| 2023-05-22 10:51:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE OCCUPANCY OF AN AREA |
| | OF THE PARKING GARAGE. |
| | |
| | AS PREVIOUSLY STATED FROM THIS OFFICE AND THE FIRE |
| | INSPECTOR, LIFE SAFETY IS REQUIRED TO BE IN PLACE, |
| | INCLUDING FIRE ALARM, FIRE SPRINKLER, EMERGENCY |
| | LIGHTING, EXIT TRAVEL TO 2 EXITS MIN., EXIT LIGHTING, |
| | EXITS, ETC. |
| | |
| | THERE IS NO INDICATION OF THE ABOVE NOTED LIFE SAFETY |
| | FEATURES. |
| | |
| | THERE IS NO LOCATION FLOOR PLAN SHOWING THE LOCATION |
| | THE CLEAR PROTECTED EXIT PATHS TO A PUBLIC WAY. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF ELECTRICAL WIRING. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND PROVIDE ELECTICAL WORK IN COMPLIOANCE |
| | WITH NFPA 70. |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATIONS OF A/C. |
| | |
| | WILL THERE BE A/C PROVIDED? |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |