Plan Review Details - Permit 23050002
Plan Review Stops For Permit 23050002
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 15:41 Rev Time 0.00
Received By jgomez Date 2023-06-29 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-23 Cont ID  
Sent By jbrooks Date 2023-06-23 Time 09:29 Rev Time 0.00
Received By jbrooks Date 2023-06-23 Time 09:08 Sent To  
Notes
2023-06-23 09:30:18JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 20-0812.09 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED HIP & RIDGE SHINGLES
 TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 (PREVIOUS COMMENT FROM FIRST REVIEW THAT WAS NOT
 ADDRESS).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 17:54 Rev Time 0.00
Received By jgomez Date 2023-05-25 Time 15:59 Sent To  
Notes
2023-05-25 17:55:07RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23050002
 717 MADDOCK ST
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF INSTALLATION IS NOT CLEAR. CERTAINTEED
 MODIFIED BITUMEN NOA 20-0723.29 SUBMITTED WAS MARKED
 WITH 3 DIFFERENT ASSEMBLIES AND CONTRACTOR ALSO
 SUBMITTED SIGNED AND SEALED NAIL ENHANCEMENT
 CALCULATIONS. CONTRACTOR NEEDS TO SUBMIT ONLY ONE
 OPTION TO AVOID CONFLICTS/DELAYS.
 IF USING THE NOA ALONE WITHOUT ENGINEERING, THEN
 CONTRACTOR NEEDS TO SELECT ONLY ONE ASSEMBLY THAT MEETS
 THE DESIGN PRESSURES FOR ALL ROOF ZONES (NOTE: ONLY
 MARKED ASSEMBLY SYSTEM TYPE E(24) ON PAGE 47 OF 48 WILL
 MEE THE DESIGN PRESSURE FOR ALL ROOF ZONES. RESUBMIT AS
 REQUIRED WITH ONLY ONE OPTION MARKED.
  
 ON THE OTHER HAND IF USING THE SIGNED AND SEALED
 CALCULATIONS , THEN THE FOLLOWING NEEDS TO BE
 ADDRESSED.
 A)ENGINEER NEEDS TO PROVIDE SKETCH SHOWING HOW THE SIX
 STAGGERED ROWS OF NAILS ARE GOING TO BE INSTALLED IN
 THE FIELD OF THE SHEET FOR ZONE 2 AND HOW THE SEVEN
 STAGGERED ROWS OF NAILS ARE GOING TO BE INSTALLED IN
 THE FIELD OF THE SHEET FOR ZONE 3. (NOTE: CHECK RAS 117
 SEC. 8.1 FOR MINIMUM FASTENER SEPARATION).
  
 B)CALCULATIONS SUBMITTED HAVE A COPY OF THE ENGINEER'S
 SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE WHEN
 SUBMITTED FOR PUBLIC RECORDS. SEC. 471 F.S.
 NOTE: ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING
 AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED.
 CLEARLY MARK WHICH SYSTEM TYPE ON PAGE 4 OF 7 IS GOING
 TO BE INSTALLED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- OWENS HIP & RIDGE SHINGLES NOA 20-0812.09 EXPIRED ON
 02/28/23. NEED CURRENT PRODUCT APPROVAL.
 F.A.C. 61G20.3.001.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-29 Cont ID  
Sent By jgomez Date 2023-06-29 Time 15:41 Rev Time 0.00
Received By jgomez Date 2023-06-26 Time 08:25 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-23 Cont ID  
Sent By jbrooks Date 2023-06-23 Time 09:34 Rev Time 0.00
Received By jbrooks Date 2023-06-13 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 17:56 Rev Time 0.00
Received By jgomez Date 2023-05-23 Time 15:07 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-23 Cont ID  
Sent By jbrooks Date 2023-06-23 Time 09:34 Rev Time 0.00
Received By jbrooks Date 2023-06-23 Time 09:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 17:55 Rev Time 0.00
Received By jgomez Date 2023-05-25 Time 17:55 Sent To  
Notes
2023-05-25 17:56:18SIGNATURE REVIEW
  
 1- RAS 117 CALCULATIONS SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE
 WHEN SUBMITTED FOR PUBLIC RECORDS. SEC. 471 F.S.
 NOTE: ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING
 AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.