Plan Review Details - Permit 23041197
Plan Review Stops For Permit 23041197 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-05-24 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-05-24 |
Time |
07:28 |
Sent To |
|
|
Notes |
2023-05-24 14:44:09 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE VULT WINDSPEED FOR THIS PROJECT IS 170 MPH. | | PLEASE REVISE FROM THE 168 MPH VULT SOECIFIED ON SHEET | | T-1. FBC CITY AMENDMENTS SECTION 120 | | | | 2) ON SHEET C-4 IT APPEARS THAT THE E.V. CHARGING | | STATION PARTIALLY BLOCKS THE ACCESS AISLE FROM THE | | ACCESSIBILE ROUTE TO THE ACCESSIBLE ENTRANCE. PLEASE | | CLARIFY. FBC ACCESSIBILITY SECTION 502.3 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-05-05 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-05-05 |
Time |
07:09 |
Sent To |
|
|
Notes |
2023-05-05 08:32:25 | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) VALUE OF PROJECT IS SUPER LOW FOR A SUPER CHARGER. | | PLEASE SUBMIT A COST BREAKDOWN OF THE EQUIPMENT AND | | LABOR FOR A COMPLETE JOB.INCLUDE ALL MATERIALS SUPPLIED | | BY CUSTOMER AND OR CONTRACTOR. | | | | 2) COR-FLEX CONDUIT PLEASE SUBMIT THE LISTING FOR THIS | | PRODUCT. 110.3 | | | | 3) PROVIDE CUT SHEETS FOR PEDESTALS SHOWING LISTING | | 110.3, 625.5 | | | | 4) PROVIDE LISTING FOR ALL EQUIPMENT SUPERCHARGER V3 | | 110.3, 625.5 | | | | 5) PROVIDE COMPLIANCE WITH 625.43 FOR THE DISCONNECTING | | MEANS FOR THESE PEDESTALS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2023-06-15 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2023-06-15 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2023-06-15 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-06-16 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-16 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-04-28 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-05-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-05-24 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-05-24 |
Time |
07:28 |
Sent To |
|
|
Notes |
2023-05-24 15:03:01 | THE PAVING AND DRAINING PLAN IS NOT DIGITALLY SIGNED BY | | THE ENGINEER. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC | | 61G15 | | IF THE DRAWING IS TO BE USED FOR REFERENCE ONLY, PLEASE | | MARK IT AS SUCH. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-05-22 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-05-22 |
Time |
10:42 |
Sent To |
|
|
Notes |
2023-05-22 10:44:38 | FAILED | | 5/22/2023 | | | | EV SPACES CAN ONLY BE IMPLUMENTED IF THERE IS EXCESS | | PARKING | | | | | | PLEASE PROVIDE A PARKING TABLE WITH TOTAL NUMBER OF | | REQUIRED PARKING SPACES FOR THE PROPERTY WHAT IS | | EXISTING AND NUMBER OF SPACES PROPOSED TO BE EV SPACES | | | | | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|
|