Plan Review Details - Permit 23041240
Plan Review Stops For Permit 23041240
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-22 Cont ID  
Sent By pvalenti Date 2023-06-22 Time 13:05 Rev Time 0.00
Received By pvalenti Date 2023-06-22 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By jbrooks Date 2023-05-02 Time 13:23 Rev Time 0.00
Received By jbrooks Date 2023-05-02 Time 08:25 Sent To  
Notes
2023-05-02 13:25:27JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2
 MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE
 DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE
 ROOF APPLICATIONS SYSTEM NO. UDL-13 DO NOT MEET OR
 EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A
 HIP ROOF; (3:12 AND OVER) ROOF SLOPE; MEAN ROOF HEIGHT
 15 FT. MINIMUM DESIGN PRESSURE REQUIREMENT OF -115.5 IN
 AN EXPOSURE CATEGORY C AREA. PROVIDE UNDERLAYMENT
 SYSTEM THAT MEETS OR EXCEEDS THE ABOVE CRITERIA. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-28 Cont ID  
Sent By jbrooks Date 2023-04-28 Time 08:50 Rev Time 0.00
Received By jbrooks Date 2023-04-28 Time 07:43 Sent To  
Notes
2023-04-28 08:50:56JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36
 HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF
 APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL12328-R9
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL12328-R10 (NON-HVHZ).
 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED. (FL5374-R6)
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-02 Cont ID  
Sent By jbrooks Date 2023-05-02 Time 13:25 Rev Time 0.00
Received By jbrooks Date 2023-04-28 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-28 Cont ID  
Sent By jbrooks Date 2023-04-28 Time 08:51 Rev Time 0.00
Received By jbrooks Date 2023-04-27 Time 08:44 Sent To  
Notes
***NONE***