Plan Review Details - Permit 23051448
Plan Review Stops For Permit 23051448
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-02 Cont ID  
Sent By jbrooks Date 2023-06-02 Time 12:53 Rev Time 0.00
Received By jbrooks Date 2023-06-02 Time 08:16 Sent To  
Notes
2023-06-02 12:56:30JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 21-0422.02 IS APPROVED FOR NEW CONSTRUCTION ONLY AND
 NOT VALID FOR USE IN A REROOF APPLICATION. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA???S FOR THE PROPOSED METAL ROOF PANEL
 SYSTEM TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R35
 HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF
 APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
 4. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-06-22 Cont ID  
Sent By amhamilt Date 2023-06-22 Time 11:33 Rev Time 0.00
Received By amhamilt Date 2023-06-22 Time 11:32 Sent To  
Notes
2023-06-22 11:33:37THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 STANDING SEAM METAL ROOF NOT APPROPRIATE PLEASE REVISE
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-23 Cont ID  
Sent By lmarchan Date 2023-06-23 Time 11:39 Rev Time 0.00
Received By lmarchan Date 2023-05-31 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-02 Cont ID  
Sent By jbrooks Date 2023-06-02 Time 12:56 Rev Time 0.00
Received By jbrooks Date 2023-06-02 Time 12:27 Sent To  
Notes
***NONE***