Plan Review Details - Permit 23051214
Plan Review Stops For Permit 23051214
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jleahy Date 2023-07-29 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-23 Cont ID  
Sent By jleahy Date 2023-06-23 Time 09:14 Rev Time 0.00
Received By jleahy Date 2023-06-23 Time 09:09 Sent To  
Notes
2023-06-23 09:17:05FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS ARE NOT REAL CLEAR AS TO HOW MANY FIXTURES ARE
 BEING INSTALLED UNDER THIS PERMIT.
  
 PLEASE SUBMIT A COST BREAK DOWN OF THE FIXTURES AND
 COST INCLUDING LABOR AND ALL MATERIALS AND FIXTURES FOR
 THIS PERMIT.
  
 (15K)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-20 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-12 Cont ID  
Sent By aoliver Date 2023-07-12 Time 07:38 Rev Time 0.00
Received By aoliver Date 2023-06-20 Time 13:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jleahy Date 2023-07-29 Time 07:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-23 Cont ID  
Sent By jleahy Date 2023-06-23 Time 09:19 Rev Time 0.00
Received By jleahy Date 2023-06-23 Time 09:09 Sent To  
Notes
2023-06-23 09:20:17FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NOT ABLE TO VERIFY SIGNATURES ON PLANS.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-11 Cont ID  
Sent By llouie Date 2023-07-11 Time   Rev Time 0.00
Received By llouie Date 2023-07-11 Time   Sent To  
Notes
2023-07-11 16:01:08** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR IN ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ALL NEW POLE FIXTURES MUST MATCH THE APPROVED SITE
 PLAN AND MUST BE SETBACK A MINIMUM OF 5 FT. FROM THE
 PROPERTY LINE.
  
 2.) PLEASE IDENTIFY WHICH POLE FIXTURES ARE NEW AND
 WHICH ARE EXSITING IN THE SITE PLAN.
  
 3.) POLE FIXTURE SETBACK DISTANCE FROM THE EDGE OF THE
 POLE TO THE PROPERTY LINE SHALL BE PROVIDED IN THE
 PLANS. THE DISTANCE (FOR ALL NEW FIXTURES MUST BE
 CONSISTENT WITH THE SETBACK REQUIREMENTS OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS)).
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTATC LINDA LOUIE @ 561.822.1458 OR [email protected]
 IF THERE ARE QUESTIONS.
  
 * Z = CPD (PALM BEACH RIVERSTONE - RESIDENTIAL POD)
  
 * MASTER PERMIT #20120803
  