Plan Review Details - Permit 23041293
Plan Review Stops For Permit 23041293
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 16:48 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 16:47 Sent To  
Notes
2023-07-21 16:48:24CONTRACTOR'S ASBESTOS ACKNOWLEDGMENT
 1-CONTRACTOR TO PROVIDE A SIGNED ACKNOWLEDGMENT LETTER,
 ON CONTRACTOR'S LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 15:32 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 17:41 Sent To  
Notes
2023-07-20 18:45:2407/20/23 COMMENTS REVISED:
 **PERMIT DESCRIPTION AND PHASING AGREED BETWEEN DON
 JOHNSON AND ROBERT BROWN ON 7/20/23. RB**
  
 PHASE 1: MOVE EXISTG HOUSE ON SAME LOT AND DEMO POOL &
 CABANA. SEPERATE PERMIT FOR PHASE 2 WILL BE ADDITN TO
 EXISITNG HOUSE AFTER RELOCATION.
  
  
 BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PHASE 1 PERMIT #23041293
 3140 WASHINGTON RD
  
 DEMOLITION CHECKLIST
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING SECTION
 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 WATERDOWN METHOD:
  
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFORMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS.
  
 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART
 MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7- PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 FOR INFORMATION ONLY (BECAUSE OF NEW SOFTWARE
 IMPLEMENTATION):
 07/21/23 PERMIT DESCRIPTION WAS CHANGED BY ROBERT
 BROWN. PERMIT WAS NOT CHANGED TO DEMO TO AVOID
 CONFLICTS WITH NEW SOFTWARE IMPLEMENTATION AND THE LAST
 DATA PULL OUT BY TAYLOR DONE ON 07/19/23.JG.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By jgomez Date 2023-07-19 Time 13:39 Rev Time 0.00
Received By jgomez Date 2023-07-19 Time 09:03 Sent To  
Notes
2023-07-19 13:40:03RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041293
 3140 WASHINGTON RD
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 (1)-THE PROPOSED ALTERATION/ADDITION IS GOING TO BE
 BUILT IN A AE FLOOD ZONE WITH A BASE FLOOD ELEVATION
 (BFE) OF 6, 7 AND 8 FEET BASED ON NAVD 88.
 THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 NOTE: PLANS (INCLUDING THE FOUNDATION PLAN) NEED TO
 SHOW THE PROPOSED FINISHED FLOOR ELEVATIONS FOR MAIN
 HOUSE AND GARAGES. ALSO, NEED TO PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY
 SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE CONSTRUCTION OF THIS STRUCTURE THREE
 DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED:
 (A)CONSTRUCTION DRAWINGS.
 (B)BUILDING UNDER CONSTRUCTION.
 (C)FINISHED CONSTRUCTION.
  
 (2)- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
 COORDINATE WITH ITEM #1 ABOVE TO AVOID
 CONFLICTS/DELAYS.
  
 (3)STRUCTURAL PLANS ARE INCOMPLETE:
 (A) THEY DON'T SHOW THE PROPOSED ADDITION. ONLY
 EXISTING HOUSE IS PROVIDED. PROVIDE COMPLETE PLANS AND
 SHOW FINISH FLOOR ELEVATIONS. COORDINATE WITH ITEM #1
 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (B)DESIGN CRITERIA ON SHEET S100: ENGINEER TO SPECIFY
 THE WIND SPEED CONVERSION. SEC. R301.2.1.3
 FBC-RESIDENTIAL.
  
 (C)ENGINEER TO SPECIFY THE COMPONENTS AND CLADDING
 DESIGN PRESSURES FOR DOORS, WINDOWS, ROOFING COVERINGS,
 ETC.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (D)PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS
 SHOWING COMPLIANCE WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. SPECIFY NAIL TYPE, SIZE AND SPACING.
 NOTE: NEED TO USE RING SHANK NAILS. ROOF SHEATHING
 NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
  
 (4)PROVIDE COMPLETE SET OF PLANS INCLUDING WALL,
 SECTIONS, ALL EXTERIOR ELEVATIONS, ETC. SEC. 107.2.1
 CITY AMENDMENTS. SEC. 107.3.5.3 CITY AMENDMENTS.
  
 (5)PROVIDE COMPLETE FLOOR PLANS SHOWING THE DIMENSIONS
 OF ALL ROOMS. R304.2 FBC-RESIDENTIAL.
  
 (6) SPECIFY HOW PROVIDING HEAT TO THE PROPOSED
 ALTERATION AND ADDITION. PROVIDE MECHANICAL FLOR PLANS
 AND SPECIFICATIONS. SEC. R303.10 FBC-RESIDENTIAL.
  
 (7)CLEARLY SPECIFY THE SECOND FLOOR LIVE AND DEAD
 LOADS. SEC. R301.1 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND PLANTER AREA ON PROPOSED SECOND
 FLOOR PLAN TO AVOID CONFLICTS/DELAYS.
  
 (8) ROOF LIVE AND DEAD LOADS.
 CLEARLY SPECIFY THE TOP CHORD LIVE AND DEAD LOADS AND
 BOTTOM CHORD LIVE AND DEAD LOADS. SEC. R301.1
 FBC-RESIDENTIAL AND TABLE R301.5 FBC-RESIDENTIAL.
  
 (9)PROVIDE COMPLETE WINDOW AND DOOR SCHEDULES.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 (10)WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 (11)PLANS DON'T PROVIDE SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 (12)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING TERRACE GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN DESIGNER OF
 RECORD NEEDS TO SPECIFY THE DESIGN GUIDELINES REQUIRED
 BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 AND
 CLEARLY SPECIFY ON PLANS THAT SHOP DRAWINGS NEED TO BE
 SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. ALL SHOP
 DRAWINGS TO BE REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 (13)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION: DIMENSIONS, RISERS, TREADS,
 HANDRAILS, GUARDRAILS, ETC. SHOWING COMPLIANCE WITH
 SEC. R311.7 FBC-RESIDENTIAL.
  
 (14) NEED TO SPECIFY HANDRAILS BY ENTRY PORCH STAIRS AS
 REQUIRED BY SEC. R311.7.8 FBC-RESIDENTIAL.
  
 (15)SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS (NEW AND EXISTING) AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 (16)NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 (17)PROVIDE DETAILS/SPECIFICATIONS FOR FIREBLOCKING,
 INCLUDING STAIRWAYS AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 (18)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 (19)SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1
 FBC-RESIDENTIAL.
  
 (20)PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING
 SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 (21)PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 (22)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 WALL FLASHING AT ALL EXTERIOR OPENINGS. SEC. R703.4
 FBC-RESIDENTIAL.
  
 (23)PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
 (A)EXTERIOR DOORS AS SHOWN ON PLANS. (NOTE: PLEASE
 IDENTIFY EACH PRODUCT APPROVAL. FOR EXAMPLE ENTRY DOOR,
 GARAGE SWING DOOR, ETC.)
 (B)WINDOWS AS SHOWN ON PLANS.
 (C)WINDOWS AND DOORS MULLIONS (NOTE: NEED TO SPECIFY
 MULLION SIZE TO VERIFY PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL).
 (D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 (E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 (F)ROOF TILE. AND CLEARLY SPECIFY/MARK FASTENING
 METHOD.
 (G)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 (H)HIP & RIDGE METAL SUPPORT TO BE USED.
 (I)SECOND FLOOR DECK UNDERLAYMENT FOR FLOOR FINISH
 SPECIFIED ON PLANS.
 (J)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
 (K)FOOD VENTS IF SPECIFIED ON PLANS.
  
 (24)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 (25)SEPARATE PERMIT REQUIRED FOR DEMOLITION OF CABANA,
 EXTERIOR WALLS OF MAIN HOUSE, POOL & DECK. SEC. 105.1
 CITY AMENDMENTS.
  
 (26)VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE PROPOSED SCOPE OF WORK. VALUATION
 TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD
 AND PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE
 ALL COSTS. PROVIDE COMPLETE COST BREAKDOWN INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 (27) DIGITAL SIGNATURE REVIEW.
 (A)GEOTECHNICAL REPORT:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (B)PLUMBING PLANS SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (C)ELECTRICAL PLAN E1.1 SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (28)NEED ENERGY CALCULATIONS. SEC. 1106 FBC-EXISTING
 BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 11:22 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 11:13 Sent To  
Notes
2023-06-05 11:23:57FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected] PAGE SUBMITTED ALREADY APPROVED FOR
 FOUNDATION. JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-07-21 Cont ID  
Sent By lquinone Date 2023-07-21 Time 15:02 Rev Time 0.00
Received By lquinone Date 2023-07-21 Time 15:02 Sent To  
Notes
2023-07-21 15:05:27FOR THE DEMOLITION PHASE:
  
 PLEASE PROVIDE STORMWATER POLLUTION PREVENTION PLAN
 SHOWN ON COPY OF PROPERTY SURVEY - SILT FENCE AROUND
 PROPERTY TO PREVENT DEBRIS RUNOFF; PROTECT ROADWAY FROM
 TRACKING OF DIRT FROM TRUCKS HAULING DEBRIS; PROTECT
 ANY STORM DRAIN INLETS IN VICINITY USING BEST
 MANAGEMENT PRACTICES (FILTER FABRIC, ETC.)
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT, EMAIL
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-07-21 Cont ID  
Sent By ccole Date 2023-07-21 Time 16:30 Rev Time 0.00
Received By ccole Date 2023-07-21 Time 16:24 Sent To  
Notes
2023-07-21 16:32:29PLEASE PROVIDE A GAS SUB-PERMIT APPLICATION FOR GAS
 PIPING DEMO AND CAPPING.
  
 IF YOU HAVE QUESTIONS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-05-26 Cont ID  
Sent By ccole Date 2023-05-26 Time 11:39 Rev Time 0.00
Received By ccole Date 2023-05-26 Time 11:20 Sent To  
Notes
2023-05-26 11:40:241ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23041293
 5/26/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW COMMENT #1
 AND NOTE THAT GAS CAN BE UNDER A SEPARATE PERMIT IF
 REQUESTED.
  
 1) P1.1: THE PLAN SHOWS TWO BBQ GRILLS AND WHAT APPEARS
 TO BE A GAS RANGE IN THE KITCHEN. PLEASE PROVIDE GAS
 PLANS INCLUDING A PIPING LAYOUT DRAWING, A RISER
 DRAWING, GAS APPLIANCE EQUIPMENT SCHEDULES, AND
 COMBUSTION AIR AND VENTING PLANS- SECS. 107.1 &
 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-06-14 Cont ID  
Sent By fmittner Date 2023-06-14 Time 08:16 Rev Time 0.00
Received By fmittner Date 2023-06-14 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 18:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-19 Cont ID  
Sent By jgomez Date 2023-07-19 Time 13:50 Rev Time 0.00
Received By jgomez Date 2023-05-19 Time 09:22 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 16:39 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 16:39 Sent To  
Notes
2023-07-21 16:39:48THIS PERMIT IS ONLY FOR DEMOLITION OF POOL CABANA AND
 POOL AND RELOCATING EXISTING HOUSE ON THE SAME LOT. SEE
 FOUNDATION PERMIT #23041442 FOR IMPACT FEE COMMENTS.
 JG.
 NOTE: THIS PERMIT WAS INITIALLY PROCESSED AS
 RES-ADDITION. PERMIT TYPE COULD NOT BE CHANGED TO DEMO
 PERMIT TO AVOID CONFLICTS WITH CURRENT SOFTWARE
 IMPLEMENTATION BY CHANGING THE PERMIT TYPE. TAYLOR LAST
 DATA PULL OUT 07/19/23. JG.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By jgomez Date 2023-07-19 Time 13:50 Rev Time 0.00
Received By jgomez Date 2023-07-19 Time 13:50 Sent To  
Notes
2023-07-19 13:50:15IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-06-15 Cont ID  
Sent By hmoser Date 2023-06-15 Time 12:46 Rev Time 0.00
Received By hmoser Date 2023-06-15 Time 12:41 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 16:32 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 16:32 Sent To  
Notes
2023-07-21 16:37:33THIS PERMIT IS ONLY FOR DEMOLITION OF POOL CABANA AND
 POOL AND RELOCATING EXISTING HOUSE ON THE SAME LOT. SEE
 FOUNDATION PERMIT #23041442 FOR NFIP COMMENTS.
 NOTE: THIS PERMIT WAS INITIALLY PROCESSED AS
 RES-ADDITION. PERMIT TYPE COULD NOT BE CHANGED TO DEMO
 PERMIT TO AVOID CONFLICTS WITH CURRENT SOFTWARE
 IMPLEMENTATION BY CHANGING THE PERMIT TYPE. TAYLOR LAST
 DATA PULL OUT 07/19/23. JG.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By jgomez Date 2023-07-19 Time 13:45 Rev Time 0.00
Received By jgomez Date 2023-07-19 Time 13:45 Sent To  
Notes
2023-07-19 13:47:36NFIP COMMENTS:
  
 (1)-THE PROPOSED ALTERATION/ADDITION IS GOING TO BE
 BUILT IN A AE FLOOD ZONE WITH A BASE FLOOD ELEVATION
 (BFE) OF 6, 7 AND 8 FEET BASED ON NAVD 88.
 THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 NOTE: PLANS (INCLUDING THE FOUNDATION PLAN) NEED TO
 SHOW THE PROPOSED FINISHED FLOOR ELEVATIONS FOR MAIN
 HOUSE AND GARAGES. ALSO, NEED TO PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY
 SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE CONSTRUCTION OF THIS STRUCTURE THREE
 DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED:
 (A)CONSTRUCTION DRAWINGS.
 (B)BUILDING UNDER CONSTRUCTION.
 (C)FINISHED CONSTRUCTION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-07-21 Cont ID  
Sent By ccole Date 2023-07-21 Time 16:32 Rev Time 0.00
Received By ccole Date 2023-07-21 Time 16:24 Sent To  
Notes
2023-07-21 16:34:01PLEASE PROVIDE A PLUMBING SUB-PERMIT APPLICATION FOR
 PLUMBING DEMOLITION.
  
 IF YOU HAVE QUESTIONS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-05-26 Cont ID  
Sent By ccole Date 2023-05-26 Time 11:20 Rev Time 0.00
Received By ccole Date 2023-05-26 Time 10:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 16:40 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 16:40 Sent To  
Notes
2023-07-21 16:41:05THIS PERMIT IS ONLY FOR DEMOLITION OF POOL CABANA AND
 POOL AND RELOCATING EXISTING HOUSE ON THE SAME LOT. JG.
 NOTE: THIS PERMIT WAS INITIALLY PROCESSED AS
 RES-ADDITION. PERMIT TYPE COULD NOT BE CHANGED TO DEMO
 PERMIT TO AVOID CONFLICTS WITH CURRENT SOFTWARE
 IMPLEMENTATION BY CHANGING THE PERMIT TYPE. TAYLOR LAST
 DATA PULL OUT 07/19/23. JG.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By jgomez Date 2023-07-19 Time 13:41 Rev Time 0.00
Received By jgomez Date 2023-07-19 Time 13:41 Sent To  
Notes
2023-07-19 13:44:30(1) PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
  
 (A) ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 (B) ROOF TILE. AND CLEARLY SPECIFY/MARK FASTENING
 METHOD.
 (C) ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 (D)HIP & RIDGE METAL SUPPORT TO BE USED.
 (E)SECOND FLOOR DECK UNDERLAYMENT FOR FLOOR FINISH
 SPECIFIED ON PLANS.
 (F)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 (2)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 16:41 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 16:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By jleahy Date 2023-06-05 Time 11:21 Rev Time 0.00
Received By jgomez Date 2023-06-05 Time 11:13 Sent To  
Notes
2023-07-19 13:40:46DIGITAL SIGNATURE REVIEW.
  
 (A)GEOTECHNICAL REPORT:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (B)PLUMBING PLANS SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (C)ELECTRICAL PLAN E1.1 SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
2023-05-26 12:07:14PLUMBING SIGNATURES PASSED.

Review Stop Z ZONING
Rev No 1 Status P Date 2023-06-14 Cont ID  
Sent By fmittner Date 2023-06-14 Time 08:16 Rev Time 0.00
Received By fmittner Date 2023-06-14 Time 08:16 Sent To  
Notes
***NONE***