Plan Review Details - Permit 23051627
Plan Review Stops For Permit 23051627
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-26 Cont ID  
Sent By lbond Date 2023-06-26 Time 10:00 Rev Time 0.00
Received By lbond Date 2023-06-26 Time 10:00 Sent To  
Notes
2023-06-26 10:04:40FBC 107.2.1
  
 PLEASE CLARIFY SCOPE OF WORK BY PROVIDING EXISTING,
 DEMO AND PROPOSED FLOOR PLAN TO SCALE WITH NOTES
 INDICATING ALL CHANGES NOTED IN SCOPE OF WORK.
 LAYOUT SHOULD BEAR THE SIGNATURE AND CONTACT INFO OF
 THE CONTRACTOR RESPONSIBLE FOR THE DESIGN AND WORK.
  
 ANY QUESTION OR COMMENTS:
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By mpeterso Date 2023-06-27 Time 11:31 Rev Time 0.00
Received By mpeterso Date 2023-06-27 Time 11:23 Sent To  
Notes
2023-06-27 11:36:13ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL
 NEW OR ALTERED ELECTRIC WORK AND A NARRITIVE ELECTRIC
 WORK SCOPE. LOCATE ALL ELECTRIC EQUIPMENT, PANELS ,
 WATER HEATERS, AIR CONDITIONING EQUIPMENT AND
 APPLIANCES ON PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-02 Cont ID  
Sent By pleduc Date 2023-06-02 Time   Rev Time 0.00
Received By pleduc Date 2023-06-02 Time 11:00 Sent To  
Notes
2023-06-02 11:04:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION ON THE SCOPE OF WORK OF FLOOR
 TILE AND FLOOR COVERING ON THE CONTRACT; HOWEVER, THE
 IS FLOORING TYPE NOR A PRODUCT NAME AND IF APPLICABLE,
 A MANUFACTURER'S SPECIFICATION SHEET.
  
 TILE FLOORING OR FLOOR COVERING CAN HAVE DIFFERENT
 MEANINGS BUT FIOORING IS MANUFACTURED AROUND THE WORLD
 BUT NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE, PRODUCT NAME AND, IF APPLICABLE, THE PRODUCT SPEC
 SHEETS INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-27 Cont ID  
Sent By mpeterso Date 2023-06-27 Time 11:36 Rev Time 0.00
Received By mpeterso Date 2023-06-01 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-23 Cont ID  
Sent By ccole Date 2023-06-23 Time 13:05 Rev Time 0.00
Received By ccole Date 2023-06-23 Time 13:01 Sent To  
Notes
2023-06-23 13:06:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051627
 6/23/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) KITCHEN AND BATH PLANS: PROVIDE A WRITTEN SCOPE OF
 WORK FOR PLUMBING ALTERATIONS. CLARIFY WHICH FIXTURES
 ARE BEING REPLACED OR RELOCATED- SEC. 107.2.1 WPB.
 PLEASE NOTE THAT RISER DRAWINGS ARE REQUIRED FOR NEW
 PLUMBING PIPING INSTALLATIONS- SEC. 107.3.5.1.3 WPB.
 ALL CONTRACTOR OR QUALIFIER DRAWN PLANS SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE CONTRACTOR- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-26 Cont ID  
Sent By lbond Date 2023-06-26 Time 10:05 Rev Time 0.00
Received By lbond Date 2023-06-26 Time 10:05 Sent To  
Notes
***NONE***