| 2023-05-25 17:55:07 | RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23050002 |
| | 717 MADDOCK ST |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- FLAT ROOF INSTALLATION IS NOT CLEAR. CERTAINTEED |
| | MODIFIED BITUMEN NOA 20-0723.29 SUBMITTED WAS MARKED |
| | WITH 3 DIFFERENT ASSEMBLIES AND CONTRACTOR ALSO |
| | SUBMITTED SIGNED AND SEALED NAIL ENHANCEMENT |
| | CALCULATIONS. CONTRACTOR NEEDS TO SUBMIT ONLY ONE |
| | OPTION TO AVOID CONFLICTS/DELAYS. |
| | IF USING THE NOA ALONE WITHOUT ENGINEERING, THEN |
| | CONTRACTOR NEEDS TO SELECT ONLY ONE ASSEMBLY THAT MEETS |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES (NOTE: ONLY |
| | MARKED ASSEMBLY SYSTEM TYPE E(24) ON PAGE 47 OF 48 WILL |
| | MEE THE DESIGN PRESSURE FOR ALL ROOF ZONES. RESUBMIT AS |
| | REQUIRED WITH ONLY ONE OPTION MARKED. |
| | |
| | ON THE OTHER HAND IF USING THE SIGNED AND SEALED |
| | CALCULATIONS , THEN THE FOLLOWING NEEDS TO BE |
| | ADDRESSED. |
| | A)ENGINEER NEEDS TO PROVIDE SKETCH SHOWING HOW THE SIX |
| | STAGGERED ROWS OF NAILS ARE GOING TO BE INSTALLED IN |
| | THE FIELD OF THE SHEET FOR ZONE 2 AND HOW THE SEVEN |
| | STAGGERED ROWS OF NAILS ARE GOING TO BE INSTALLED IN |
| | THE FIELD OF THE SHEET FOR ZONE 3. (NOTE: CHECK RAS 117 |
| | SEC. 8.1 FOR MINIMUM FASTENER SEPARATION). |
| | |
| | B)CALCULATIONS SUBMITTED HAVE A COPY OF THE ENGINEER'S |
| | SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE WHEN |
| | SUBMITTED FOR PUBLIC RECORDS. SEC. 471 F.S. |
| | NOTE: ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ENGINEERS |
| | 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING |
| | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED. |
| | CLEARLY MARK WHICH SYSTEM TYPE ON PAGE 4 OF 7 IS GOING |
| | TO BE INSTALLED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- OWENS HIP & RIDGE SHINGLES NOA 20-0812.09 EXPIRED ON |
| | 02/28/23. NEED CURRENT PRODUCT APPROVAL. |
| | F.A.C. 61G20.3.001. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |