Plan Review Details - Permit 23051075
Plan Review Stops For Permit 23051075
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-07-18 Cont ID  
Sent By cpuell Date 2023-07-18 Time 13:06 Rev Time 0.00
Received By cpuell Date 2023-07-18 Time 13:06 Sent To  
Notes
2023-07-18 13:07:26SUITES ADDRESSES ASSIGNED TO PARCEL, AREAS OF WORK ARE
 FOR 4805 4815 AND 4829 S DIXIE HWY

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-06-29 Cont ID  
Sent By cpuell Date 2023-06-29 Time 16:59 Rev Time 0.00
Received By cpuell Date 2023-06-29 Time 16:59 Sent To  
Notes
2023-06-29 17:01:454 ADDRESSES WERE PROPOSED FOR THIS JOB, 4805 4815 4829
 AND 4885 S DIXIE HWY, THE ADDRESS OF 4885 S DIXIE HWY
 IS NEEDED FOR THE WAREHOUSE BUILDING TO THE SOUTH, WE
 NEED APPROVAL FOR ALL 4 ADDRESSES WHICH WE HAVE NOT
 RECIEVED, PLEASE CONTACT [email protected] OR CALL
 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-05-27 Cont ID  
Sent By cpuell Date 2023-05-27 Time 12:37 Rev Time 0.00
Received By cpuell Date 2023-05-27 Time 12:37 Sent To  
Notes
2023-05-27 12:38:52CURRENTLY THERE IS ONLY ONE ADDRESSES ON THAT PROPERTY,
 ADDRESSES NEED TO BE ESTABLISHED FOR AREA INDIACATED ON
 THE PLANS AS SUITES. PLEASE HAVE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESS ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 06:49 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 06:40 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-07-03 Cont ID  
Sent By jwitmer Date 2023-07-03 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2023-07-03 Time 07:55 Sent To  
Notes
2023-07-03 08:36:02COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By jwitmer Date 2023-06-07 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2023-06-07 Time 10:59 Sent To  
Notes
2023-06-07 11:02:52COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 06:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-03 Cont ID  
Sent By jwitmer Date 2023-07-03 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2023-07-03 Time 07:54 Sent To  
Notes
2023-07-03 08:35:10WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23051075
 ADD: 4805 S DIXIE HWY
 CONT: SDJ & ASSOCIATES, LLC
 TEL: 561-396-5813
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 07TH/2023
 ACTION: DENIED
  
 1) 2ND REQUEST. CONTRACTORS RESPONSIBILITY, CONTACT
 CAROLINE PUELL AT 561-805-6659 FOR APPROVAL OF PROPOSED
 ADDRESSES. THIS PROPERTY CONTROL NUMBER ONLY HAS ONE
 SITUS ADDRESS OF 4805 S DIXIE HWY. SEPARATE TENANT
 ADDRESSES WILL BE REQUIRED. SEE ADDRESSING STOP FOR
 FURTHER INFORMATION. 2020 FBC-B 501.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
  
 2-7) COMPLIED.
  
  
  
  
 8) 2ND REQUEST. MISSING PRODUCT APPROVAL. COMPONENTS &
 CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING
 PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
  
 9) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 10) 2ND REQUEST. DELEGATED ENGINEERING. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL
 HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 13) COMPLIED.
  
 14) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By jwitmer Date 2023-06-07 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2023-06-07 Time 10:59 Sent To  
Notes
2023-06-07 11:02:18WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23051075
 ADD: 4805 S DIXIE HWY
 CONT: SDJ & ASSOCIATES, LLC
 TEL: 561-396-5813
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 07TH/2023
 ACTION: DENIED
  
 1) THIS PROPERTY CONTROL NUMBER ONLY HAS ONE SITUS
 ADDRESS OF 4805 S DIXIE HWY. SEPARATE TENANT ADDRESSES
 WILL BE REQUIRED. SEE ADDRESSING STOP FOR FURTHER
 INFORMATION. 2020 FBC-B 501.2 ADDRESS IDENTIFICATION.
 NEW AND EXISTING BUILDINGS SHALL BE PROVIDED WITH
 APPROVED
 ADDRESS IDENTIFICATION.
  
 2) SHEET A2.1 SHOWS THE 2 ACCESSIBLE RESTROOMS 103 &
 104 WITH IN SWING DOORS. TOILET ROOM DOORS. 2020
 FBC-ACCESSIBILITY CODE FIGURE 604.8.1.6 SHOWS AN
 OUTSWING DOOR. PLEASE REVIEW SECTION 603.2.3. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCES REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE FOR
 INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING. WHAT IS MISSING IS THE REQUIRED 30X48 INCH
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY
 AT A 45% ANGLE TO THE DOOR ENTRANCE.
  
 3) SHEET A2.1 NOR A0.03 ADA RESTROOM DETAILS PROVIDE
 DETAILS FOR THE DRINKING FOUNTAINS. 2020
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. CODE.
 SPOUT OUTLETS SHALL COMPLY WITH 602.4 SPOUT HEIGHT. 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND FOR
 WHEELCHAIR BOUND INDIVIDUALS.
  
 4) I DIDN???T FIND A ROOM SCHEDULE, RESTROOMS AND
 SERVICE SINKS NEED TO SHOW COMPLIANCE WITH: 2020 FBC-B
 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT
 OF THE BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN
 BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT
 IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT
 SURFACE.
  
 4A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 5A) A0.10 CODE INFORMATION, BUILDING DATA STATES
 BUILDING SPRINKLERED. DOES THIS MEAN IS GOING TO BE
 SPRINKLERED OR IS GOING TO BE SPRINKLERED?
  
 5B) SHEET A0.10 BUILDING DATA STATES THE CONSTRUCTION
 TYPE IS TYPE IV OR HEAVY TIMBER CONSTRUCTION, THE FLOOR
 PLAN INDICATES EXISTING CMU BLOCK WALLS. SEE 2023
 SECTION602.4 HEAVY TIMBER CONSTRUCTION.
  
 6) SHEET A2.2 SHOWS A WAREHOUSE APPROXIMATELY 2,800
 SQUARE FEET. 2020 FBC-BUILDING SECTION 903.2.9(5) GROUP
 S-1 OCCUPANCIES USED FOR STORAGE OF UPHOLSTERED
 FURNITURE OR MATTRESSES EXCEEDS 2,500 SQ. FT. REQUIRE
 AN AUTOMATIC SPRINKLER SYSTEM.
  
 7) SHEET A2.01 SHOWS NEW WINDOWS AND EXTERIOR DOORS.
 SHEET A3.03 SHOWS DESIGN PRESSURES BUT THEY ARE NOT
 STATED IF THEY ARE IN VASD OR VULT. 2020 FBC-B 1603.1.4
 WIND DESIGN CRITERIA. WIND DESIGN DATA IS FOUND ONS-1.
  
 8) MISSING PRODUCT APPROVAL. COMPONENTS & CLADDING.
 PLEASE SUBMIT THE COMPONENTS AND CLADDING PRODUCT
 APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
  
 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 10) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 13) SHEET S-1 INDICATES NICHE ENTRANCE, PLEASE LOCATE
 ON SHEET A2.03 THE ROOF PLAN WHERE THIS WORK IS TO
 OCCUR? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 14) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-30 Cont ID  
Sent By jleahy Date 2023-06-30 Time 11:05 Rev Time 0.00
Received By jleahy Date 2023-06-30 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-26 Cont ID  
Sent By jleahy Date 2023-05-26 Time 08:22 Rev Time 0.00
Received By jleahy Date 2023-05-26 Time 07:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-07-05 Cont ID  
Sent By parking Date 2023-07-05 Time 13:22 Rev Time 0.00
Received By cseifer Date 2023-07-05 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-30 Cont ID  
Sent By clfranci Date 2023-06-30 Time   Rev Time 0.00
Received By clfranci Date 2023-06-30 Time   Sent To  
Notes
2023-06-30 07:23:26FIRE COMMENTS WERE ADDRESSES AND OR CORRECTED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-24 Cont ID  
Sent By pleduc Date 2023-05-24 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 13:52 Sent To  
Notes
2023-05-24 15:44:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.11 & E 4.0 - THERE IS AN INDICATION ON THE
 LIFE SAFETY SHEET AT DOOR 109 OF "PROVIDE NOT AN EXIT
 SIGN, HOWEVER, ON THE ELECTICAL SHEET THERE IS AN
 INDICATION OF AN EXIT SIGN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 0.11, A2.02 & A2.01 - THERE ARE NO
 INDICATIONS OF A DOOR SCHEDULE ON THESE SHEETS NOR ANY
 OTHER.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A DOOR SCHEDULE INDICATING COMPLIANCE
 WITH APPLICABLE NFPA 101 OCCUPANCY CHAPTERS INCLUDING
 CH 7, MEANS OF EGRESS TO INCLUDE HARDWARE, LOCKS &
 LATCHES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-18 Cont ID  
Sent By cpuell Date 2023-07-18 Time 13:07 Rev Time 0.00
Received By cpuell Date 2023-07-17 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-13 Cont ID  
Sent By asangele Date 2023-07-13 Time 09:52 Rev Time 0.00
Received By asangele Date 2023-07-13 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-14 Cont ID  
Sent By hmoser Date 2023-06-14 Time 10:17 Rev Time 0.00
Received By hmoser Date 2023-05-22 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-06-14 Cont ID  
Sent By hmoser Date 2023-06-14 Time 10:17 Rev Time 0.00
Received By hmoser Date 2023-06-14 Time 08:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-29 Cont ID  
Sent By ccole Date 2023-06-29 Time 09:21 Rev Time 0.00
Received By ccole Date 2023-06-29 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-05-24 Cont ID  
Sent By ccole Date 2023-05-24 Time 14:57 Rev Time 0.00
Received By ccole Date 2023-05-24 Time 13:07 Sent To  
Notes
2023-05-24 14:57:471ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051075
 5/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-1.0: REFER TO SEC. 607.2.2 FBC P AND SHOW THE
 RECIRCULATION PUMP LOCATION AND RECIRCULATION LINE
 CONNECTIONS IN THE WATER HEATER DETAIL.
  
 2) A2.01: DOORS 103 & 104 SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACES FOR THE ACCESSIBLE LAVATORIES- SEC.
 603.2.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-30 Cont ID  
Sent By jleahy Date 2023-06-30 Time 11:06 Rev Time 0.00
Received By jleahy Date 2023-06-30 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-14 Cont ID  
Sent By hmoser Date 2023-06-14 Time 08:59 Rev Time 0.00
Received By hmoser Date 2023-06-14 Time 08:59 Sent To  
Notes
2023-06-07 11:05:53ARCHITECTURAL & STRUCTURAL SHEETS DIGITALLY SIGNED &
 SEALED. 6-07-23 J WITMER

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By asangele Date 2023-07-13 Time 09:52 Rev Time 0.00
Received By asangele Date 2023-07-13 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-06-13 Cont ID  
Sent By asangele Date 2023-06-13 Time 10:37 Rev Time 0.00
Received By asangele Date 2023-06-13 Time 10:37 Sent To  
Notes
***NONE***