Plan Review Details - Permit 23051114
Plan Review Stops For Permit 23051114
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By rmcdouga Date 2023-06-27 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2023-06-27 Time 15:48 Sent To  
Notes
2023-06-27 15:52:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS. SUBMIT A SITE
 PLAN OR SURVEY SHOWING THE LOCATION OF THE GENERATOR
 AND NOTE ON THE DRAWING THAT THE GENERATOR EXHAUST IS
 REQUIRED TO BE 10 FEET FROM OPENINGS INTO THE BUILDING.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 15:07 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 14:53 Sent To  
Notes
2023-06-05 15:13:12FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30 445 FBC 107.2.1
  
 SHOW SIZE OF GENERATOR 16,22,24????
  
 SHOW LOAD CALCULATION FOR LOADS ON GENERATOR.
  
 SIGN AND DATE PLAN FOR SUBMITTAL.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2023-07-19 Cont ID  
Sent By rwbrown Date 2023-07-19 Time 07:17 Rev Time 0.00
Received By rwbrown Date 2023-07-19 Time 07:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-18 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-27 Cont ID  
Sent By rmcdouga Date 2023-06-27 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2023-05-23 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-06-16 Cont ID  
Sent By hmoser Date 2023-06-16 Time 11:24 Rev Time 0.00
Received By hmoser Date 2023-06-16 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-07-19 Cont ID  
Sent By rwbrown Date 2023-07-19 Time 07:17 Rev Time 0.00
Received By rwbrown Date 2023-07-19 Time 07:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 15:13 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 15:13 Sent To  
Notes
2023-06-05 15:14:11NO PLANS SUBMITTED FOR REVIEW. SIGN AND DATE ALL PLANS
 SUBMITTED TO THE CITY.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-26 Cont ID  
Sent By lgelman Date 2023-06-26 Time 10:57 Rev Time 0.00
Received By lngelman Date 2023-06-26 Time 10:56 Sent To  
Notes
2023-06-26 10:57:09PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE
 PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM
 BOUNDARY LINES.
  
 ***** REVIEWED BY *****
 LINDSEY GELMAN
 561-822-1275
 [email protected]