Plan Review Details - Permit 23051068
Plan Review Stops For Permit 23051068
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-01 Cont ID  
Sent By jgomez Date 2023-06-01 Time 10:13 Rev Time 0.00
Received By jgomez Date 2023-06-01 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-31 Cont ID  
Sent By jgomez Date 2023-05-31 Time 15:57 Rev Time 0.00
Received By jgomez Date 2023-05-31 Time 15:15 Sent To  
Notes
2023-05-31 15:58:03RESIDENTIAL REROOF SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051068
 6143 WHALTON ST
  
 PREVIOUS COMMENT:
 2-HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE
 INSTALLATION AS REQUIRED BY SEC. R905.3.7.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE
 WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE
 INSTALLATION MANUAL (6TH EDITION) OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
 ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE
 PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND
 CLEARLY MARK ATTACHMENT METHOD.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL5374-R6 WAS SUBMITTED BUT
 ATTACHMENT METHOD WAS NOT SPECIFIED/MARKED ON THE
 PRODUCT APPROVAL. CLEARLY MARK ATTACHMENT METHOD.
  
 PREVIOUS COMMENT:
 3- ROOF TILE UNDERLAYMENT FL5259-R37 SUBMITTED. THIS
 FLORIDA PRODUCT APPROVAL WAS REVISED WITH FL5259-R38.
 SUBMIT CURRENT PRODUCT APPROVAL AND CLEARLY MARK WHICH
 UNDERLAYMENT IS GOING TO BE USED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL5259-R38 WAS SUBMITTED BUT
 UNDERLAYMENT WAS NOT SPECIFIED/MARKED ON THE PRODUCT
 APPROVAL. CLEARLY MARK UNDERLAYMENT TO BE INSTALLED.
  
 PREVIOUS COMMENT:
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT NOTE: THIS
 TOWNHOUSE REQUIRES A MINIMUM OF 5/8" THICK AND 4'-0"
 WIDE FIRE RETARDANT PLYWOOD SHEATHING BETWEEN UNITS.
 (MASTER BUILDING PERMIT #03042334). ALSO, ROOF
 SHEATHING NAILS TO BE RING SHANK NAILS WITH MINIMUM
 SIZE AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NAIL SIZE SPECIFIED BY GABRIEL PRIETO ON EMAIL DATED
 05/30/23 DOESN'T COMPLY WITH SEC. R803.2.3.1
 FBC-RESIDENTIAL. 1-1/4" RING SHANK COILED ROOFING NAIL
 DOESN'T COMPLY. SEE SEC. R803.2.3.1 FBC-RESIDENTIAL FOR
 MINIMUM SIZE REQUIRED DEPENDING ON THE PLYWOOD
 THICKNESS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 15:26 Rev Time 0.00
Received By jgomez Date 2023-05-25 Time 14:27 Sent To  
Notes
2023-05-25 15:27:05RESIDENTIAL REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23051068
 6143 WHALTON ST
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- ROOF TILE NOA 22-0201.07 SUBMITTED. CLEARLY
 MARK/SPECIFY TILE FASTENING METHOD AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R3012.1
 FBC-RESIDENTIAL. IF SPECIFYING SCREWS, THEN SPECIFY THE
 NUMBER AND SIZE OF SCREWS TO BE USED FOR ALL ROOF
 ZONES. IF SPECIFYING FOAM ADHESIVE, THEN CLEARLY
 MARK/SPECIFY PADDY SIZE.
 NOTE: NEED FOAM ADHESIVE PRODUCT APPROVAL IF USING
 FOAM. SEE ROOF TILE NOA FOR LISTED FOAM.
  
 2-HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE
 INSTALLATION AS REQUIRED BY SEC. R905.3.7.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE
 WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE
 INSTALLATION MANUAL (6TH EDITION) OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
 ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE
 PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND
 CLEARLY MARK ATTACHMENT METHOD.
  
 3- ROOF TILE UNDERLAYMENT FL5259-R37 SUBMITTED. THIS
 FLORIDA PRODUCT APPROVAL WAS REVISED WITH FL5259-R38.
 SUBMIT CURRENT PRODUCT APPROVAL AND CLEARLY MARK WHICH
 UNDERLAYMENT IS GOING TO BE USED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT NOTE: THIS
 TOWNHOUSE REQUIRES A MINIMUM OF 5/8" THICK AND 4'-0"
 WIDE FIRE RETARDANT PLYWOOD SHEATHING BETWEEN UNITS.
 (MASTER BUILDING PERMIT #03042334). ALSO, ROOF
 SHEATHING NAILS TO BE RING SHANK NAILS WITH MINIMUM
 SIZE AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.???
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-01 Cont ID  
Sent By jgomez Date 2023-06-01 Time 10:13 Rev Time 0.00
Received By jgomez Date 2023-06-01 Time 09:36 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-31 Cont ID  
Sent By jgomez Date 2023-05-31 Time 15:58 Rev Time 0.00
Received By jgomez Date 2023-05-30 Time 17:46 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 15:27 Rev Time 0.00
Received By jgomez Date 2023-05-23 Time 09:06 Sent To I
Notes
***NONE***