| Plan Review Stops For Permit 23051012 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-24 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-24 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2023-07-24 11:38:05 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE 5-5.5 RISER SHOWS 1200 AMPERE BREAKERS FROM | | | SERVICE AND GENERATOR FEEDING A 400 AMPERE TRANSFER | | | SWITCH. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-06-30 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-06-30 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2023-06-30 14:10:04 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE ATS SPECIFICATIONS. FBC 107.3.5 | | | | | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | TO BE LOW. WPB F.B.C. 109.3 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN P. PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-07-21 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-06-27 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2023-06-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2023-06-27 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-07-20 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-07-20 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-07-20 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-26 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-26 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2023-06-26 08:48:32 | 1ST GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT THE | | | GAS RISER THAT INCLUDES THE GAS LINE TO THE GENERATOR | | | AS WELL AS THE SYSTEM TO THE BUILDING FOR REVIEW. | | | INCLUDE THE MATERIALS USED, PIPE LENGHTS AND SIZING | | | METHOD. INCLUDE THE LOCATION OF THE REGULATORS. | | | | | | 2. 2017 WPB AMEND 107.3.5.3 (13) - ON A SITE PLAN, SHOW | | | THE ROUTING OF THE GAS LINE FROM THE METER TO THE | | | GENERATOR. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-19 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-14 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-07-11 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-22 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-22 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-07-11 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-11 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-11 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2023-07-11 13:48:06 | MECHANICAL PLAN REVIEW FAIL | | | | | | SHOW EXHAUST PER FBC SEC 107 | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-20 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-07-20 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-07-20 |
Time |
07:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-26 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-26 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-07-11 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-11 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-11 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2023-07-14 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2023-07-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-14 13:48:19 | * SCOPE OF REVIEW IS FOR EMERGENCY GENERATOR ONLY. | | | | | | * REFERENCE: PB 1837D (PALM BEACH RIVERSTONE CPD). |
|
|