Plan Review Details - Permit 23050433
Plan Review Stops For Permit 23050433
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-07-07 Cont ID  
Sent By lbond Date 2023-07-07 Time 08:52 Rev Time 0.00
Received By lbond Date 2023-07-07 Time 08:52 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 10:35 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 10:20 Sent To  
Notes
2023-06-12 10:21:55BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23050433
  
 REVIEWED: 6.12.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-07 Cont ID  
Sent By lbond Date 2023-07-07 Time 08:54 Rev Time 0.00
Received By lbond Date 2023-07-07 Time 08:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 10:23 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 10:23 Sent To  
Notes
2023-06-12 10:34:37BUILDING PLAN REVIEW : FAILED
  
  
  
 PER FBC 107.2.1.
 CLARIFY SCOPE OF WORK AND PROVIDE
  
 1. EXTERIOR WALL SECTION WHERE YOU ARE PROPOSING NEW
 INSURALTION SHOW SECTION MARK EXACTLY WHERE THIS IS
 HAPPENING- FULL LENGHT OF THE WALL? PARTIAL?
 IS THIS APPROVED BY THE HOA?
  
 2. SHOW NEW PARTITION IN SECTION AND EXACT LOCATION IN
 PLAN.
  
 3. DIMENSION PLAN AND SHOW EXACTLY WHERE YOU ARE
 PROPOSING A NEW DOOR.
  
 4. PROVIDE CEILING HEIGHTS @ SCOPE OF WORK ROOMS.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS YOU MAY CONTACT
 ME
  
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 PLEASE PROVIDE NARRITIVE WITH COMMENTS RESPONSE

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By jleahy Date 2023-07-14 Time 10:21 Rev Time 0.00
Received By jleahy Date 2023-07-13 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-05 Cont ID  
Sent By rperdomo Date 2023-06-05 Time 11:23 Rev Time 0.00
Received By rperdomo Date 2023-06-05 Time 09:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-19 Cont ID  
Sent By pleduc Date 2023-05-19 Time   Rev Time 0.00
Received By pleduc Date 2023-05-19 Time 15:32 Sent To  
Notes
2023-05-19 15:41:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF A MANUFACTURER'S
 SPECIFICATION SHEET NOR A PRODUCT NAME FOR THE PROPOSED
 VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS AN INDICATION OF A DROP CEILING BUT NO
 CALL-OUT FOR THE CEILING STRUCTURE
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE CEILING DETAILS.
  
  
  
 3) THERE IS AN INDICATION OF A DROP CEILING BUT NO
 CALL-OUT FOR FIRE SPRINKLER MODIFICATIONS
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A NOTE TO MODIFY FIRE SPRINKLER HEADS
 UNDER SEPARATE PERMIT & SHOP DRAWINGS.
  
  
  
 4) THERE IS AN INDICATION OF INSTALL A DOOR BUT NO DOOR
 SCHEDULE INCLUDING SIZE AND HARDWARE.
  
 ALSO INCLUDE THE EXACT LOCATION ON THE FLOOR PLAN
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE DOOR DETAILS
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-14 Cont ID  
Sent By jleahy Date 2023-07-14 Time 10:21 Rev Time 0.00
Received By jleahy Date 2023-07-06 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 10:35 Rev Time 0.00
Received By lbond Date 2023-05-18 Time 10:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 10:34 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 10:34 Sent To  
Notes
2023-06-12 10:35:30FLORIDA LICENSED CONTRACTOR DOING THE WORK SEE PLAN