Plan Review Details - Permit 23041431
Plan Review Stops For Permit 23041431
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-05-12 Cont ID  
Sent By cpuell Date 2023-05-12 Time 10:55 Rev Time 0.00
Received By cpuell Date 2023-05-12 Time 10:54 Sent To  
Notes
2023-05-12 10:56:38APPLICANT CONFIRMED WORK IS FOR BOTH THE BUILDINGS,
 UPDATED PERMIT TO REFLECT THE 2 ADDRESSES

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-05-11 Cont ID  
Sent By cpuell Date 2023-05-11 Time 10:30 Rev Time 0.00
Received By cpuell Date 2023-05-11 Time 10:30 Sent To  
Notes
2023-05-11 10:31:49WHICH BUILDING IS THE WORK TO BE DONE, EAST OR WEST?
 PLEASE RESPOND TO [email protected] OR CALL
 561-805-6659 BOTH BUILDINGS HAVE SEPARATE ADDRESSES

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-02 Cont ID  
Sent By jgomez Date 2023-06-02 Time 18:02 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 17:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-31 Cont ID  
Sent By jgomez Date 2023-05-31 Time 13:54 Rev Time 0.00
Received By jgomez Date 2023-05-31 Time 09:27 Sent To  
Notes
2023-05-31 13:54:16RESIDENTIAL(R3) RE-ROOF SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041431
 2737 S FLAGLER DR
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL:
 ORIGINAL COMMENT:
 A)CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND INSTALLATION INSTRUCTIONS ON THE SAME PDF.
  
 RESPONSE:
 INFORMATION UPLOADED TO PROJECTDOX ON 05/26/23 IS
 MISMATCHING TWO DIFFERENT PRODUCT APPROVALS. CONTRACTOR
 UPLOADED THE REVISED PRODUCT APPROVAL COVER PAGE
 FL2533-R29 BUT THE INSTALLATION INSTRUCTIONS SUBMITTED
 ARE FOR THE OLD REVISION FL2533-R28. SELECTED SYSTEM
 W-67 IS NOT THE SAME FOR FL2533-R28 AND FL2533-R289.
 NEED TO SUBMIT MATCHING FLORIDA PRODUCT APPROVAL COVER
 PAGE AND INSTALLATION INSTRUCTIONS TO AVOID
 CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 B)BASED ON OLD FLORIDA PRODUCT APPROVAL FL2533-R28
 SUBMITTED, IT LOOKS LIKE THE PROPOSED ASSEMBLY IS W-68.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY LIMITATION #5.7.2 OF PRODUCT APPROVAL
 SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM ABOVE. MISMATCHING TWO DIFFERENT
 PRODUCT APPROVALS.
  
 ORIGINAL COMMENT:
 2- HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE
 INSTALLATION AS REQUIRED BY SEC. R905.3.7.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE
 WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE
 INSTALLATION MANUAL (6TH EDITION) OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
 ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE
 PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND
 CLEARLY MARK ATTACHMENT METHOD.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENTS BASED ON INFORAMTION SUBMITTED:
 3- ENGINEER TO REVISE THE ROOF COVERINGS ATTACHMENT
 CALCULATIONS SUBMITTED:
 A) COORDINATE SELECTED ASSEMBLY WITH CURRENT REVISED
 PRODUCT APPROVAL FL2533-R29. SEE ITEM #1(A) ABOVE.
  
 B)ENGINEER TO PROVIDE SKETCH SHOWING HOW THE PROPOSED
 NAILS ARE GOING TO BE INSTALLED FOR THE SEVEN CENTER
 ROWS IN ZONE 3. NEED TO VERIFY THAT FASTENER SEPARATION
 IS NOT LESS THAN 4"O.C. AS REQUIRED BY SEC. 8.1 OF RAS
 117.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/??? AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-17 Cont ID  
Sent By jgomez Date 2023-05-17 Time 11:05 Rev Time 0.00
Received By jgomez Date 2023-05-17 Time 09:04 Sent To  
Notes
2023-05-17 11:05:49RESIDENTIAL(R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041431
 2737 S FLAGLER DR
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R29:
 A)CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND INSTALLATION INSTRUCTIONS ON THE SAME PDF.
  
 B)BASED ON OLD FLORIDA PRODUCT APPROVAL FL2533-R28
 SUBMITTED, IT LOOKS LIKE THE PROPOSED ASSEMBLY IS W-68.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY LIMITATION #5.7.2 OF PRODUCT APPROVAL
 SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE
 INSTALLATION AS REQUIRED BY SEC. R905.3.7.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE
 WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE
 INSTALLATION MANUAL (6TH EDITION) OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
 ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE
 PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND
 CLEARLY MARK ATTACHMENT METHOD.
  
 3- DESIGNER OF RECORD FOR MASTER PERMIT 23010885
 REFERENCED IN THE PERMIT APPLICATION TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-05-25 Cont ID  
Sent By fmittner Date 2023-05-25 Time 07:25 Rev Time 0.00
Received By fmittner Date 2023-05-25 Time 07:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-02 Cont ID  
Sent By jgomez Date 2023-06-02 Time 18:02 Rev Time 0.00
Received By jgomez Date 2023-06-01 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-31 Cont ID  
Sent By jgomez Date 2023-05-31 Time 13:55 Rev Time 0.00
Received By jgomez Date 2023-05-26 Time 16:27 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-26 Cont ID  
Sent By aoliver Date 2023-05-26 Time 08:46 Rev Time 0.00
Received By aoliver Date 2023-05-09 Time 10:39 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status N Date 2023-06-02 Cont ID  
Sent By jgomez Date 2023-06-02 Time 13:03 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 13:03 Sent To  
Notes
2023-06-02 13:04:1406/02/23 TALKED TO MRS. JILL WALK (CAMPANY ROOFING).
 THERE IS NOT MASTER PERMIT AND NOT PRIVATE PROVIDER FOR
 INSPECTIONS. JG.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2023-05-26 Cont ID  
Sent By aoliver Date 2023-05-26 Time 08:08 Rev Time 0.00
Received By aoliver Date 2023-05-26 Time 08:08 Sent To  
Notes
2023-05-26 08:09:04APPROVED UNDER MASTER 23010885

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-02 Cont ID  
Sent By jgomez Date 2023-06-02 Time 18:02 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 18:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-31 Cont ID  
Sent By jgomez Date 2023-05-31 Time 13:55 Rev Time 0.00
Received By jgomez Date 2023-05-31 Time 13:54 Sent To  
Notes
2023-05-31 13:55:53SIGNATURE REVIEW:
  
 1- ENGINEER TO REVISE THE ROOF COVERINGS ATTACHMENT
 CALCULATIONS SUBMITTED:
 A) COORDINATE SELECTED ASSEMBLY WITH CURRENT REVISED
 PRODUCT APPROVAL FL2533-R29. SEE ITEM #1(A) ABOVE.
  
 B)ENGINEER TO PROVIDE SKETCH SHOWING HOW THE PROPOSED
 NAILS ARE GOING TO BE INSTALLED FOR THE SEVEN CENTER
 ROWS IN ZONE 3. NEED TO VERIFY THAT FASTENER SEPARATION
 IS NOT LESS THAN 4"O.C. AS REQUIRED BY SEC. 8.1 OF RAS
 117.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/??? AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.