Plan Review Details - Permit 23051185
Plan Review Stops For Permit 23051185
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-07-06 Cont ID  
Sent By jgomez Date 2023-07-06 Time 11:10 Rev Time 0.00
Received By jgomez Date 2023-07-06 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-05 Cont ID  
Sent By jgomez Date 2023-07-05 Time 10:18 Rev Time 0.00
Received By jgomez Date 2023-07-05 Time 10:08 Sent To  
Notes
2023-07-05 10:19:50RESIDENTIAL(R3) REROOF FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051185
 1827 PINEHURST DR
  
 PREVIOUS COMMENT:
 2-RAS 117 CALCULATIONS SUBMITTED:
 REVISED CALCULATIONS STILL SHOW THE DESIGN PRESSURES
 LOWER THAN THE DESIGN PRESSURES SHOWN ON THE FIRST
 CALCULATIONS SUBMITTED WHEN THE BUILDING EXPOSURE WAS
 ASSUMED TO BE EXPOSURE B. REVISE AS REQUIRED.
 ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES ARE SO LOW
 COMPARED TO TABLE R301.2(2) AND TABLE R301.2(2)
 FBC-RESIDENTIAL.
 ALSO, ENGINEER TO PROVIDE THE DESIGN PRESSURES FOR ALL
 FOUR ROOF ZONES.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 RESPONSE:
 CALCULATIONS WERE REVISED AND FASTENER SPACING
 SPECIFIED FOR ZONE 1' DOESN'T MATCH FASTENER SPACING
 FOR FASTENING OPTION #2 FOR -52.5 PSF SHOWN ON NOA
 18-0919.12 AS SPECIFIED BY THE ENGINEER ON PAGE 2 OF
 WIND UPLIFT CALCULATIONS SUBMITTED. REVISE AS REQUIRED
 TO MATCH. NOTE: COORDINATE ENHANCED NAILING FOR THE
 OTHER ZONES AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 3- DIGITAL SIGNATURE REVIEW:
 A)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE
 IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR
 G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/...
 AND REVISE AS REQUIRED TO MATCH.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 B)IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED
 OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE .
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/...
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-27 Cont ID  
Sent By jgomez Date 2023-06-27 Time 15:36 Rev Time 0.00
Received By jgomez Date 2023-06-27 Time 13:26 Sent To  
Notes
2023-06-27 15:36:41RESIDENTIAL(R3) REROOF FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051185
 1827 PINEHURST DR
  
 PREVIOUS COMMENT:
 2-RAS 117 CALCULATIONS SUBMITTED:
 ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES SHOWN ON
 THE REVISED RAS 117 CALCULATIONS ARE LOWER FOR BUILDING
 EXPOSURE "C" THAN THE DESIGN PRESSURES GIVEN FOR
 EXPOSURE "B". DESIGN PRESSURES CAN NOT BE LOWER.
 PROVIDE CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISED CALCULATIONS STILL SHOW THE DESIGN PRESSURES
 LOWER THAN THE DESIGN PRESSURES SHOWN ON THE FIRST
 CALCULATIONS SUBMITTED WHEN THE BUILDING EXPOSURE WAS
 ASSUMED TO BE EXPOSURE B. REVISE AS REQUIRED.
 ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES ARE SO LOW
 COMPARED TO TABLE R301.2(2) AND TABLE R301.2(2)
 FBC-RESIDENTIAL.
 ALSO, ENGINEER TO PROVIDE THE DESIGN PRESSURES FOR ALL
 FOUR ROOF ZONES.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-20 Cont ID  
Sent By jgomez Date 2023-06-20 Time 10:11 Rev Time 0.00
Received By jgomez Date 2023-06-16 Time 18:49 Sent To  
Notes
2023-06-20 10:12:03RESIDENTIAL(R3) REROOF THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051185
 1827 PINEHURST DR
  
 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED
 ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 2-RAS 117 CALCULATIONS SUBMITTED:
 A)THE BUILDING EXPOSURE IS "C" NOT "B". REVISE AS
 REQUIRED AND REVISE THE DESIGN PRESSURES ACCORDINGLY.
 SEC. R301.2.1.4 FBC-RESIDENTIAL. SEC. R301.2.1.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES SHOWN ON
 THE REVISED RAS 117 CALCULATIONS ARE LOWER FOR BUILDING
 EXPOSURE "C" THAN THE DESIGN PRESSURES GIVEN FOR
 EXPOSURE "B". DESIGN PRESSURES CAN NOT BE LOWER.
 PROVIDE CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-05 Cont ID  
Sent By jgomez Date 2023-06-05 Time 13:01 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 18:05 Sent To  
Notes
2023-06-05 13:01:53RESIDENTIAL(R3) SECOND REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051185
 1827 PINEHURST DR
  
 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED
 ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 RAS 117 CALCULATIONS SUBMITTED:
 A)THE BUILDING EXPOSURE IS "C" NOT "B". REVISE AS
 REQUIRED AND REVISE THE DESIGN PRESSURES ACCORDINGLY.
 SEC. R301.2.1.4 FBC-RESIDENTIAL. SEC. R301.2.1.2
 FBC-RESIDENTIAL.
  
 B)BASED ON CALCULATED DESIGN PRESSURES, THE SELECTED
 ASSEMBLY CAN NOT BE USED BECAUSE ACCORDING TO SEC. 8.1
 OF RAS 117, THE DESIGN PRESSURES OF THE PRODUCT
 APPROVAL SHOULD BE APPLICABLE TO ZONE 1' OR 1. REVISE
 AS REQUIRED.
  
 C)ENGINEER OF RECORD TO PROVIDE SKETCH SHOWING THE
 DIMENSIONS FOR ALL THE ROOF ZONES APPLICABLE TO THIS
 PROJECT AS REQUIRED BY NEW ROOF ZONES ON FIGURE
 R301.2(7) FBC-RESIDENTIAL.
  
 3- ENGINEER'S SIGNATURE REVIEW:
 A) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE
 IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR
 G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/. AND
 REVISE AS REQUIRED TO MATCH.
  
 B) IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED
 OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE .
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGIN
 EERING-DOCUMENTS/
  
 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 15:57 Rev Time 0.00
Received By jgomez Date 2023-05-25 Time 15:31 Sent To  
Notes
2023-05-25 15:57:30RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051185
 1827 PINEHURST DR
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- SHINGLES ROOFING UNDERLAYMENT
 PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED
 ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 3- CONTRACTOR REROOFING AFFIDAVIT IS NOT ACCEPTABLE AT
 PLAN REVIEW. THIS IS SUPPOSED TO BE DONE AFTER THE WORK
 IS DONE. COORDINATE WITH CHIEF BUILDING INSPECTOR
 BEFORE DOING THE JOB FOR AFFIDAVIT REQUIREMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status F Date 2023-07-06 Cont ID  
Sent By jgomez Date 2023-07-06 Time 11:10 Rev Time 0.00
Received By jgomez Date 2023-07-06 Time 10:35 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-05 Cont ID  
Sent By jgomez Date 2023-07-05 Time 10:20 Rev Time 0.00
Received By jgomez Date 2023-07-05 Time 10:08 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-27 Cont ID  
Sent By jgomez Date 2023-06-27 Time 16:01 Rev Time 0.00
Received By jgomez Date 2023-06-27 Time 13:26 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-20 Cont ID  
Sent By jgomez Date 2023-06-20 Time 10:12 Rev Time 0.00
Received By jgomez Date 2023-06-12 Time 09:04 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-05 Cont ID  
Sent By jgomez Date 2023-06-05 Time 13:01 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 18:05 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 15:57 Rev Time 0.00
Received By jgomez Date 2023-05-23 Time 12:18 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-07-06 Cont ID  
Sent By jgomez Date 2023-07-06 Time 11:10 Rev Time 0.00
Received By jgomez Date 2023-07-06 Time 11:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-07-05 Cont ID  
Sent By jgomez Date 2023-07-05 Time 10:20 Rev Time 0.00
Received By jgomez Date 2023-07-05 Time 10:19 Sent To  
Notes
2023-07-05 10:20:44DIGITAL SIGNATURE REVIEW:
 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE
 IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR
 G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/...
 AND REVISE AS REQUIRED TO MATCH.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 2- IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED
 OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE .
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/...
  
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-27 Cont ID  
Sent By jgomez Date 2023-06-27 Time 15:56 Rev Time 0.00
Received By jgomez Date 2023-06-27 Time 15:56 Sent To  
Notes
2023-06-27 16:00:40SIGNATURE REVIEW:
 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE
 IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR
 G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/...
 AND REVISE AS REQUIRED TO MATCH.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 2- IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED
 OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE .
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/...
  
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 08:49 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-05 Cont ID  
Sent By jgomez Date 2023-06-05 Time 13:23 Rev Time 0.00
Received By jgomez Date 2023-06-05 Time 13:17 Sent To  
Notes
2023-06-05 13:23:48SIGNATURE REVIEW:
 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE
 IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR
 G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/...
 AND REVISE AS REQUIRED TO MATCH.
  
 2- IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED
 OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE .
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/...
  
 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  