIDE WATER DISTRIBUTION |
| | DESIGN CRITERIA- SEC. 604.3 FBC P. |
| | |
| | 22) P4.2.1: COMPLETE WATER RISER DRAWINGS FROM THE |
| | GROUND FLOOR THROUGH THE FLOOR INTERVALS TO THE ROOF |
| | HAVE NOT BEEN PROVIDED. PLEASE PROVIDE THE RISERS- SEC. |
| | 107.3.5.1.3 WPB. TO HELP EXPEDITE THE REVIEW PLEASE |
| | NUMBER THE INDIVIDUAL RISERS AND PROVIDE MATCHING |
| | NUMBERS AT THE RISER LOCATIONS SHOWN ON THE GROUND |
| | FLOOR ISOMETRIC DRAWINGS. |
| | |
| | A) THE WATER RISER DRAWINGS SHALL SHOW PIPE SIZES FROM |
| | FLOOR-TO-FLOOR INTERVALS, PIPE SIZES AT UNIT ENTRANCES, |
| | AND LOCATIONS OF SHUTOFF VALVES AND PRV'S WHERE |
| | REQUIRED- SECS 604.4, 604.7 & 606.1 FBC P. |
| | |
| | 23) P4.1.1: COMPLETE CONVENTIONAL SANITARY |
| | DRAINAGE/VENT RISER DRAWINGS FROM THE GROUND FLOOR |
| | THROUGH THE FLOOR INTERVALS TO THE ROOF HAVE NOT BEEN |
| | PROVIDED. PLEASE PROVIDE THE RISERS- SEC. 107.3.5.1.3 |
| | WPB. TO HELP EXPEDITE THE REVIEW PLEASE NUMBER THE |
| | INDIVIDUAL RISERS AND PROVIDE MATCHING NUMBERS AT THE |
| | RISER LOCATIONS SHOWN ON THE GROUND FLOOR ISOMETRIC |
| | DRAWINGS. |
| | |
| | B) THE CONVENTIONAL SANITARY RISERS SHALL SHOW SOIL, |
| | WASTE, AND VENT STACK SIZES FROM FLOOR-TO-FLOOR, |
| | LOCATIONS AND SIZES OF OFFSETS AND RELIEF VENTS WHERE |
| | REQUIRED, VENT TO ROOF LOCATIONS, CLEANOUT LOCATIONS, |
| | AND DFU CALCULATIONS- SECS. 710.1, 904.1, 904.2, 904.4, |
| | 904.5, 906.1, 907.1, & 908.1 FBC P. |
| | |
| | 24) P4.1.1 & P.503: CONCERNING THE TUFF-RITE SOVENT |
| | SYSTEM PLEASE REFER TO SEC. 316 FBC P. THE SYSTEM IS |
| | DEFINED AS AN ALTERNATIVE ENGINEERED DESIGN WHICH |
| | REQUIRES THE ENGINEER OF RECORD TO SUBMIT TECHNICAL |
| | DATA TO SUBSTANTIATE THE PROPOSED ALTERNATIVE DESIGN |
| | AND TO PROVE THE PERFORMANCE MEETS THE INTENT OF THE |
| | CODE- SEC. 316.1.3. PLEASE PROVIDE THE FOLLOWING ITEMS |
| | |
| | A) ENGINEER'S LETTER TO THE BUILDING OFFICIAL WITH |
| | SUFFICIENT EVIDENCE TO REQUEST APPROVAL OF THE |
| | ALTERNATIVE SYSTEM. |
| | |
| | B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS WITH ENGINEER'S APPROVAL STAMP. |
| | |
| | C) SEPARATE SITE-SPECIFIC FLOOR PLANS AND COMPLETE |
| | RISER DRAWINGS. THE CURRENT PLANS SUBMITTED CAN BE |
| | SEPARATED, MODIFIED, LABELED PROPERLY AND PROVIDED WITH |
| | ADDITIONAL SITE-SPECIFIC INFORMATION SUCH AS PIPE |
| | SLOPES AND HORIZONTAL PIPE LENGTHS ETC.- SEC. 316.1.4. |
| | PLEASE NOTE WHERE REQUIRED THE RISERS SHALL BE |
| | CONTINUOUS FROM GROUND FLOOR TO ROOF. |
| | |
| | 25) P.4.1.1: SHOW REQUIRED TRAPS FOR THE DW 1 DRAINS- |
| | SEC. 1002.1 FBC P. |
| | |
| | 26) P1.1.2A, P1.1.2B, P4.2.1: COLD OR TEMPERED WATER |
| | SHALL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC |
| | P. |
| | |
| | 27) P1.1.2A, P1.1.2B, P4.2.1: THE 1/2-INCH HOT WATER |
| | FIXTURE SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING |
| | THE MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT |
| | WATER SOURCES- TABLE C404.5.1 FBC ENERGY. |
| | |
| | 28) P4.2.1: SHOW FULL-OPEN SHUT OFF VALVES AT BASE OF |
| | THE WATER RISERS- SEC. 606.1 (4) FBC P. |
| | |
| | 29) P1.2.1A, P1.3.1A, P1.4A: THE DRAWINGS APPEAR TO |
| | SHOW AREA DRAINS (AD) ON THE WEST SIDE DRAINING INTO |
| | THE SANITARY WHICH IS PROHIBITED PER SEC. 90-126 (B) |
| | WPB CODE OF ORDINANCES. |
| | |
| | 30) P1.5.2C NOTE 6: A BACKFLOW PREVENTER IS REQUIRED |
| | FOR THE MAKEUP WATER LINE TO THE POOL EQUIPMENT- SEC. |
| | 608.3 FBC P. |
| | |
| | 31) P1.6.1A: THE PLAN APPEARS TO SHOW A SANITARY DRAIN |
| | LINE PENETRATING THE INTERIOR EXIST STAIRWAY 2 WHICH IS |
| | PROHIBITED PER SEC. 1023.5 FBC B. |
| | |
| | 32) P1.6.1B KITCHEN GREASE INTERCEPTOR: PLEASE PROVIDE |
| | THE FOLLOWING ITEMS PER SEC. 1003.3.5 FBC P. |
| | |
| | A) EQUIPMENT SCHEDULE- MAKE AND MODEL, GALLON SIZE. |
| | |
| | B) SIZING CALCULATIONS. |
| | |
| | C) ENLARGED PIPING DIAGRAM SHOWING DRAIN PIPE SIZES AND |
| | RUNS FROM FIXTURES, OUTLET AND VENT PIPING SIZES AND |
| | RUNS. |
| | |
| | D) PLEASE NOTE DISCHARGES FROM HAND SINKS, ICE MAKER |
| | AND ICE BINS SHALL NOT DRAIN INTO THE INTERCEPTOR- SEC. |
| | 1003.3.1 FBC P. |
| | |
| | E) P4.1.2: SHOW THE INTERCEPTOR LOCATION ON THE RISER- |
| | SEC. 107.2.1 WPB. |
| | |
| | 33) P1.6.1B, P1.6.2B: PLEASE PROVIDE A PLUMBING |
| | APPLIANCE AND FIXTURE EQUIPMENT SCHEDULE AND |
| | CORRELATING PLAN FOR THE KITCHEN- SEC. 107.2.1 WPB. |
| | |
| | 34) P1.6.2A, P1.6.2B: PROVIDE BACKFLOW PREVENTERS FOR |
| | WATER SUPPLY LINES TO POOL EQUIPMENT AND STEAM |
| | GENERATORS- SEC. 608.3 FBC P. |
| | |
| | 35) P1.6.2A, P1.6.2B: COLD OR TEMPERED WATER SHALL BE |
| | DELIVERED FROM THE LAVATORIES- SEC. 419.5. |
| | |
| | 36) P1.6.2A, P1.6.2B: THE 1/2-INCH HOT WATER FIXTURE |
| | SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THE |
| | MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER |
| | SOURCES- TABLE C404.5.1 FBC ENERGY. |
| | |
| | 37) P2.0.1, A2.0.1, A8.4.1: THE OVERFLOW SCUPPERS SIZES |
| | ARE NOT SHOWN AND THE SCUPPER LOCATIONS ON THE PLANS |
| | DON'T MATCH- SEC. 1108.3 FBC P. |
| | |
| | 38) P4.01 & P4.02: THE STORM RISERS DO NOT SHOW THE GPM |
| | FLOWS FROM THE AD'S, PD'S, AND CND'S, AND ALSO THE |
| | ACCUMULATIVE TOTALS BRANCH CONNECTIONS AND MAIN |
| | OUTFLOWS- SEC. 1106.2 FBC P. |
| | |
| | 39) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1, |
| | P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3, |
| | P3.12.4: SHOW WATER SHUTOFF LOCATIONS AT UNIT |
| | ENTRANCES- SEC. 606.1 (6) FBC P. |
| | |
| | 40) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1, |
| | P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3, |
| | P3.12.4: IT APPEARS THE DEVELOPED LENGTH OF THE HOT |
| | WATER TO SOME OF THE UNIT PLUMBING FIXTURES MAY EXCEED |
| | 50 FT. FROM THE HOT WATER SOURCES- SEC. 607.2 FBC P. |
| | PLEASE REVIEW AND CORRECT OIF NECESSARY. |
| | |
| | 41) P3.13.0: A MEANS OF DILUTING OR NEUTRALIZING THE |
| | CONDENSATE WASTE FROM THE GAS-FIRED WATER HEATERS IS |
| | REQUIRED- SEC. 803.1 FBC P. |
| | |
| | 42) P0.0.1 & P5.0.1: PROVIDE PIPING SPECIFICATIONS FOR |
| | WATER, SANITARY, GREASE, OIL, VENT, GAS AND COMPLETE |
| | FIRESTOPPING DETAILS FOR WALL AND FLOOR PENETRATIONS- |
| | SECS. 315.1 605.4, 702.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |