Plan Review Details - Permit 23050263
Plan Review Stops For Permit 23050263
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-07-14 Cont ID  
Sent By jleahy Date 2023-07-14 Time 14:05 Rev Time 0.00
Received By jleahy Date 2023-07-14 Time 11:23 Sent To  
Notes
2023-07-14 14:10:53FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONE DETAIL SHOWS CAMERAS ON POLES, IF THEY ARE TO BE
 INSTALLED PLEASE SHOW COMPLIANCE WITH 725.136
  
 725.136 SEPARATION FROM ELECTRIC LIGHT, POWER, CLASS 1,
 NON???POWER-LIMITED FIRE ALARM CIRCUIT CONDUCTORS, AND
 MEDIUM-POWER NETWORK-POWERED BROADBAND COMMUNICATIONS
 CABLES.
 (A) GENERAL.
  
 CABLES AND CONDUCTORS OF CLASS 2 AND CLASS 3 CIRCUITS
 SHALL NOT BE PLACED IN ANY CABLE, CABLE TRAY,
 COMPARTMENT, ENCLOSURE, MANHOLE, OUTLET BOX, DEVICE
 BOX, RACEWAY, OR SIMILAR FITTING WITH CONDUCTORS OF
 ELECTRIC LIGHT, POWER, CLASS 1, NON???POWER-LIMITED
 FIRE ALARM CIRCUITS, AND MEDIUM-POWER NETWORK-POWERED
 BROADBAND COMMUNICATIONS CIRCUITS UNLESS PERMITTED BY
 725.136(B) THROUGH (I).
  
 PLEASE PROVIDE A BREAKDOWN OF HOW MANYURES ARE BEING
 INSTALLED, OR RELOCATED.
  
 PERMIT VALUE TO INCLUDE ALL LABOR AND MATERIALS
 INVOLVED CUSTOMER OR CONTRACTOR SUPPLIED. PLEASE
 PROVIDE A COST BREAKDOWN OF WORK.
  
 FBC 109.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-25 Cont ID  
Sent By jleahy Date 2023-05-25 Time 15:38 Rev Time 0.00
Received By jleahy Date 2023-05-25 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-12 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-16 Cont ID  
Sent By lmarchan Date 2023-06-16 Time 07:39 Rev Time 0.00
Received By lmarchan Date 2023-05-19 Time 10:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-07-14 Cont ID  
Sent By jleahy Date 2023-07-14 Time 13:55 Rev Time 0.00
Received By jleahy Date 2023-07-14 Time 11:23 Sent To  
Notes
2023-07-14 14:05:19FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MOST OF THE PLANS ARE COPIES, NEED TO SUBMIT COPIES
 WITH VERFIABLE SIGATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jleahy Date 2023-05-25 Time 15:38 Rev Time 0.00
Received By jleahy Date 2023-05-25 Time 15:38 Sent To  
Notes
2023-05-25 15:39:45DIGITAL SIGNATURES NOT VERIFIABLE JLEAHY

Review Stop Z ZONING
Rev No 2 Status F Date 2023-07-24 Cont ID  
Sent By eschneid Date 2023-07-24 Time 14:21 Rev Time 0.75
Received By eschneid Date 2023-07-21 Time 13:20 Sent To  
Notes
2023-07-24 14:22:25FAILED
  
 1) UPDATED COMMENT: CARLOS FLORIAN STATED IN AN EMAIL
 RESPONSE THAT THE LOCATIONS ALONG WEST EXECUTIVE CENTER
 DRIVE EXCEEDING ONE FOOTCANDLE AT THE BOUNDARIES OF THE
 SITE ARE DUE TO THE EXISTING LIGHTS WITHIN THE
 RIGHT-OF-WAY AND NOT DUE TO THE LIGHTING BEING
 INSTALLED AS PART OF THIS PROJECT. A NOTE TO STATING
 THIS MUST BE INCLUDED ON THE PHOTOMETRIC PLAN.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-15 Cont ID  
Sent By eschneid Date 2023-06-15 Time 18:08 Rev Time 0.75
Received By eschneid Date 2023-06-15 Time 17:15 Sent To  
Notes
2023-06-15 18:03:57FAILED
  
 1) THE POLE DETAIL SHOWN ON SHEET C901.6(E-16.0)
 DIFFERS FROM THE POLE DETAIL SHOWN ON SHEETS C901.0 AND
 C901.1. ALL SHEETS MUST SHOW THE SAME CONDITIONS.
  
 A. THE POLE PLUS FIXTRUE HEIGHTS DIFFE BY APPROXIMATELY
 SIX (6) FEET.
 B. THE POLE DETAIL ON SHEET C901.6(E-16.0) SHOWS
 SPOTLIGHTS MOUNTED TO THE POLES. YOU MUST DESIGNATE
 WHICH POLES THESE ARE LOCATED ON AND REFLECT THE
 PHOTOMETRICS ACCORDINGLY. PLEASE NOTE THAT THEIR
 POSITIONING MAY NOT RESULT IN GLARE IN THE RIGHT-OF-WAY
 OR RESIDENTIAL PROPERTY.
  
 2) THE FOOTCANDLE VALUES ON THE PHOTOMETRIC PLANS ARE
 VERY DIFFICULT TO READ. PLEASE MAKE THEM MORE LEGIBLE.
  
 3) THE ZONING AND LAND DEVELOPMENT REGULATIONS SPECIFY
 THAT ANY SOURCE OF ILLUMINATION LOCATED WITHIN A
 COMMERCIAL PLANNED DEVELOPMENT DISTRICT(WHICH IS
 APPLIES TO BRANDSMART/BJS) SHALL NOT EXCEED ONE
 FOOTCANDLE AT OR BEYOND THE BOUNDARIES OF SUCH
 DEVELOPMENT. THE ONE FOOTCANDLE MAXIMUM IS EXCEEDED IN
 A NUMBER OF LOCATIONS. THIS MUST BE CORRECTED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446.
 [email protected]