Plan Review Details - Permit 23060267
Plan Review Stops For Permit 23060267
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By cpuell Date 2023-07-13 Time 14:39 Rev Time 0.00
Received By cpuell Date 2023-07-13 Time 14:39 Sent To  
Notes
2023-07-13 14:40:17FLOOR PLAN PROVIDED ACTIVATED ADDRESS AND UPDATED THE
 PERMIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-06-20 Cont ID  
Sent By cpuell Date 2023-06-20 Time 09:57 Rev Time 0.00
Received By cpuell Date 2023-06-20 Time 09:57 Sent To  
Notes
2023-06-20 09:59:29SUITE 620 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER
 QUESTIONS YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jwitmer Date 2023-06-28 Time 14:33 Rev Time 0.00
Received By jwitmer Date 2023-06-28 Time 14:32 Sent To  
Notes
2023-06-28 14:33:01COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By jwitmer Date 2023-06-28 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2023-06-28 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-26 Cont ID  
Sent By mpeterso Date 2023-06-26 Time 14:08 Rev Time 0.00
Received By mpeterso Date 2023-06-26 Time 12:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-27 Cont ID  
Sent By pleduc Date 2023-07-27 Time   Rev Time 0.00
Received By pleduc Date 2023-07-27 Time 10:45 Sent To  
Notes
2023-07-27 10:45:37FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES
 AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-16 Cont ID  
Sent By pleduc Date 2023-06-16 Time   Rev Time 0.00
Received By pleduc Date 2023-06-16 Time 09:32 Sent To  
Notes
2023-06-16 09:42:32FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES
 AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-26 Time 08:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-17 Cont ID  
Sent By rwbrown Date 2023-07-17 Time 08:50 Rev Time 0.00
Received By rwbrown Date 2023-07-13 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-06 Cont ID  
Sent By hmoser Date 2023-07-06 Time 14:18 Rev Time 0.00
Received By hmoser Date 2023-06-15 Time 11:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-06 Cont ID  
Sent By hmoser Date 2023-07-06 Time 14:18 Rev Time 0.00
Received By hmoser Date 2023-07-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By rwbrown Date 2023-07-17 Time 08:45 Rev Time 0.00
Received By rwbrown Date 2023-07-17 Time 08:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By rwbrown Date 2023-06-21 Time 06:13 Rev Time 0.00
Received By rwbrown Date 2023-06-21 Time 06:13 Sent To  
Notes
2023-06-21 06:14:461ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1/613.1 - THE DETAIL ON P6.1 NEEDS TO
 SHOW THAT THE POINT OF USE WATER HEATER HAS A LIMITING
 DEVICE COMPLIANT WITH ASSE 1070.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-07-17 Cont ID  
Sent By rwbrown Date 2023-07-17 Time 08:48 Rev Time 0.00
Received By rwbrown Date 2023-07-17 Time 08:48 Sent To  
Notes
2023-07-17 08:50:30SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 THE MEP PAGES ARE OKAY. THE "T" PAGES ARE NOT PROPERLY
 ELECTRONICALLY SEALED.
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By hmoser Date 2023-07-06 Time 13:35 Rev Time 0.00
Received By hmoser Date 2023-07-06 Time 13:35 Sent To  
Notes
2023-07-06 13:58:09MEP SHEETS AND ARCHITECTURAL SHEETS ARE GOOD
 ALL OTHER NEED A DIGITAL SIGNATURE. HM.
2023-06-28 14:38:43ARCHITECTURAL SHEETS SIGNATURE IS GOOD. J WITMER
 6-28-23