Plan Review Details - Permit 23050224
Plan Review Stops For Permit 23050224
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 15:12 Sent To  
Notes
2023-06-30 15:36:34WINDOWS AND FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE WIND DESIGN ENGINEERING PROVIDED SHOWS THE
 BUILDING MEAN ROOF HEIGHT AT 80 FEET - THE BUILDINGS
 MEAN ROOF IS HIGHER THAN THAT - PLEASE CORRECT. FBC WPB
 107.2.1
  
 2) THE WIND DESIGN ENGINEERING PROVIDED SHOWS EXPOSURE
 "C" USED - THE BUILDING IS AN EXPOSURE "D" - PLEASE
 CORRECT. FBC 1609.4.2
  
 3) THE WIND DESIGN ENGINEERING PROVIDED FROM
 ENGINEERING EXPRESS DOES NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
 4) FLOOR PLAN SHOWS END WINDOW TO BE IN A WIND ZONE 5
 (PRODUCT APPROVAL WIND PRESSURES WILL NEED TO MEET OR
 EXCEED ZONE 5 WIND PRESSURES SHOWN ON THE PROVIDED WIND
 DESIGN ENGINEERING) - PLEASE SHOW THE BUILDING
 DIMENSIONS AND THE DISTANCE FROM THE EDGE OF THE WINDOW
 TO THE CORNER OF THE BUILDING TO VERIFY THE WIND ZONES.
 FBC WPB 107.2.1
  
 5) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE FIXED
 GLASS WINDOWS. FBC WPB 107.1
  
 6) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 FOR THE FLOORING UNDERLAYMENT.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-08 Cont ID  
Sent By pleduc Date 2023-06-08 Time   Rev Time 0.00
Received By pleduc Date 2023-06-08 Time 10:43 Sent To  
Notes
2023-06-08 10:46:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF NEW VINYL FLOORING.
  
 THERE IS AN INDICATION OF THE SPEC SHEET FOR THE FLOOR
 UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR
 THE ACTUAL PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2023-06-07 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By rmcphers Date 2023-06-30 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2023-06-30 Time 15:42 Sent To  
Notes
2023-06-30 15:45:13SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ENGINEERING SIGNED AND SEALED BY ENGINEERING EXPRESS
 DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  