Plan Review Details - Permit 23051183
Plan Review Stops For Permit 23051183
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 10:35 Rev Time 0.00
Received By jbrooks Date 2023-07-25 Time 07:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-18 Cont ID  
Sent By jbrooks Date 2023-07-18 Time 10:26 Rev Time 0.00
Received By jbrooks Date 2023-07-18 Time 08:00 Sent To  
Notes
2023-07-18 10:28:16JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL5259-R39 (NON-HVHZ).
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39
 (NON- HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER
 OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES, ATTACHMENT
 LIMITATIONS & INSTALLATION APPROVED ASSEMBLIES. SELECT
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1
 DIRECT-TO-DECK TABLE 4A: ALLOWABLE DESIGN PRESSURES,
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 PAGE #6 & 7 OR ATTACHMENT LIMITATION SYSTEM FROM
 5.8.3.2 MECHANICALLY-ATTACHED BASE SHEET TABLE 4B
 ALLOWABLE DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS
 IN TILE ROOF APPLICATIONS PAGES #8-14.
 3. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 17-0322.03 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF TILE ADHESIVE TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By jbrooks Date 2023-07-14 Time 10:24 Rev Time 0.00
Received By jbrooks Date 2023-07-14 Time 08:05 Sent To  
Notes
2023-07-14 10:24:44JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 22-0201.13 COVERS MULTIPLE ATTACHMENT SYSTEMS;
 MECHANICAL, ADHESIVE AND MORTAR SET. SELECT SYSTEM TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 SUBMITTED LETTER DOES NOT SPECIFY FASTENER TYPE WITH
 ATTACHMENT RESISTANCE.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R37
 HAS BEEN REVISED TO FL5259-R39. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF
 APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED. (FL5374-R6)
 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE TILE ADHESIVE TO BE USED.
 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 10:36 Rev Time 0.00
Received By jbrooks Date 2023-07-19 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-18 Cont ID  
Sent By jbrooks Date 2023-07-18 Time 10:28 Rev Time 0.00
Received By jbrooks Date 2023-07-14 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-14 Cont ID  
Sent By jbrooks Date 2023-07-14 Time 10:24 Rev Time 0.00
Received By jbrooks Date 2023-07-13 Time 17:30 Sent To  
Notes
***NONE***