Plan Review Details - Permit 23060173
Plan Review Stops For Permit 23060173
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-15 Cont ID  
Sent By lbond Date 2023-06-15 Time 14:05 Rev Time 0.00
Received By lbond Date 2023-06-15 Time 14:04 Sent To  
Notes
2023-06-15 14:12:46ITEM NO 7 PAGE S-3
 AS PER CONVERSATION WITH GC 6.15.2023 2:25

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-07-05 Cont ID  
Sent By ccole Date 2023-07-05 Time 12:53 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 10:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-06-26 Cont ID  
Sent By ccole Date 2023-06-26 Time 08:14 Rev Time 0.00
Received By ccole Date 2023-06-23 Time 17:09 Sent To  
Notes
2023-06-26 08:15:02 
 2ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23060173
 6/26/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET PG-1: BASED ON TABLE G2413.4(1) {402.4(2)} FBC
 RES. THE 3/4-INCH STEEL PIPE FROM THE METER TO THE
 WATER HEATER SHALL BE INCREASED TO 1-INCH. NO SIZE
 INCREASE REQUIRED FROM THE BRANCH PIPES TO THE RANGE
 AND DRYER. PLEASE NOTE I WAS UNABLE TO LOCATE AN AO
 SMITH MODEL ATHMOSN 120,000 BTU TANKLESS WATER HEATER
 OR THE MANUFACTURER'S WEBSITE, AND THE SMALLEST
 CAPACITY TANKLESS I COULD LOCATE WAS AN ATI MODEL AT
 140,000 BTUS. PLEASE CORRECT THE PLAN AND RISER
 DRAWING.
  
 2) PG-1: THE COMBUSTION AIR PLAN IS APPROVED HOWEVER
 PLEASE NOTE THAT SECS. G2407.1 EXCEPTION 1 AND G2439.5
 ALLOW FOR AN INTERIOR MAKEUP AIR OPENING TO BE USED FOR
 THE DRYER INSTEAD USING THE EXTERIOR OPENING PROPOSED.
 THE MINIMUM NET AREA INTERIOR OPENING INTO THE
 CONNECTING SPACE REQUIRED IS 100 SQ. INCHES. A 12X12
 LOUVER WILL NET 108 SQ. INCHES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By ccole Date 2023-06-16 Time 11:47 Rev Time 0.00
Received By ccole Date 2023-06-16 Time 11:06 Sent To  
Notes
2023-06-16 11:48:37 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23060173
 6/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET PG-1: THE SUBMITTED MANUFACTURER???S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATER INDICATE
 THE UNIT IS NOT APPROVED FOR OUTDOOR INSTALLATION- SEE
 PAGE 5. PLEASE SUBMIT SPECS FOR A UNIT APPROVED FOR
 OUTDOOR INSTALLATION OR REDESIGN THE PLANS TO SHOW THE
 UNIT IN AN INTERIOR LOCATION- SEC. G2448.1 FBC RES.
 PLEASE NOTE THE SPECS REQUIRE COMBUSTION AND VENTING
 FOR INDOOR INSTALLATIONS.
  
 2) PG-1 GAS RISER CORRECTIONS:
 A) SHOW THE LENGTH OF EACH PIPE SEGMENT AND THE TOTAL
 LENGTH OF THE PIPE RUN FROM THE METER TO THE WATER
 HEATER- SEC. G2413.4.1 FBC RES.
 B) PROVIDE THE PIPE SIZING TABLE USED. PLEASE NOTE THE
 RESIDENTIAL LOW PRESSURE TABLE G2413.4 (1) LIMITS A
 ??-INCH STEEL PIPE SUPPLYING 266 BTU TO A TOTAL
 DEVELOPED LENGTH OF 10 FT., HOWEVER A 1-INCH PIPE CAN
 SUPPLY A 284 BTU LOAD AT 50 FT. PLEASE NOT THE ??-INCH
 PIPE DROPS MAY ALSO HAVE TO BE INCREASED IN SIZE
 DEPENDING ON THE TOTAL LENGTH OF THE SYSTEM.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW
 RANGE AND DRYER- SEC. G2407.1 FBC RES. IF USING THE
 STANDARD METHOD OF INDOOR AIR PER SEC. G2407.5.1 THE
 MINIMUM REQUIRED VOLUME IS 50 CU. FT. PER 1000 BTUH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-07-05 Time   Rev Time 0.00
Received By amcgrego Date 2023-07-03 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-06-26 Time   Rev Time 0.00
Received By amcgrego Date 2023-06-21 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-06-16 Time   Rev Time 0.00
Received By lmarchan Date 2023-06-13 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2023-07-05 Cont ID  
Sent By ccole Date 2023-07-05 Time 10:55 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-06-26 Cont ID  
Sent By ccole Date 2023-06-26 Time 07:14 Rev Time 0.00
Received By ccole Date 2023-06-23 Time 17:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-06-16 Cont ID  
Sent By ccole Date 2023-06-16 Time 11:48 Rev Time 0.00
Received By ccole Date 2023-06-16 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-05 Cont ID  
Sent By ccole Date 2023-07-05 Time 12:53 Rev Time 0.00
Received By ccole Date 2023-07-05 Time 10:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-26 Cont ID  
Sent By ccole Date 2023-06-26 Time 07:21 Rev Time 0.00
Received By ccole Date 2023-06-23 Time 17:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-15 Cont ID  
Sent By lbond Date 2023-06-15 Time 14:05 Rev Time 0.00
Received By lbond Date 2023-06-15 Time 14:05 Sent To  
Notes
***NONE***