Plan Review Details - Permit 23050883
Plan Review Stops For Permit 23050883
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-07 Cont ID  
Sent By lbond Date 2023-07-07 Time 08:59 Rev Time 0.00
Received By lbond Date 2023-07-07 Time 08:59 Sent To  
Notes
2023-07-07 09:00:14PROVISO
 PROVIDE INFO ABOUT FLOORING AS INDICATED IN FIRE
 COMMENTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-29 Cont ID  
Sent By lbond Date 2023-06-29 Time 11:22 Rev Time 0.00
Received By lbond Date 2023-06-29 Time 11:22 Sent To  
Notes
2023-06-29 11:24:07PROVISO
  
 FBC 107.2.1
 PLEASE CLARIFY
 TYPE OF INSULATION FOR EXTERIOR WALL
 TYPE OF NEW FLOORING AND UNDERLAYMENT WITH SPECS
  
 ANY QUUESTIONS:
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-19 Cont ID  
Sent By pleduc Date 2023-05-19 Time   Rev Time 0.00
Received By pleduc Date 2023-05-19 Time 15:57 Sent To  
Notes
2023-05-19 16:01:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION TO REPAIR SUBFLOORS BUT NO
 INDICATION OF A FINNISHED FLOOR
  
 FOR CLARIFICATION PURPOSES, WILL YOU BE PROVIDING THE
 FINISHED FLOOR INSTALLATION?
  
  
 IF SO, A MANUFACTURER'S SPECIFICATION SHEET AND A
 PRODUCT NAME FOR THE PROPOSED FLOORING IS REQUIRED..
  
 FFLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL
 ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 NAME AND THE PRODUCT SPEC SHEETS INDICATING THE FIRE
 BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-10 Cont ID  
Sent By lmarchan Date 2023-07-10 Time 15:41 Rev Time 0.00
Received By lmarchan Date 2023-07-06 Time 13:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-29 Cont ID  
Sent By lbond Date 2023-06-29 Time 11:24 Rev Time 0.00
Received By lbond Date 2023-05-18 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-06-29 Cont ID  
Sent By lbond Date 2023-06-29 Time 11:24 Rev Time 0.00
Received By lbond Date 2023-06-29 Time 11:24 Sent To  
Notes
***NONE***