2023-05-26 13:36:19BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23050351
 REVIEWED: MAY 26, 2023
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
  
 1207.2 FBC[B] FLOORING SUBMITTAL.
 - TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-02 Cont ID  
Sent By clfranci Date 2023-06-02 Time   Rev Time 0.00
Received By clfranci Date 2023-06-02 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-12 Cont ID  
Sent By clfranci Date 2023-05-12 Time   Rev Time 0.00
Received By clfranci Date 2023-05-12 Time   Sent To  
Notes
2023-05-12 15:18:52FLOORING / UNDERLAYMENT
 THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF VINYL FLOOR AND UNDER
 LAYMENT BUT NO SPECIFICATIONS SHEETS THAT INDICATE
 MEETING THE REQUIREMENTS PER NFPA 101
  
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-06 Cont ID  
Sent By dbattles Date 2023-06-06 Time 12:53 Rev Time 0.00
Received By dbattles Date 2023-06-02 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-26 Cont ID  
Sent By dbattles Date 2023-05-26 Time 13:30 Rev Time 0.00
Received By dbattles Date 2023-05-10 Time 08:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-05-26 Cont ID  
Sent By dbattles Date 2023-05-26 Time 13:30 Rev Time 0.00
Received By dbattles Date 2023-05-26 Time 13:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved