Plan Review Details - Permit 23051624
Plan Review Stops For Permit 23051624
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By rmcphers Date 2023-06-28 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2023-06-28 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-24 Cont ID  
Sent By rmcphers Date 2023-07-24 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 14:21 Sent To  
Notes
2023-07-24 14:37:09RESTAURANT REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) EGRESS GATES CANNOT BE MORE THAN 4 FEET WIDE PER =
 FBC 1010.2 GATES. GATES SERVING THE MEANS OF EGRESS
 SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION. GATES USED AS A COMPONENT IN A MEANS OF EGRESS
 SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS.
 FBC 1010.1.1SIZE OF DOORS. THE MAXIMUM WIDTH OF A
 SWINGING DOOR LEAF SHALL BE 48 INCHES (1219 MM)
 NOMINAL. THE MINIMUM CLEAR HEIGHT OF DOOR OPENINGS
 SHALL BE NOT LESS THAN 80 INCHES
  
 2) DRAWING A2.0 SHOWS A FLOOR ELEVATION OF (1'6")
 SHOULD THAT HAVE BEEN REMOVED WHEN THE FLOOR IS NOT
 BEING RAISED?
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By rmcphers Date 2023-06-28 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2023-06-28 Time 15:38 Sent To  
Notes
2023-06-28 16:31:40RESTAURANT REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 2) DRAWING A0.1 SHOWS THE FRONT DOOR (BEYOND THE
 PROPERTY LINE) ENCHROACHING INTO THE RIGHT OF WAY - FBC
 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO
 THE PUBLIC RIGHT-OF-WAY.
  
 3) PLEASE PROVIDE DETAILS FOR THE RAISED FLOOR - FBC
 WPB 107.2
  
 4) PLEASE SHOW THE EXTERIOR EGRESS GATE SIZES - THE
 EGRESS PATH OF TRAVEL IS TO A PUBLIC WAY - FBC 1028.5
 ACCESS TO A PUBLIC WAY.
 THE EXIT DISCHARGE SHALL PROVIDE A DIRECT AND
 UNOBSTRUCTED ACCESS TO A PUBLIC WAY.
  
 5) PLEASE PROVIDE DETAILS FOR THE HANGING WOOD CEILING
 - SHOW ALL MATERIAL SIZES AND ATTACHMENTS TO THE
 EXISTING STRUCTURE - FBC WPB 107.2
  
 6) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE RAISED
 DINING AREA - FBC A 206.2.5 RESTAURANTS AND CAFETERIAS.
 IN RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE
 SHALL BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 7) PLEASE SHOW THE ACCESSIBLE BAR SEATING FOR BAR 108 -
 FBC A 226.2
  
 8) DRAWING A6.0 SHOWS THE BAR SEATING DETAIL - PLEASE
 PROVIDE A DETAIL FOR THE ACCESSIBLE BAR SEATING AREA -
 COUNTER HEIGHT, KNEE AND TOE CLEARANCE - FBC A 902
  
 9) PLEASE SHOW THE TOILET GRAB BAR HEIGHT TO THE TOP OF
 THE GRIPPING SURFACE (NOT TO THE CENTER OF THE GRAB
 BAR) - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 10) PLEASE SHOW THE STAIR HAND RAIL EXTENSION AT THE
 BOTTOM TO CONTINUE TO SLOPE PER FBC 1014.6 THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-08 Cont ID  
Sent By jleahy Date 2023-06-08 Time 18:07 Rev Time 0.00
Received By jleahy Date 2023-06-08 Time 17:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-07-05 Cont ID  
Sent By parking Date 2023-07-05 Time 13:20 Rev Time 0.00
Received By cseifer Date 2023-07-05 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-25 Cont ID  
Sent By pleduc Date 2023-07-25 Time   Rev Time 0.00
Received By pleduc Date 2023-07-24 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By pleduc Date 2023-06-01 Time   Rev Time 0.00
Received By pleduc Date 2023-06-01 Time 08:53 Sent To  
Notes
2023-06-01 14:54:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A0.2 & A2.0- THERE ARE INDICATIONS OF A SINGLE
 DOOR ALONG THE FRONT FENCE OF THE SIDE YEARD OUTSIDE
 SEATING AREA. THE DOOR IS INDICATED AS SWINGING INWARD.
  
 PREVIOUS APPROVED PLANS ON RECORD 16050258 SHOWED DOORS
 SWINGING OUTWARD.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS,
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
  
  
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET A2.0 & A5.0 - THERE ARE INDICATIONS OF
 GATES/DOORS ON THE EXTEIOR FENCES OF THE OUTSIDE AREA
 THAT ARE INDICATED AND REQUIRED AS EXITS.
  
 THE ARE NO INDICATIONS ON THE DOOR SCHEDULE OF THE EXIT
 HARDWARE/LOCKS/LATCHES THAT ARE IN COMPLINACE WITH THE
 REQUIREMENTS OF NFPA 101 CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET M1.1A - THERE ARE INDICATIONS OF NEW HOOD
 WORK.
  
 ANY WORK ON THE HOOD SYSTM SHALL BE UNER SEPARATE
 PERMIT & SHOP DRAWINGS PER NFPA 96.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLGMENT ON THE PLAN.
  
  
  
 4) SHEET A0.2 & A2.0 - THE OCCUPNACY HAS AN EXISTING
 FIRE SPRINKLER AND FIRE ALARM SYSTEM.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE
 CORRECTED/REPAIRED PER NFPA 13 & 72, UNDER SEPARATE
 PERMIT AND SHOP DRAWING BY FS/FA CONTRACTORS
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR & LIFE SAFETY PLAN.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-07-22 Cont ID  
Sent By ccole Date 2023-07-22 Time 08:44 Rev Time 0.00
Received By ccole Date 2023-07-22 Time 07:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By ccole Date 2023-06-07 Time 10:17 Rev Time 0.00
Received By ccole Date 2023-06-06 Time 16:47 Sent To  
Notes
2023-06-07 10:18:311ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23051624
 6/7/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.4: PLEASE INCREASE THE 3/4--INCH SUPPLY
 PIPES TO THE WATER HEATERS TO 1-INCH BASED ON TABLE
 402.4(2) FBC FG.
  
 2) P0.4 & P2.1A: INDICATE HOW COMBUSTION AIR WILL BE
 PROVIDED FOR THE GAS-FIRED COOKING APPLIANCES AND
 PROVIDE CALCULATIONS- SEC. 304.21 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-21 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-06 Cont ID  
Sent By hmoser Date 2023-07-06 Time 06:44 Rev Time 0.00
Received By aoliver Date 2023-05-31 Time 13:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-06-23 Cont ID  
Sent By hmoser Date 2023-06-23 Time 12:53 Rev Time 0.00
Received By hmoser Date 2023-06-22 Time 14:33 Sent To  
Notes
2023-06-23 12:52:48PASS PROVISO
 KITCHEN HOODS AND REFRIGERATION NEED
 SEPARATE APPLICATION, PLAN AND PERMIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6676
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-07-22 Cont ID  
Sent By ccole Date 2023-07-22 Time 08:42 Rev Time 0.00
Received By ccole Date 2023-07-22 Time 07:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By ccole Date 2023-06-07 Time 09:53 Rev Time 0.00
Received By ccole Date 2023-06-06 Time 13:09 Sent To  
Notes
2023-06-07 09:59:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051624
 6/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY EFFICIENCY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR, AT A MINIMUM, THE PERMIT APPLICATION FOR
 SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING PLAN
 APPROVAL. IF A CONTRACTOR IS NOT CURRENTLY SELECTED THE
 INSTALLATION, A PERMIT APPLICATION CAN BE SUBMITTED TBD
 (TO BE DETERMINED). THE COMPLETED APPLICATION SHALL BE
 EMAILED TO [email protected] . YOU WILL THEN
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS P0.2, P0.3, P0.5, P0.6, P1.1A, P1.1B: REFER
 TO SEC. 1003.3.1 FBC P- GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED. THE PLANS SHOW DRAINAGE
 FROM FIXTURES SUCH AS HAND SINKS, FLOOR SINKS UNDER ICE
 MACHINES, AND COOLER EVAPORATORS DISCHARGING INTO THE
 GREASE WASTE LINE. PLEASE RE-ROUTE THE DRAINAGE FROM
 THE FIXTURES LISTED BELOW TO THE SANITARY SYSTEM:
 HAND SINKS- A61, A77, B14, B33, B43
 FLOOR SINKS RECEIVING DRAINAGE FROM B43, B43.1, B43.2,
 B48.2, B53.2.
  
 3) P0.2: BASED ON COMMENT #1 ABOVE THE HAND SINKS SHALL
 BE REMOVED FROM THE GREASE WASTE CALCULATIONS- SEC.
 1003.3.1 FBC P.
  
 4) P2.1A, P2.1B: FOR CLARIFY PLEASE NOTE THE LOCATIONS
 OF THE WATER HEATERS USING THE NUMBER 9 PER THE NOTES
 ON THE PLANS- SEC. 107.2.1 WPB.
  
 5) P0.1 & P0.2: BASED ON SEC. 607.1.1 FBC P,
 TEMPERATURE LIMITING DEVICES SHALL BE PROVIDED FOR THE
 NEW WATER HEATERS. TYPICALLY A MASTER THERMOSTATIC
 MIXING VALVE CAN BE INSTALLED TO MEET COMPLIANCE.
 PLEAASE SHOW THE DEVICE IN THE DETAIL AND PIPING
 CONNECTIONS.
  
 6) P0.2, P2.1A, & P2.1B: PLEASE SHOW THE BATHROOM
 FIXTURE WATER SUPPLY LINES POINTS OF CONNECTIONS TO THE
 NEW BRANCH WATER LINES- SEC. 107.2.1 WPB.
  
 7) A2.1: PLEASE SHOW THE DIMENSIONS OF THE WATER CLOSET
 AND LAVATORY CLEAR FLOOR SPACES AS REQUIRED BY SECS.
 604.3 & 606.2 FBC ACC. BASED ON THE MALE AND FEMALE
 ACCESSIBLE STALL WIDTHS SHOWN ON THE PLANS, IT APPEARS
 THE CLEAR FLOOR SPACES REQUIRED FOR THE WATER CLOSETS
 WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT ALLOWED
 PER SEC. 604.3.2.
  
 8) A2.1: PLEASE SHOW THE HEIGHTS OF THE GRAB BARS
 MEASURED FROM THE FINISHED FLOORS TO THE TOPS OF THE
 BAR GRIPPING SURFACES- SEC. 609.4 FBC ACC.
  
 9) A2.1: PLEASE SHOW THE ADA LAVATORY KNEE CLEARANCE
 WILL BE 11 INCHES DEEP MINIMUM AT 9 INCHES ABOVE THE
 FINISH FLOOR OR GROUND, AND 8 INCHES DEEP MINIMUM AT 27
 INCHES ABOVE THE FINISH FLOOR OR GROUND.
  
 10) PLEASE ADD THE ENERGY COMPLIANCE DATA FOR THE WATER
 HEATERS TO THE ENERGYGAUGE REPORT- SEC. C101.5 & TABLE
 C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-24 Cont ID  
Sent By rmcphers Date 2023-07-24 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 14:54 Sent To  
Notes
2023-07-22 08:44:01PLUMBING SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-08 Cont ID  
Sent By jleahy Date 2023-06-08 Time 18:07 Rev Time 0.00
Received By jleahy Date 2023-06-08 Time 17:05 Sent To  
Notes
2023-06-06 14:36:59PLUMBING AND GAS SIGNATURES PASSED.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By cibaven Date 2023-06-16 Time 11:48 Rev Time 0.00
Received By cibaven Date 2023-06-16 Time 11:46 Sent To  
Notes
2023-06-16 11:48:03ZONING AND PLANNING - 1ST REVIEW
 1. THE SURVEY SHALL BE WITHIN ONE (1) YEAR OLD, PLEASE
 SUBMIT AN UPDATED SURVEY.
  
 2. THE PROJECT IS LOCATED WITHIN THE LOFTIN DISTRICT
 (LD-5). PER SEC. 94-125, TABLE IV-31, PLEASE PROVIDE A
 PLAN TO SHOW THE 25% AREA OF THE SITE THAT IS THE
 REQUIRED AS PRIVATE OPEN SPACE. THE LD-5 PERMITS THE
 INTERIOR COURTYARD TYPE AS PRIVATE OPEN SPACE, PLEASE
 HIGHLIGHT THE AREAS REQUIRED FOR THIS TYPE OF OPEN
 SPACE STANDARDS, SHOWN ON SEC. 94-109, TABLE IV-7, SUCH
 AS 20% MIN. VEGETATED AREA, AND 20% MAX. OVERHEAD
 COVER.
  
 3. A MINIMUM OF 5 FEET SETBACK IS REQUIRED FROM THE
 PROPERTY LINE TO THE NEAREST FACADE OR VERTICAL
 SURFACE. PLEASE CONFIRM THAT THERE ARE NO WALLS OR ANY
 VERTICAL SURFACES BESIDES FENCE AND GATES WITHIN THE 5
 FEET SETBACK. FEEL FREE TO ADD SETBACK LINE TO SITE
 PLAN.
  
 4. PLEASE PROVIDE DETAIL OF FENCE TO ENSURE IT MEETS
 HEIGHT AND MATERIALS REQUIREMENTS. FENCES PROPOSED IN
 REAR SETBACKS SHALL BE A MAXIMUM HEIGHT OF 6 FEET. REAR
 AND SIDE CHAIN LINK FENCES SHALL BE VINYL-COATED AND
 SHALL INCLUDE A TOP RAIL.
  
 5. SHEET A0.1 SITE PLAN DOES NOT SHOW ENCLOSED SPACE ON
 THE WEST SIDE AND BACK OF THE PROPERTY COMPARED TO
 SHEETS L1 OVERALL LANDSCAPE PLAN AND L1 OVERALL
 PLANTING PLAN. IF EXISTING, IT SHOULD SHOW ON SURVEY,
 IF PROPOSED, PLEASE MAKE SURE ALL PLANS ARE CONSISTENT.
 IF THE ENCLOSED AREA IS PROPOSED, PLEASE LABEL THE AREA
 TO CLARIFY WHAT KIND SPACE IS BEEN PROPOSED, AND ADD
 AND SQ. FT. OF THE AREA.
  
 6. OUTDOOR MECHANICAL EQUIPMENT SUCH AS BUT NOT LIMITED
 TO GARBAGE OR TRASH RECEPTACLES SHALL COMPLY WITH
 SUBSECTION 94-315(A). SCREENING SHALL BE CONSTRUCTED OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS. PLANS FOR THE LAYOUT OF TRASH RECEPTACLES
 SHALL BE IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS
 SET FORTH IN SEC. 94-315,FIGURE XIV-3. ALL WALL MOUNTED
 EQUIPMENT SHALL BE SCREENED FROM VIEW WITH A SCREEN
 EQUAL TO THE HEIGHT OF THE EQUIPMENT.
  
 7. MECHANICAL EQUIPMENT AND APPURTENANCES NECESSARY TO
 THE OPERATION OR MAINTENANCE OF THE BUILDING OR
 STRUCTURE ITSELF SUCH AS, BUT NOT LIMITED TO, COOLING
 TOWERS, ELEVATORS, STAIRS AND MECHANICAL PENTHOUSES,
 VENT STACKS AND ANTENNAS SHALL BE ENCLOSED AND SCREENED
 IN SUCH A MANNER THAT THE ENCLOSURE IS DESIGNED AS AN
 INTEGRAL PART OF THE OVERALL BUILDING DESIGN. ROOF PLAN
 SHOWS MECHANICAL EQUIPMENT, SCREENING WITH DETAILS WILL
 NEED TO BE PROVIDED.
  
 8. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 9. A SEPARATE LANDSCAPE PERMIT IS REQUIRED.
  
 FEEL FREE TO PROVIDE WRITTEN RESPONSES TO COMMENTS
 ABOVE IN YOUR NEXT SUBMITTAL. FOR ANY QUESTIONS OR
 CLARIFICATIONS, FEEL FREE TO REACH OUT DIRECTLY. PLEASE
 NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY RESULT
 IN ADDITIONAL COMMENTS.
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER / ZONING AND PLANNING
 [email protected]
 561-822-1402
  