Plan Review Details - Permit 23051198
Plan Review Stops For Permit 23051198
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-05-27 Cont ID  
Sent By cpuell Date 2023-05-27 Time 09:31 Rev Time 0.00
Received By cpuell Date 2023-05-27 Time 09:31 Sent To  
Notes
2023-05-27 09:32:03ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 07:42 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jwitmer Date 2023-06-28 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2023-06-28 Time 08:46 Sent To  
Notes
2023-06-28 08:54:48COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 07:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jwitmer Date 2023-06-28 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2023-06-28 Time 08:47 Sent To  
Notes
2023-06-28 08:48:27WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23051198
 ADD: 525 OKEECHOBEE BLVD # 1200
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 28TH/ 2023
 ACTION: DENIED
  
 1) SHEET A0-01 INDEX & PROJECT INFORMATION.
 1A) CODE ANALYSIS II APPLICABLE BUILDING CODES LIST A-L
 CODES, THE FLORIDA FAMILY OF CODES AS THE FLORIDA 2017
 CODES SIXTH EDITION. PLEASE UPDATE TO THE 2020 FBC
 (FAMILY OF CODE) 7TH EDITION. THE STATE OF FLORIDA
 ADOPTED STATEWIDE ON DEC. 31/2020 THE 7TH EDITION OF
 THE FLORIDA CODES.
  
 2) IV GENERAL BUILDING FEATURES LIST EVERYTHING IN THE
 IBC, AGAIN WE ARE IN THE 7TH EDITION OF THE FLORIDA
 BUILDING CODES.
  
 3) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS
 F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL REQUIRE CORE
 DRILLING OF THE POST TENSION FLOORS. THERE IS NO
 MENTION OF POST TENSION FLOORS THAT ARE TO HAVE
 PENETRATION OF THE CONCRETE ARE REQUIRED TO HAVE THE
 SLAB X-RAYED TO LOCATE TENDONS. CONFORMANCE. 2020
 EXISTING BUILDING CODE, LEVEL-1 ALTERATION 701.2,
 LEVEL-2 ALTERATION 801.3, & LEVEL-3 ALTERATIONS
 901.2COMPLIANCE. AN EXISTING BUILDING OR PORTION
 THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING
 BECOMES LESS SAFE THAN ITS EXISTING CONDITION.
 4) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS
 F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL PENETRATE
 THE FIRE RATED CONCRETE SLAB. SHEET A7-02 UL DETAILS DO
 NOT HAVE ASSEMBLIES FOR THE FLOOR PENETRATIONS. 2020
 FBC-BUILDING CODE SECTION 714.4.1.2 THROUGH-PENETRATION
 FIRESTOP SYSTEM.
 5) NEITHER SHEETS A1-12 OR A0-21 SHOW EITHER A SIDE
 APPROACH OR FRONT APPROACH TO THE BREAK ROOM SINK OR
 MICROWAVE. PLEASE SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 305.4 KNEE AND TOE CLEARANCES.
 305.5 POSITION.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-28 Cont ID  
Sent By mpeterso Date 2023-07-28 Time 11:39 Rev Time 0.00
Received By mpeterso Date 2023-07-28 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-20 Cont ID  
Sent By mpeterso Date 2023-06-20 Time 01:58 Rev Time 0.00
Received By mpeterso Date 2023-06-20 Time 01:35 Sent To  
Notes
2023-06-20 02:04:13ELECTRIC REVIEW FAILED
  
 1) ALL MEP DRAWINGS DO NOT DETAIL THE REQUIRED DIGITAL
 SIGNATURE AS REQUIRED. PLEASE CORRECT AS OUTLINED
 BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
  
 2) PLEASE DETAIL FIXED WALL RECEPTACLES IN ACCORDANCE
 WITH NEC 210.71 MEETING ROOMS
 (B) RECEPTACLE OUTLETS REQUIRED.
 THE TOTAL NUMBER OF RECEPTACLE OUTLETS, INCLUDING FLOOR
 OUTLETS AND RECEPTACLE OUTLETS IN FIXED FURNITURE,
 SHALL NOT BE LESS THAN AS DETERMINED IN (1) AND (2).
 THESE RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 LOCATED AS DETERMINED BY THE DESIGNER OR BUILDING
 OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS.
 RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE
 WITH 210.52(A)(1) THROUGH (A)(4)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 14:41 Sent To  
Notes
2023-07-10 14:42:06FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES
 AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-05-26 Cont ID  
Sent By pleduc Date 2023-05-26 Time   Rev Time 0.00
Received By pleduc Date 2023-05-25 Time 15:06 Sent To  
Notes
2023-05-26 08:56:53FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES
 AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-28 Cont ID  
Sent By mpeterso Date 2023-07-28 Time 11:51 Rev Time 0.00
Received By mpeterso Date 2023-07-06 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-06-28 Time   Rev Time 0.00
Received By amcgrego Date 2023-05-23 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-26 Cont ID  
Sent By cmontell Date 2023-07-26 Time 13:36 Rev Time 0.00
Received By cmontell Date 2023-07-26 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By cmontell Date 2023-06-27 Time 13:21 Rev Time 0.00
Received By cmontell Date 2023-06-27 Time 13:22 Sent To  
Notes
2023-06-27 13:22:23SEE ELECTRIC NOTES
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-07-11 Cont ID  
Sent By rwbrown Date 2023-07-11 Time 10:41 Rev Time 0.00
Received By rwbrown Date 2023-07-11 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By rwbrown Date 2023-06-16 Time 07:38 Rev Time 0.00
Received By rwbrown Date 2023-06-16 Time 07:38 Sent To  
Notes
2023-06-16 07:40:201ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1/613.1 - KEYED NOTE #1 ON PAGE P-1
 SAYS SEE PAGE P-2 FOR WATER HEATER DETAILS AND THERE IS
 NO PAGE P-2. PROVIDE DETAIL OF WATER HEATER. NOTE THAT
 THE WATER HEATER MUST HAVE A MIXING DEVICE THAT MEETS
 ASSE 1017 PER THIS SECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-28 Cont ID  
Sent By mpeterso Date 2023-07-28 Time 11:50 Rev Time 0.00
Received By mpeterso Date 2023-07-28 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-20 Cont ID  
Sent By mpeterso Date 2023-06-20 Time 02:11 Rev Time 0.00
Received By mpeterso Date 2023-06-20 Time 02:11 Sent To  
Notes
2023-06-20 02:12:20SIGNATURE REVIEW FAILED
  
 1) ALL MEP DRAWINGS DO NOT DETAIL THE REQUIRED DIGITAL
 SIGNATURE AS REQUIRED. PLEASE CORRECT AS OUTLINED
 BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  