| 2023-05-30 15:47:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION OF INSTALL NEW TILE |
| | THROUGHOUT THE UNIT, HOWEVER, THERE IS NO TILE TYPE |
| | INDICATED NOR, IF APPLICABLE, A MANUFACTURER'S |
| | SPECIFICATION SHEET NOR A PRODUCT NAME. |
| | |
| | THERE IS ALSO NO INDICATION OF A SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT NOR THE PRODUCT NAME. |
| | |
| | TILEL FLOORING CAN HAVE DIFFERENT MEANINGS OF THE |
| | PTODUCT TYPE AND IS MANUFACTURED AROUND THE WORLD BUT |
| | NOT ALL ARE TESTED AND MEETING LISTED AND NFPA |
| | STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | TYPE NAME AND, IF APPLICABLE, THE PRODUCT SPEC SHEETS |
| | INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 2) THERE IS INDICATION OF BATHROOM WORK THAT MAY |
| | INVOLVE A FIRE RATED TENANT/CORRIDOR SEPARATION WALL. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE |
| | MAINTAINED & REPAIRED IF DAMAGED. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON |
| | THE PLAN. |
| | |
| | |
| | |
| | 3) THERE IS INDICATION OF PAINTING THE UNIT WITH 2 |
| | COATES OF PAINT WORK. THERE ARE FIRE SPRINKLER HEADS |
| | AND FIRE ALARM DEVICES AND SMOKE ALARMS IN THE UNIT. |
| | |
| | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE |
| | CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP |
| | DRAWING BY FS/FA CONTRACTORS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON |
| | THE PLAN. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |