Plan Review Details - Permit 23051654
Plan Review Stops For Permit 23051654
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 11:32 Sent To  
Notes
2023-06-29 11:50:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. THIS SHOULD BE
 NOTED ON THE SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-21 Cont ID  
Sent By jcooley Date 2023-06-21 Time 18:44 Rev Time 0.00
Received By jcooley Date 2023-06-21 Time 17:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-07-25 Cont ID  
Sent By rwbrown Date 2023-07-25 Time 09:23 Rev Time 0.00
Received By rwbrown Date 2023-07-25 Time 09:23 Sent To  
Notes
2023-07-25 09:25:352ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 ALTHOUGH SOMEONE HAS SUBMITTED FOR THE SUB PERMIT, IT
 IS REQUIRED TO SUBMIT THE GAS DOCUMENTS WITH THIS
 MASTER. AS A SUB, THEY WILL USE THE DOCUMENTS FROM THE
 MASTER AS THEIRS. SEE BELOW AND SUBMIT THE INFORMATION.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS
 RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING
 APPLICABLE ITEMS. LOCATION OF SHUT-OFFS, THE PIPING
 MATERIAL, GAS PIPE SIZING METHOD AND BTU LOADS,
 (LABELING EXISTING AND NEW FOR CLARITY).
  
 2. 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE TIE DOWN
 INFORMATION FOR ANTI-FLOTATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By rwbrown Date 2023-06-16 Time 12:47 Rev Time 0.00
Received By rwbrown Date 2023-06-16 Time 12:47 Sent To  
Notes
2023-06-16 12:48:571ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS
 RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING
 APPLICABLE ITEMS. LOCATION OF SHUT-OFFS, THE PIPING
 MATERIAL, GAS PIPE SIZING METHOD AND BTU LOADS,
 (LABELING EXISTING AND NEW FOR CLARITY).
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-24 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-08 Cont ID  
Sent By avolcy Date 2023-07-08 Time 13:40 Rev Time 0.00
Received By avolcy Date 2023-06-12 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-07-25 Cont ID  
Sent By rwbrown Date 2023-07-25 Time 09:25 Rev Time 0.00
Received By rwbrown Date 2023-07-25 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-06-16 Cont ID  
Sent By rwbrown Date 2023-06-16 Time 12:47 Rev Time 0.00
Received By rwbrown Date 2023-06-16 Time 12:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 11:32 Sent To  
Notes
2023-06-29 11:40:08SIGNATURE WILL NEED TO BE CHECKED ON PREFAB GENERATOR
 PADS WHEN RESUBMITTED.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-07-08 Cont ID  
Sent By gvolcy Date 2023-07-08 Time 13:39 Rev Time 0.00
Received By avolcy Date 2023-07-08 Time 13:39 Sent To  
Notes
2023-07-08 13:39:5407.08.2023
  
 GENERATOR SHALL BE SCREENED FROM VIEW BY SHRUBS OR
 VEGETATION.