| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23060173 |
| | 6/16/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET PG-1: THE SUBMITTED MANUFACTURER???S |
| | SPECIFICATIONS FOR THE TANKLESS WATER HEATER INDICATE |
| | THE UNIT IS NOT APPROVED FOR OUTDOOR INSTALLATION- SEE |
| | PAGE 5. PLEASE SUBMIT SPECS FOR A UNIT APPROVED FOR |
| | OUTDOOR INSTALLATION OR REDESIGN THE PLANS TO SHOW THE |
| | UNIT IN AN INTERIOR LOCATION- SEC. G2448.1 FBC RES. |
| | PLEASE NOTE THE SPECS REQUIRE COMBUSTION AND VENTING |
| | FOR INDOOR INSTALLATIONS. |
| | |
| | 2) PG-1 GAS RISER CORRECTIONS: |
| | A) SHOW THE LENGTH OF EACH PIPE SEGMENT AND THE TOTAL |
| | LENGTH OF THE PIPE RUN FROM THE METER TO THE WATER |
| | HEATER- SEC. G2413.4.1 FBC RES. |
| | B) PROVIDE THE PIPE SIZING TABLE USED. PLEASE NOTE THE |
| | RESIDENTIAL LOW PRESSURE TABLE G2413.4 (1) LIMITS A |
| | ??-INCH STEEL PIPE SUPPLYING 266 BTU TO A TOTAL |
| | DEVELOPED LENGTH OF 10 FT., HOWEVER A 1-INCH PIPE CAN |
| | SUPPLY A 284 BTU LOAD AT 50 FT. PLEASE NOT THE ??-INCH |
| | PIPE DROPS MAY ALSO HAVE TO BE INCREASED IN SIZE |
| | DEPENDING ON THE TOTAL LENGTH OF THE SYSTEM. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW |
| | RANGE AND DRYER- SEC. G2407.1 FBC RES. IF USING THE |
| | STANDARD METHOD OF INDOOR AIR PER SEC. G2407.5.1 THE |
| | MINIMUM REQUIRED VOLUME IS 50 CU. FT. PER 1000 BTUH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |