| Plan Review Stops For Permit 23050024 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-07-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-07-03 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2023-07-03 14:13:12 | COMMERCIAL ASBESTOS | | | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING | | | THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS | | | PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM | | | BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION | | | WILL BE GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-07-03 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-07-03 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-05 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-05 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2023-07-05 08:14:22 | ELECTRIC REVIEW FAILED | | | | | | 1) REFLECTED CIELING PLAND HAS CONFLICTING NOTES, ONE | | | STATES CIELING TILES AND LIGHTS TO REMAIN AND THEOTHER | | | STATES NEW GRID AND LED LIGHTS TO BE INSTALLED. PLEASE | | | CORRECT AS APPLICABLE. FBC 107.2 | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL | | | | | | 2) DIGITAL SIGNATURE OF AOR DETAILS AN INVALID, ALTERED | | | DOCUMENTSAFTER SIGNATURE WAS APPLIED. PLEASE CORRECT AS | | | APPLICABLE FOR ALL PLANS. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | 61G15023.004(2) (2) A PROFESSIONAL ENGINEER UTILIZING A | | | DIGITAL SIGNATURE TO ELECTRONICALLY SIGN AND SEAL | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS SHALL HAVE THEIR IDENTITY AUTHENTICATED BY A | | | CERTIFICATION AUTHORITY AND SHALL ASSURE THAT THE | | | DIGITAL SIGNATURE IS: | | | (A) UNIQUE TO THE PERSON USING IT; | | | (B) CAPABLE OF VERIFICATION; | | | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND, | | | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE | | | DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS | | | INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-06-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-06-09 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2023-06-09 11:29:35 | FIRE PROVISO: | | | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES | | | AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS FOR CODE COMPLIANT COVERAGE | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-07-15 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-07 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-07-03 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-07-03 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-07-15 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-07-15 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2023-07-15 10:32:57 | PLAN DENIED | | | EXHAUST DUCT MUST BE METAL PER SECTION 501.5 DUCTS | | | 2020 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-30 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-30 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2023-06-30 16:16:56 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23050024 | | | 6/30/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-6: PLEASE REFER TO SEC. 810.1 FBC EX AND | | | PROVIDE THE EXISTING OCCUPANT LOAD OF THE FLOOR AND THE | | | INCREASED OCCUPANT LOAD BASED ON THE OFFICE CONVERSION | | | TO NEW CLASSROOM. PLEASE NOTE IF THE EXISTING LOAD | | | INCREASES BY MORE THAN 20%, PLUMBING FIXTURES SHALL BE | | | PROVIDED IN COMPLIANCE WITH TABLE 403.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2023-06-26 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2023-06-26 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2023-06-26 11:04:34 | PLEASE PROVIDE CERTIFICATE OF INSURANCE. | | | | | | CERTIFICATE OF INSURANCE FOR PROFESSIONAL LIABILITY OF | | | FIRM. MINIMUM COVERAGE OF $1,000,000.00 PER OCCURRENCE | | | AND $2,000,000.00 AGGREGATE ARE REQUIRED. F.S. 553.791 | | | (4) (B) AND (16). CERTIFICATE OF INSURANCE FOR | | | PROFESSIONAL LIABILITY OF FIRM. MINIMUM COVERAGE OF | | | $1,000,000.00 PER OCCURRENCE AND $2,000,000.00 | | | AGGREGATE ARE REQUIRED. F.S. 553.791 (4) (B) AND (16). | | | IN THE DESCRIPTION OF OPERATIONS PLEASE ADD LANGUAGE TO | | | STATE "THE PROFESSIONAL LIABILITY POLICY INCLUDES AN | | | EXTENDED REPORTING PERIOD ENDORSEMENT (TAIL COVERAGE) | | | FOR FIVE YEARS. ___________IS PROVIDING PROFESSIONAL | | | LIABILITY INSURANCE COVERING ALL SERVICES TO BE | | | PERFORMED AS A PRIVATE PROVIDER. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-05 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-05 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2023-07-05 08:16:51 | SIGNATURE REVIEW FAILED | | | | | | 1)THE DIGITAL SIGNATURE OF THE ENGINEER OF RECORD ON | | | ALL DRAWINGS COULD NOT BE CERTIFIED USING ADOBE OR | | | BLUEBEAM SOFTWARE. PLEASE CORRECT AS OUTLINED BELOW | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | . |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2023-06-30 |
Time |
19:52 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2023-06-30 |
Time |
19:52 |
Sent To |
|
|
| Notes |
|
|