Plan Review Details - Permit 23060302
Plan Review Stops For Permit 23060302
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 12:31 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 12:31 Sent To  
Notes
2023-06-27 12:31:591ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23060302
 6/27/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 NFPA 58-2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SURVEY SHOWS THE TANK WILL BE LOCATED IN THE
 DRIVEWAY. PLEASE SHOW THE LOCATION WILL BE A MINIMUM 10
 FT. AWAY FROM THE BUILDING AND THE PROPERTY LINES- SEC.
 6.3.3.2 NFPA 58.
  
 2) PROVIDE A TANK PROFILE DETAIL SHOWING THE BURIAL
 DEPTH, CLEARANCE FROM GRADE, HOW ACCESS TO THE SHUTOFF
 VALVE AND REGULATOR WILL BE PROVIDED, AND HOW THE TANK
 AND CONTROLS WILL BE PROTECTED FROM VEHICULAR DAMAGE-
 SECS. 6.6.6.1 B, C, & E.
  
 3) THE TANK ANCHORAGE SUBMITTAL FROM TIE DOWN
 ENGINEERING HAS OUTDATED CODE REFERENCES AND IS NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD-
 SECS. 107.2.1 WPB AND FL. STATUTE 471.025 AND SEC.
 61G15-23.005 FAC. PLEASE NOTE THE TIE DOWN ENGINEERING
 IS GENERIC AND SHALL BE MARKED UP BY THE ENGINEER TO
 SHOW THE PHYSICAL ADDRESS OF THE TANK, THE SIZE OF THE
 TANK, THE NUMBER AND TYPE OF TIE DOWN STRAPS OR CABLES,
 AND THE SOIL CLASSIFICATION AND SIZE OF AUGERS.
  
 4) THE ANODE SPEC SHEET IS GENERIC AND SHALL BE MARKED
 UP TO SHOW THE PRODUCT NUMBER OF THE ANODE TO BE
 INSTALLED. PLEASE PROVIDE INSTALLATION AND TESTING
 INSTRUCTIONS OR PLACE A NOTE TO INDICATE THEY WILL BE
 ONSITE FOR INSPECTION- SECS. 6.17.1- 6.17.3.3 NFPA 58.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-06-27 Time   Rev Time 0.00
Received By amcgrego Date 2023-06-26 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 10:37 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 12:32 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 09:56 Sent To  
Notes
2023-06-27 12:35:071ST SIGNATURES FBC-2020 RES. GAS
 PERMIT- 23060302
 6/27/23
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE TANK ANCHORAGE SUBMITTAL FROM TIE DOWN
 ENGINEERING HAS OUTDATED CODE REFERENCES AND IS NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD-
 SECS. 107.2.1 WPB AND FL. STATUTE 471.025 AND SEC.
 61G15-23.005 FAC. PLEASE NOTE THE TIE DOWN ENGINEERING
 IS GENERIC AND SHALL BE MARKED UP BY THE ENGINEER TO
 SHOW THE PHYSICAL ADDRESS OF THE TANK, THE SIZE OF THE
 TANK, THE NUMBER AND TYPE OF TIE DOWN STRAPS OR CABLES,
 AND THE SOIL CLASSIFICATION AND SIZE OF AUGERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  