Plan Review Details - Permit 23041470
Plan Review Stops For Permit 23041470
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-26 Cont ID  
Sent By cthroop Date 2023-06-26 Time 12:33 Rev Time 0.00
Received By cthroop Date 2023-06-26 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-06 Cont ID  
Sent By jbrooks Date 2023-06-06 Time 13:42 Rev Time 0.00
Received By jbrooks Date 2023-06-06 Time 13:20 Sent To  
Notes
2023-06-06 13:43:13JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-2;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170). ZONE 3 IS MARKED ???N/A???
 WHICH INDICATES SYSTEM IS ???NOT APPLICABLE??? TO ZONE1
 PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED.
 SELECT A SYSTEM THAT MEETS THE ABOVE CRITERIA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-04 Cont ID  
Sent By jbrooks Date 2023-05-04 Time 09:53 Rev Time 0.00
Received By jbrooks Date 2023-05-04 Time 08:05 Sent To  
Notes
2023-05-04 09:54:22JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-4;
 EXPOSURE (C); ENCLOSURE (OPEN); ROOF HEIGHT H<15;
 ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT
 ENCLOSURE FOR THE LISTED ADDRESS IS ENCLOSED; WIND
 SPEED 170. PLEASE SELECT THE CORRECT OPTIONS INCLUDING
 CORRECT FASTENING PATTERNS FOR ZONE 1 PRIME, ZONES 1, 2
 & 3. IF APPLICABLE.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN
 ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-06 Cont ID  
Sent By jbrooks Date 2023-06-06 Time 13:43 Rev Time 0.00
Received By jbrooks Date 2023-06-01 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-04 Cont ID  
Sent By jbrooks Date 2023-05-04 Time 09:54 Rev Time 0.00
Received By jbrooks Date 2023-05-03 Time 12:01 Sent To  
Notes
***NONE***