Plan Review Details - Permit 23050632
| Plan Review Stops For Permit 23050632 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-28 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-28 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2023-06-28 12:48:32 | OFFICE BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IS THE OFFICE TRAILER TEMPORARY OR PERMANENT ? - FBC | | | 102.2 | | | | | | 2) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE | | | PARKING SPACE TO THE OFFICE ENTRY - FBC A 206.2.1 | | | FBC A 402.2 COMPONENTS. ACCESSIBLE ROUTES SHALL CONSIST | | | OF ONE OR MORE OF THE FOLLOWING COMPONENTS: WALKING | | | SURFACES WITH A RUNNING SLOPE NOT STEEPER THAN 1:20, | | | DOORWAYS, RAMPS, CURB RAMPS EXCLUDING THE FLARED SIDES, | | | ELEVATORS, AND PLATFORM LIFTS. | | | | | | 3) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE | | | FOLLOWING INFORMATION 107.2.5 SITE PLAN. THE | | | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION | | | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING | | | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND | | | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT | | | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED | | | FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE | | | AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND | | | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN | | | ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY | | | LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY | | | PROPOSED WATER RETAINING SWALES) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-06-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-06-15 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-06-15 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2023-06-15 11:48:05 | ELECTRIC REVIEW FAILED | | | | | | 1) WORK SCOPE IS NOT CLEAR. IS THIS TRAILER TEMPORARY? | | | WHAT IS ITS USE? PLEASE PROVIDE A NARRATIVE RESPONSE. | | | FBC 107.2 | | | 2) PLEASE PROVIDE AN ELECTRICAL SITE PLAN DETAILING | | | ELECTRIC EQUIPMENT LOCATIONS. IE METER, MAIN PANEL, | | | ETC. FBC 107.2 | | | 3) PLEASE PROVIDE ELECTRIC FLOOR PLAN FOR TRAILER. | | | DETAIL ALL ELECTRIC LOADS, LOAD CALCULATIONS FOR | | | TRAILER AND UPSTREAM PANEL AT BUILDING, AND PANEL | | | SCHEDULES FOR EACH. NEC 215.5 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-06-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-06-08 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2023-06-08 12:17:28 | FIRE PREVENTION COMMENT: | | | | | | PER NFPA 241, MUST BE MIN. 20' FROM BLDG. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-08 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-07-08 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-06-07 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-06-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-14 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-14 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2023-06-14 16:35:41 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23050632 | | | 6/14/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLUMBING PLAN: INDICATE THE TYPE AND SIZE OF WATER | | | SERVICE LINE, POINT OF CONNECTION TO THE EXISTING | | | BUILDING SERVICE, UNDERGROUND OR ABOVEGROUND | | | INSTALLATION, AND LOCATIONS OF SHUTOFF VALVES AND | | | REQUIRED BACKFLOW PREVENTER- SECS. 602.1, 603.2, & | | | 608.3 FBC P. INDICATE THE TYPE AND SIZE OF BACKFLOW | | | PREVENTER TO BE INSTALLED- SEC. 608.3 FBC P. | | | | | | 2) PLUMBING PLAN: SHOW THE TYPE AND SIZE OF TEMPORARY | | | SEWER LINE AND CLEANOUT LOCATIONS- SECS. 701.2, 701.3 & | | | 708.1.2 FBC P. | | | | | | 3) PLUMBING RISER: THE INTERIOR PIPING, FIXTURES AND | | | WATER HEATER SHOWN IN THE RISERS APPEAR TO BE FACTORY | | | INSTALLED IN THE MANUFACTURED BUILDING. PLEASE PLACE A | | | NOTE ON THE PLAN TO CLARIFY- SEC. 107.2.1 WPB. | | | | | | 4) THE CORRECTED PLUMBING PLAN AND RISER DRAWING SHALL | | | BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR | | | OR QUALIFIER WHO PREPARED THE DESIGN- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-06-28 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-28 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-07-08 |
|
|
Cont ID |
|
| Sent By |
gvolcy |
Date |
2023-07-08 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-07-08 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2023-07-08 15:09:32 | 07.08.2023 - FAILED | | | | | | PROVIDE SETBACKS FOR THE STRUCTURE ON THE SURVEY. | | | | | | PROVIDE A NARRATIVE WITH THE USE AND THE DURATION FOR | | | WHICH THE STRUCTURE WILL BE THERE. | | | | | | PROVIDE ELEVATIONS FOR THE PROPOSED TRAILER. | | | | | | ** REVIEWED BY:** | | | GAISHA (ANNE-CLERISSE) VOLCY | | | PLANNER | | | [email protected] |
|
|
|