Plan Review Details - Permit 23051403
Plan Review Stops For Permit 23051403
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By rmcdouga Date 2023-06-30 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2023-06-30 Time 13:20 Sent To  
Notes
2023-06-30 13:55:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS
 107.2.1.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE,
 LAMINATE, WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS
 OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED
 CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
 6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-12 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By pleduc Date 2023-06-21 Time   Rev Time 0.00
Received By pleduc Date 2023-06-21 Time 11:20 Sent To  
Notes
2023-06-05 11:55:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE APPLICATION DOES NOT HAVE A UNIT # NOR IS THERE
 A FLOOR PLAN INDICATING THE UNIT # AS WELL AS THE AREAS
 THAT ARE PROPOSED TO HAVE TILE INSTALLED.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE THE UNIT # AND FLOOR PLAN.
  
  
 2) THERE IS AN INDICATION OF REPLACE FLOOR TILE.
  
 THERE IS NO INDICATION OF WHAT TYPE OF TILE AND SIZE IS
 PROPOSED. TILE CAN HAVE DIFFERENT MEANINGS AND NEEDS TO
 CLARIFIED.
  
 THERE IS ALSO AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED TILE FLOORING.
  
 TILE FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING TYPE, PRODUCT NAME AND IF APPLICABLE THE
 PRODUCT SPEC SHEETS INDICATING THE FIRE BEHAVIOR
 RATING.
  
 IF THE PROPOSED TILE FLOORING IS PORCELAIN/CERAMIC
 TILE, NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC
 SHEETS WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-10 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By rmcdouga Date 2023-06-30 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2023-06-02 Time 11:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By rmcdouga Date 2023-06-30 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2023-06-30 Time 13:20 Sent To  
Notes
2023-06-30 13:21:15NO PLANS WERE SUBMITTED.