2023-07-25 10:17:09JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 (NON- HVHZ) COVERS MULTIPLE ATTACHMENT LIMITATIONS &
 INSTALLATION APPROVED ASSEMBLIES. SELECT ATTACHMENT
 LIMITATION SYSTEM FROM 5.8.3.2 MECHANICALLY-ATTACHED
 BASE SHEET TABLE 4B ALLOWABLE DESIGN PRESSURES, 2-PLY
 UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS PAGES
 #8-14. SELECT SYSTEM THAT MEETS OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENTS FOR A HIP ROOF; 5:12 ROOF
 SLOPE; MRH 25 FT. MINIMUM DESIGN PRESSURE REQUIREMENT
 OF -78 IN AN EXPOSURE CATEGORY C AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-30 Cont ID  
Sent By jbrooks Date 2023-06-30 Time 10:46 Rev Time 0.00
Received By jbrooks Date 2023-06-30 Time 07:53 Sent To  
Notes
2023-06-30 10:46:39JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL5259-R39 (NON-HVHZ).
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 (NON- HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER
 OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES, ATTACHMENT
 LIMITATIONS & INSTALLATION APPROVED ASSEMBLIES. SELECT
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1
 DIRECT-TO-DECK TABLE 4A: ALLOWABLE DESIGN PRESSURES,
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 PAGE #6 & 7 OR ATTACHMENT LIMITATION SYSTEM FROM
 5.8.3.2 MECHANICALLY-ATTACHED BASE SHEET TABLE 4B
 ALLOWABLE DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS
 IN TILE ROOF APPLICATIONS PAGES #8-14. MUST MEET OR
 EXCEED -78 DESIGN PRESSURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-14 Cont ID  
Sent By rmcphers Date 2023-06-14 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2023-06-14 Time 16:31 Sent To  
Notes
2023-06-14 16:47:50ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL FL5259-R38 - YOU HAVE CIRCLED
 UDL-13 ON PAGE 8 WHICH HAS A MAXIMUM WIND UPLIFT DESIGN
 OF (-45) - (-45) DOES NOT MEET THE REQUIRED UPLIFT
 PRESSURES PER FBC TABLE R301.2(2) - PLEASE SEE NOTE
 5.8.3.2 ON THE PRODUCT APPROVAL.
  
 2) PRODUCT APPROVAL FL5374-R26 - PLEASE CIRCLE THE
 ATTACHMENT TO BE USED ON PAGE 5 OF THE PRODUCT
 APPROVAL.
  
 3) PRODUCT APPROVAL FL6332 R9 - PLEASE CIRCLE THE
 ATTACHMENT TO BE USED ON PAGE 3 OF THE PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-09 Cont ID  
Sent By jbrooks Date 2023-06-09 Time 10:42 Rev Time 0.00
Received By jbrooks Date 2023-06-09 Time 07:58 Sent To  
Notes
2023-06-09 10:42:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36
 HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF
 APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED. (FL5374-R6)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 10:17 Rev Time 0.00
Received By jbrooks Date 2023-07-19 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-30 Cont ID  
Sent By jbrooks Date 2023-06-30 Time 10:46 Rev Time 0.00
Received By jbrooks Date 2023-06-22 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-14 Cont ID  
Sent By rmcphers Date 2023-06-14 Time 16:47 Rev Time 0.00
Received By rmcphers Date 2023-06-13 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-09 Cont ID  
Sent By jbrooks Date 2023-06-09 Time 10:42 Rev Time 0.00
Received By jbrooks Date 2023-06-08 Time 09:51 Sent To  
Notes
***NONE***