Plan Review Details - Permit 23050108
Plan Review Stops For Permit 23050108
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-06-09 Cont ID  
Sent By pvalenti Date 2023-05-15 Time 16:31 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 16:31 Sent To  
Notes
2023-05-15 16:33:15PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW APPROVED:
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-06 Cont ID  
Sent By pvalenti Date 2023-07-06 Time 13:22 Rev Time 0.00
Received By pvalenti Date 2023-06-22 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-15 Cont ID  
Sent By pvalenti Date 2023-05-15 Time 15:52 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 15:32 Sent To  
Notes
2023-05-15 15:56:28PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 3. WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-07-06 Cont ID  
Sent By cseifer Date 2023-06-23 Time 09:50 Rev Time 0.00
Received By cseifer Date 2023-07-06 Time 13:45 Sent To  
Notes
2023-07-06 13:46:41PASSED WITH PROVISO: PROVIDE SILT FENCE ALONG PROPERTY
 LINE FOR EROSION CONTROL.
  
 THANKS,
 CHLOE SEIFER, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-05-31 Cont ID  
Sent By lquinone Date 2023-05-31 Time 19:52 Rev Time 0.00
Received By lquinone Date 2023-05-31 Time 19:52 Sent To  
Notes
2023-05-31 19:53:17PLEASE PROVIDE STORMWATER POLLUTION PREVENTION PLAN
 SHOWN ON COPY OF PROPERTY SURVEY - SILT FENCE AROUND
 PROPERTY TO PREVENT DEBRIS RUNOFF; PROTECT ROADWAY FROM
 TRACKING OF DIRT FROM TRUCKS HAULING DEBRIS; PROTECT
 ANY STORM DRAIN INLETS IN VICINITY USING BEST
 MANAGEMENT PRACTICES (FILTER FABRIC, ETC.)
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED
 BY BUILDING DEPT. - STORMWATER POLLUTION PREVENTION
 PLAN, AND UTILITY SIGNOFFS - WATER/SEWER, PEST, FPL,
 FPU, ASBESTOS ETC.
  
 TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN
 REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND
 WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT
 FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING
 BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN
 REVIEW TIME.
  
 ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DONT
 UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST
 PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO
 DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE
 AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN
 REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES
 WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S
 ERVICES/PERMITS AND SEE WHERE CAN I FIND MY PLAN REVIEW
 COMMENTS ONLINE? FOR INSTRUCTIONS.
  
 FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON
 WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION
 TEAM MEMBER WILL HELP YOU.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-22 Cont ID  
Sent By pleduc Date 2023-06-22 Time   Rev Time 0.00
Received By pleduc Date 2023-06-22 Time 10:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-05-31 Cont ID  
Sent By pleduc Date 2023-05-08 Time   Rev Time 0.00
Received By pleduc Date 2023-05-08 Time 15:01 Sent To  
Notes
2023-05-08 15:07:06APPLICANT MADE CONTACT, THIS IS NOT A FENCE PERMIT AND
 MYU COMMENTS BELOW DO NOT APPLY.
  
  
 PASSED FIRE
 5/31/23
 PML
  
  
 *******************************************************
 *******************************************************
 ************************************
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS A SURVEY SUBMITTED HOWEVER, THERE IS NO
 INDICATION OF WHERE THE PROPOSED FENCE WILL BE LOCATED
 NOR THE HEIGHT, FENCE TYPE NOR THE LOCATION
 OF ANY PROPOSED GATES AND GATE SIZE.
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FENCE
 DETAILS, GATE TYPE AND SIZE.
  
 2) INFORMATIONAL ONLY:
  
 A KNOX PADLOCK IS RECOMMENDED, NOT REQUIRED, FOR 24 HR
 FD EMERGENCY ACCESS AND TO NOT CUT YOUR LOCK SHOULD
 ENTRY BE NEEDED.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-05-31 Cont ID  
Sent By amhamilt Date 2023-05-31 Time 10:51 Rev Time 0.00
Received By amhamilt Date 2023-05-31 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-06 Cont ID  
Sent By pvalenti Date 2023-07-06 Time 14:19 Rev Time 0.00
Received By pvalenti Date 2023-06-21 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-01 Cont ID  
Sent By aoliver Date 2023-06-01 Time 08:11 Rev Time 0.00
Received By aoliver Date 2023-05-05 Time 12:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-06-30 Cont ID  
Sent By lngelman Date 2023-06-30 Time 16:44 Rev Time 0.00
Received By lngelman Date 2023-06-30 Time 16:43 Sent To  
Notes
2023-06-30 16:44:35PURSUANT TO SECTION 94-316(D). ALL CONSTRUCTION WASTE
 AND DEBRIS FROM NEW CONSTRUCTION OR MAJOR ALTERATION OR
 REPAIR SHALL BE KEPT IN AN ENCLOSED CONTAINER TO
 MINIMIZE DEBRIS FROM LITTERING ADJACENT PROPERTIES AND
 PUBLIC RIGHTS-OF-WAY. THE PERMITTEE, CONTRACTOR OR
 PROPERTY OWNER SHALL CAUSE SUCH WASTE OR DEBRIS TO BE
 REMOVED WEEKLY IN ACCORDANCE WITH SECTION 74-2 OF THIS
 CODE.
 C. ALL MUD OR DEBRIS SHALL BE CONTINUALLY REMOVED FROM
 THE PUBLIC SIDEWALKS AND STREETS.
 D. ALL WEEDS AND GRASS SHALL BE MAINTAINED IN
 ACCORDANCE WITH SUBSECTION 74-2(C) AND SECTION 94-446
 OF THIS CODE.
  
 *****REVIEWED BY*****
 LINDSEY GELMAN
 561-822-1275
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-18 Cont ID  
Sent By lgelman Date 2023-05-18 Time 16:47 Rev Time 0.00
Received By lngelman Date 2023-05-18 Time 16:47 Sent To  
Notes
***NONE***