Plan Review Details - Permit 23050669
Plan Review Stops For Permit 23050669
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-30 Cont ID  
Sent By rmcdouga Date 2023-06-30 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2023-06-30 Time 11:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By rmcdouga Date 2023-06-21 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2023-06-21 Time 14:28 Sent To  
Notes
2023-06-21 14:57:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON
 THE SURVEY. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL
 AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-17 Cont ID  
Sent By jcooley Date 2023-05-17 Time 18:09 Rev Time 0.00
Received By jcooley Date 2023-05-17 Time 17:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-06 Cont ID  
Sent By avolcy Date 2023-07-06 Time 11:11 Rev Time 0.00
Received By avolcy Date 2023-06-26 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-21 Cont ID  
Sent By rmcdouga Date 2023-06-21 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2023-05-15 Time 11:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-21 Cont ID  
Sent By rmcdouga Date 2023-06-21 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2023-06-21 Time 14:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-06 Cont ID  
Sent By avolcy Date 2023-07-06 Time 11:11 Rev Time 0.00
Received By avolcy Date 2023-07-06 Time 11:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By gvolcy Date 2023-06-07 Time 17:03 Rev Time 0.00
Received By avolcy Date 2023-06-07 Time 17:03 Sent To  
Notes
2023-06-07 17:07:0406.07.2023 - FAILED
  
  
 PROVIDE SIDE SETBACK FOR GENERATOR ON SURVEY. IT CANNOT
 ENCROACH MORE THAN 4FT INTO REQUIRED SETBACK.
  
 WHERE IS THE UNDERGROUND LP TANK DOME PROPOSED? WILL IT
 BE IN THE MIDDLE OF DRIVEWAY?
  
 **** REVIEWD BY ****
 GAISHA (ANNE) VOLCY
 PLANNER
 [email protected]
  