Plan Review Details - Permit 23050946
Plan Review Stops For Permit 23050946
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 08:32 Rev Time 0.00
Received By lbond Date 2023-06-20 Time 08:39 Sent To  
Notes
2023-06-20 08:33:55BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23050946
  
 REVIEWED: 6.20.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS PLAN REVIEW: FAILED
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING:
  
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 08:32 Rev Time 0.00
Received By lbond Date 2023-06-20 Time 08:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By pleduc Date 2023-05-30 Time   Rev Time 0.00
Received By pleduc Date 2023-05-30 Time 15:35 Sent To  
Notes
2023-05-30 15:47:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF INSTALL NEW TILE
 THROUGHOUT THE UNIT, HOWEVER, THERE IS NO TILE TYPE
 INDICATED NOR, IF APPLICABLE, A MANUFACTURER'S
 SPECIFICATION SHEET NOR A PRODUCT NAME.
  
 THERE IS ALSO NO INDICATION OF A SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT NOR THE PRODUCT NAME.
  
 TILEL FLOORING CAN HAVE DIFFERENT MEANINGS OF THE
 PTODUCT TYPE AND IS MANUFACTURED AROUND THE WORLD BUT
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE NAME AND, IF APPLICABLE, THE PRODUCT SPEC SHEETS
 INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS INDICATION OF BATHROOM WORK THAT MAY
 INVOLVE A FIRE RATED TENANT/CORRIDOR SEPARATION WALL.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE
 MAINTAINED & REPAIRED IF DAMAGED.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON
 THE PLAN.
  
  
  
 3) THERE IS INDICATION OF PAINTING THE UNIT WITH 2
 COATES OF PAINT WORK. THERE ARE FIRE SPRINKLER HEADS
 AND FIRE ALARM DEVICES AND SMOKE ALARMS IN THE UNIT.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE
 CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP
 DRAWING BY FS/FA CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON
 THE PLAN.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 08:39 Rev Time 0.00
Received By lbond Date 2023-05-26 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By ccole Date 2023-06-01 Time 11:01 Rev Time 0.00
Received By ccole Date 2023-06-01 Time 10:52 Sent To  
Notes
2023-06-01 11:02:021ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050946
 6/1/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REMODELING PLAN SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON WHO DREW THE PLAN- SEC. 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 08:30 Rev Time 0.00
Received By lbond Date 2023-06-20 Time 09:00 Sent To  
Notes
2023-06-20 08:31:34SEE PLUMBING NOTE REGARDING SIGNATURE-