Plan Review Details - Permit 23050180
Plan Review Stops For Permit 23050180
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By rmcdouga Date 2023-06-28 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2023-06-28 Time 09:04 Sent To  
Notes
2023-06-28 09:53:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. THIS SHOULD BE
 SPECIFIED ON THE SURVEY/SITE FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 2) SEE THE SIGNATURE REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 15:47 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-21 Time 15:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-28 Cont ID  
Sent By lngelman Date 2023-06-28 Time 11:06 Rev Time 0.00
Received By lngelman Date 2023-05-24 Time 14:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By rmcdouga Date 2023-06-28 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2023-06-28 Time 09:04 Sent To  
Notes
2023-06-28 09:28:40THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 GENERATOR PAD ENGINEERING. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC 61G1
 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By lgelman Date 2023-06-28 Time 11:06 Rev Time 0.00
Received By lngelman Date 2023-06-28 Time 11:03 Sent To  
Notes
2023-06-28 11:06:46PER CODE SECTION 94-305, MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 INDICIATE SIDE SETBACK FOR GENERATOR. SIDE SETBACK FOR
 WEST PROPERTY LINE IS APPROX. 10 FEET, SO MINIMUM
 SETBACK ALLOWED IS 6 FEET.
  
 WILL GENERATOR BE SCREENED WITH LANDSCAPING? IF SO,
 INDICATE LANDSCAPING LOCATION ON SURVEY.
  
 ***** REVIEWED BY*****
 LINDSEY GELMAN
 561-822-1275
 [email protected]


Account Summary | Usage Policy | Privacy Policy