Plan Review Details - Permit 23050618
Plan Review Stops For Permit 23050618
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By rmcphers Date 2023-07-10 Time 08:15 Rev Time 0.00
Received By rmcphers Date 2023-07-10 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-05 Cont ID  
Sent By rmcphers Date 2023-07-05 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2023-07-05 Time 10:35 Sent To  
Notes
2023-07-05 10:42:38FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 THE ONLY TEST REPORT ADDED TO PROJECTDOX IS THE VINYL
 PLANK LV200 FOR THE IIC AND STC - NEED FLAME SPREAD
 TEST REPORTS FOR LV200 AND - THE IIC AND STC AND FLAME
 SPREAD TEST REPORTS FOR THE TILE UNDERLAYMENT.
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 13:07 Sent To  
Notes
2023-06-30 13:09:14FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-11 Cont ID  
Sent By pleduc Date 2023-07-11 Time   Rev Time 0.00
Received By pleduc Date 2023-07-11 Time 08:54 Sent To  
Notes
2023-07-11 08:56:266/21/23
  
 SPOKE WITH APPLICANT, MR VINCENT PATAGLIORIA 9:43 AM.
 WHOM STATED HE BOUGHT HIS FLOORING FROM LOWES,
 STAINMASTER SPRUCE, WHICH IS AN APPROVED FLOORING.
  
 HE STATED HE WILL HAVE THE SPECS AND A FLOORING BOX
 COVER ON SITE FOR FIRE INSPECTOR REVIEW URING
 INSPECTION.
  
 MY COMMENTS BELOW HAVE BEEN ADDRESSED.
  
 FIRE REVIEW PASSED.PML

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 11:57 Sent To  
Notes
2023-07-06 11:57:366/21/23
  
 SPOKE WITH APPLICANT, MR VINCENT PATAGLIORIA 9:43 AM.
 WHOM STATED HE BOUGHT HIS FLOORING FROM LOWES,
 STAINMASTER SPRUCE, WHICH IS AN APPROVED FLOORING.
  
 HE STATED HE WILL HAVE THE SPECS AND A FLOORING BOX
 COVER ON SITE FOR FIRE INSPECTOR REVIEW URING
 INSPECTION.
  
 MY COMMENTS BELOW HAVE BEEN ADDRESSED.
  
 FIRE REVIEW PASSED.PML

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-21 Cont ID  
Sent By pleduc Date 2023-06-21 Time   Rev Time 0.00
Received By pleduc Date 2023-06-13 Time 11:22 Sent To  
Notes
2023-06-13 11:28:146/21/23
  
 SPOKE WITH APPLICANT, MR VINCENT PATAGLIORIA 9:43 AM.
 WHOM STATED HE BOUGHT HIS FLOORING FROM LOWES,
 STAINMASTER SPRUCE, WHICH IS AN APPROVED FLOORING.
  
 HE STATED HE WILL HAVE THE SPECS AND A FLOORING BOX
 COVER ON SITE FOR FIRE INSPECTOR REVIEW URING
 INSPECTION.
  
 MY COMMENTS BELOW HAVE BEEN ADDRESSED.
  
 FIRE REVIEW PASSED.PML
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 *****************
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF A MANUFACTURER'S
 SPECIFICATION SHEET NOR A PRODUCT NAME FOR THE PROPOSED
 VINYL FLOORING.
  
 THERE IS AN INDICATION OF THE SPEC SHEET FOR THE FLOOR
 UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR
 THE ACTUAL PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 1A) THERE ARE INDICATIONS OF VINYL AND TILE WITHIN 2
 BEDROOM AREAS, HOWEVER, THERE IS NO TILE TYPE, NOR THE
 LINE SEPARATING THE 2 AREAS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
 PLEASE REVIEW AND PROVIDE THE TILE TYPE AND FOR THE
 OFFICIAL RECORD THE INSTALLATION SEPARATION LINES.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-11 Cont ID  
Sent By lmarchan Date 2023-07-11 Time 09:00 Rev Time 0.00
Received By lmarchan Date 2023-07-07 Time 17:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-07 Cont ID  
Sent By aoliver Date 2023-07-07 Time 08:05 Rev Time 0.00
Received By aoliver Date 2023-07-03 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2023-06-12 Time 12:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 13:09 Sent To  
Notes
***NONE***