Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By rmcphers Date 2023-06-28 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2023-06-28 Time 12:38 Sent To  
Notes
2023-06-28 12:48:32OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IS THE OFFICE TRAILER TEMPORARY OR PERMANENT ? - FBC
 102.2
  
 2) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING SPACE TO THE OFFICE ENTRY - FBC A 206.2.1
 FBC A 402.2 COMPONENTS. ACCESSIBLE ROUTES SHALL CONSIST
 OF ONE OR MORE OF THE FOLLOWING COMPONENTS: WALKING
 SURFACES WITH A RUNNING SLOPE NOT STEEPER THAN 1:20,
 DOORWAYS, RAMPS, CURB RAMPS EXCLUDING THE FLARED SIDES,
 ELEVATORS, AND PLATFORM LIFTS.
  
 3) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-15 Cont ID  
Sent By mpeterso Date 2023-06-15 Time 11:48 Rev Time 0.00
Received By mpeterso Date 2023-06-15 Time 11:47 Sent To  
Notes
2023-06-15 11:48:05ELECTRIC REVIEW FAILED
  
 1) WORK SCOPE IS NOT CLEAR. IS THIS TRAILER TEMPORARY?
 WHAT IS ITS USE? PLEASE PROVIDE A NARRATIVE RESPONSE.
 FBC 107.2
 2) PLEASE PROVIDE AN ELECTRICAL SITE PLAN DETAILING
 ELECTRIC EQUIPMENT LOCATIONS. IE METER, MAIN PANEL,
 ETC. FBC 107.2
 3) PLEASE PROVIDE ELECTRIC FLOOR PLAN FOR TRAILER.
 DETAIL ALL ELECTRIC LOADS, LOAD CALCULATIONS FOR
 TRAILER AND UPSTREAM PANEL AT BUILDING, AND PANEL
 SCHEDULES FOR EACH. NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-08 Cont ID  
Sent By pleduc Date 2023-06-08 Time   Rev Time 0.00
Received By pleduc Date 2023-06-08 Time 12:09 Sent To  
Notes
2023-06-08 12:17:28FIRE PREVENTION COMMENT:
  
 PER NFPA 241, MUST BE MIN. 20' FROM BLDG.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-08 Cont ID  
Sent By avolcy Date 2023-07-08 Time 15:10 Rev Time 0.00
Received By avolcy Date 2023-06-07 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-14 Cont ID  
Sent By ccole Date 2023-06-14 Time 16:34 Rev Time 0.00
Received By ccole Date 2023-06-14 Time 15:39 Sent To  
Notes
2023-06-14 16:35:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050632
 6/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLUMBING PLAN: INDICATE THE TYPE AND SIZE OF WATER
 SERVICE LINE, POINT OF CONNECTION TO THE EXISTING
 BUILDING SERVICE, UNDERGROUND OR ABOVEGROUND
 INSTALLATION, AND LOCATIONS OF SHUTOFF VALVES AND
 REQUIRED BACKFLOW PREVENTER- SECS. 602.1, 603.2, &
 608.3 FBC P. INDICATE THE TYPE AND SIZE OF BACKFLOW
 PREVENTER TO BE INSTALLED- SEC. 608.3 FBC P.
  
 2) PLUMBING PLAN: SHOW THE TYPE AND SIZE OF TEMPORARY
 SEWER LINE AND CLEANOUT LOCATIONS- SECS. 701.2, 701.3 &
 708.1.2 FBC P.
  
 3) PLUMBING RISER: THE INTERIOR PIPING, FIXTURES AND
 WATER HEATER SHOWN IN THE RISERS APPEAR TO BE FACTORY
 INSTALLED IN THE MANUFACTURED BUILDING. PLEASE PLACE A
 NOTE ON THE PLAN TO CLARIFY- SEC. 107.2.1 WPB.
  
 4) THE CORRECTED PLUMBING PLAN AND RISER DRAWING SHALL
 BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 OR QUALIFIER WHO PREPARED THE DESIGN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By rmcphers Date 2023-06-28 Time 12:54 Rev Time 0.00
Received By rmcphers Date 2023-06-28 Time 12:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-08 Cont ID  
Sent By gvolcy Date 2023-07-08 Time 15:07 Rev Time 0.00
Received By avolcy Date 2023-07-08 Time 15:07 Sent To  
Notes
2023-07-08 15:09:3207.08.2023 - FAILED
  
 PROVIDE SETBACKS FOR THE STRUCTURE ON THE SURVEY.
  
 PROVIDE A NARRATIVE WITH THE USE AND THE DURATION FOR
 WHICH THE STRUCTURE WILL BE THERE.
  
 PROVIDE ELEVATIONS FOR THE PROPOSED TRAILER.
  
 ** REVIEWED BY:**
 GAISHA (ANNE-CLERISSE) VOLCY
 PLANNER
 [email protected]