| 2023-05-18 11:21:23 | RESIDENTIAL(R2) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R10 |
| | SUBMITTED CAN NOT BE USED FOR THIS BUILDING. THIS |
| | BUILDING IS LOCATED IN EXPOSURE D WITH A WIND SPEED OF |
| | 170MPH. ACCORDING TO BASE SHEET ATTACHMENT SYSTEM ON |
| | PAGE 25 OF 25 THIS PRODUCT APPROVAL CAN NOT BE USED FOR |
| | ROOF ZONE #3. IT SAYS N/A FOR ROOF ZONE 3. |
| | THE SUBMITTED ENGINEERING CALCULATIONS CAN NOT BE USED |
| | EITHER BECAUSE THE PRODUCT APPROVAL DOESN'T ALLOW |
| | ENHANCED FASTENING. |
| | NEED TO PROVIDE PRODUCT APPROVAL WITH AN ASSEMBLY THAT |
| | MEETS OR EXCEEDS THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES OR THAT ALLOWS ENHANCED FASTENING. |
| | F.A.C. 61G20.3.001. SEC. 1609.1 FBC-BUILDING. |
| | |
| | 2- ROOF TO WALL CONNECTIONS: |
| | THE BUILDING HAS A VALUATION OF MORE THAN $300,000. |
| | NEED TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS |
| | REQUIRED BY SEC. 706.8 FBC-EXISTING BUILDING. |
| | STORM ROOFING, INC LETTER SUBMITTED IS NOT ACCEPTABLE. |
| | THE ESTIMATE FOR THE ROOF TO WALL EVALUATION AND |
| | INSTALLATION OF CONNECTIONS AT GABLE ENDS OR ALL |
| | CORNERS HAS TO BE DONE BY LICENSED GENERAL OR BUILDING |
| | CONTRACTOR NOT BY ROOFING CONTRACTOR. |
| | ANOTHER OPTION IS TO SHOW THAT THE EXISTING ROOF TO |
| | WALL CONNECTIONS MEET OR EXCEED FLORIDA BUILDING CODE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |