Plan Review Details - Permit 23051287
Plan Review Stops For Permit 23051287
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-05-26 Cont ID  
Sent By pleduc Date 2023-05-26 Time   Rev Time 0.00
Received By pleduc Date 2023-05-26 Time 09:01 Sent To  
Notes
2023-05-26 09:02:03FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED
 CODE: 603
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/
 DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR
 LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  