Plan Review Details - Permit 23041184
Plan Review Stops For Permit 23041184
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By rmcphers Date 2023-07-13 Time 13:22 Rev Time 0.00
Received By rmcphers Date 2023-07-13 Time 13:17 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2023-05-30 Time 16:09 Sent To  
Notes
2023-06-01 08:57:26PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-14 Cont ID  
Sent By rmcphers Date 2023-07-14 Time 07:47 Rev Time 0.00
Received By rmcphers Date 2023-07-13 Time 13:17 Sent To  
Notes
2023-07-13 15:53:00BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GUARD RAIL LOCATIONS (3RD FLOOR HALL
 WAY, STAIR PLATFORMS OVERLOOKING "TIMBER HALL", ETC.) -
 FBC 1015.2
  
 2) DRAWING A-415 DETAIL 1 - PLEASE SHOW THE REQUIRED
 HAND RAILS FOR BOTH SIDES OF THE STAIR FROM THE "TIMBER
 HALL" - 1011.11 HANDRAILS. FLIGHTS OF STAIRWAYS SHALL
 HAVE HANDRAILS ON EACH SIDE AND SHALL COMPLY WITH
 SECTION 1014.
  
 3) DRAWING A-413 AND A-411 - PLEASE SHOW THE BOTTOM
 HAND RAIL TO CONTINUE TO SLOPE - FBC 1014.6 WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 4) PLEASE SHOW RESTROOM CEILING TO COMPLY WITH FBC
 468.3.5.10 CEILINGS.
 CEILINGS IN GROUP TOILET ROOMS, KITCHENS, SCULLERIES,
 CAN WASH AREAS, SHOWERS AND LOCKER ROOMS SHALL BE
 IMPERVIOUS.
  
 5) DOOR 113 IS SHOWN ON THE DOOR SCHEDULE AS 9 FOOT
 WIDE - (PLEASE CLARIFY) THE MAXIMUM DOOR WIDTH IS 4
 FOOT PER FBC 1010.1.1
  
 6) PLEASE SHOW RESTROOM AND MOP SINK WALL FINISHES TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 7) DRAWINGS SAY TO SEE THE ENERGY CALCS. FOR EXTERIOR
 WALL INSULATION - THE ENERGY CALCS. PROVIDED DO NOT
 APPEAR TO SHOW THE CORRECT EXTERIOR WALL CONFIGURATION
 (2X4 WALLS WITH R-11) ?
  
 8) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN - FBC 1603.1.4
  
 9) THE BUILDING IS A RISK CATEGORY III PER FBC TABLE
 1604.5
  
 10) THE CHANGE OF OCCUPANCY TO A HIGHER RISK CATEGORY
 REQUIRES A WIND DESIGN ANALYSIS REPORT SIGNED AND
 SEALED FROM A DESIGN PROFESSIONAL - FBC EXISTING
 BUILDING 1007.2 SNOW AND WIND LOADS.
 BUILDINGS AND STRUCTURES SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER WIND OR SNOW RISK CATEGORIES BASED ON
 THE FLORIDA BUILDING CODE, BUILDING TABLE 1604.5,
 (HIGH-VELOCITY HURRICANE ZONES SHALL COMPLY WITH
 SECTION 1620) SHALL BE ANALYZED AND SHALL COMPLY WITH
 THE APPLICABLE WIND OR SNOW LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 11) PLEASE SHOW THE TERMITE PROTECTION TYPE PER FBC
 1816
  
 12) DRAWING LS-101 SHOWS A CLASS ROOM WITH 1078 SQ.FT.
 AND 54 OCCUPANTS - 2 MEANS OF EGRESS WOULD BE REQUIRED
 FOR THAT SPACE - FBC 1006.2.1
  
 13) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL13303 (SKY LIGHT) FBC 107.2.1
  
 14) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL18413 (DOOR) FBC 107.2.1
  
 15) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL20877 (STOREFRONT WALL) FBC 107.2.1
  
 16) PRODUCT APPROVAL PROVIDED FOR THE ROOFING SYSTEM =
 IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL.
  
 17) THE DRAWING A-100.1 SHOWS CLOSER PARKING SPACES -
 PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING AND SIDEWALKS TO THE ACCESSIBLE ENTRY - FBC A
 208.3LOCATION. PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4
 FBC A 208.1.2 - A FACILITY THAT IS MAKING ALTERATIONS
 UNDER SECTION 202 AS REQUIRED BY S.303(A) OF THE
 AMERICANS WITH DISABILITES ACT OF 1990 MUST COMPLY WITH
 SECTION 208 TO THE MAXIMUM EXTENT FEASIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2023-05-30 Time 16:09 Sent To  
Notes
2023-06-01 09:22:36BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THERE ARE STRUCTURAL DRAWINGS LISTED ON THE COVER
 SHEET WHICH ARE NOT IN PROJECTDOX - FBC WPB 107.2
  
 2) DRAWING LS-101 UNDER "EXIT CAPACITY GROUND LEVEL" -
 EXIT NUMBER 113 IS NOTED BUT IS NOT SHOWN ON THE
 DRAWINGS - PLEASE CLARIFY
  
 3) PLEASE PROVIDE AN EXISTING FLOOR PLAN.
  
 4) PLEASE DESCRIBE THE ROOM (110) OR THE ITEM LABELED
 "LIFT" .
  
 5) PLEASE PROVIDE GUARD RAIL DETAILS - FBC 1015.2
  
 6) PLEASE SHOW THE ROOF HATCH DISTANCE FROM THE
 BUILDING EDGE - FBC 1015.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A
 WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW.
  
 7) PLEASE SHOW THE REQUIRED HAND RAILS FOR BOTH SIDES
 OF THE GRAND STAIR - 1011.11 HANDRAILS. FLIGHTS OF
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE AND SHALL
 COMPLY WITH SECTION 1014.
  
 8) DRAWING A-413 - PLEASE SHOW THE BOTTOM HAND RAIL TO
 CONTINUE TO SLOPE (ONE SIDE OF THE SECTION SHOWS THE
 HAND RAIL TO SLOPE CORRECTLY) - FBC 1014.6 WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 9) PLEASE SHOW THE FIRE RATED WALLS DESIGN ASSEMBLY (UL
 NUMBERS) - FBC 703.3
  
 10) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTEIOR WINDOWS AND DOORS
 - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 11) PLEASE SHOW THE BUILDING SET BACKS FROM THE
 PROPERTY LINES - A SITE PLAN SHOULD INCLUDE THE
 FOLLOWING - FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 12) EXTERIOR DOORS SHALL NOT ENCROACH INTO OTHER
 PROPERTIES - FBC 3202.2 ENCROACHMENTS ABOVE GRADE AND
 BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 13) PLEASE SHOW THE REQUIRED FIRE RATING FOR THE RATED
 DOOR ON THE DOOR SCHEDULE - FBC 716
  
 14) PLEASE SHOW REQUIRED DOOR CLOSURES -
 FBC 468.3.5.3.3 TOILET ROOMS ADJACENT TO FOOD
 PREPARATION OR DINING AREAS SHALL BE COMPLETELY
 ENCLOSED, HAVE SELF-CLOSING DOORS, AND SHALL OPEN INTO
 VESTIBULES WITH SELF-CLOSING DOORS.
 FBC 716.5.9 DOOR CLOSING. FIRE DOORS SHALL BE LATCHING
 AND SELF- OR AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS
 SECTION.
  
 15) PLEASE SHOW RESTROOM CEILING TO COMPLY WITH FBC
 468.3.5.10 CEILINGS.
 CEILINGS IN GROUP TOILET ROOMS, KITCHENS, SCULLERIES,
 CAN WASH AREAS, SHOWERS AND LOCKER ROOMS SHALL BE
 IMPERVIOUS.
  
 16) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 DISPENSER LOCATIONS PER FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 17) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERING TO THE MIRROR
 LOCATIONS - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 18) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET GRAB
 BAR HEIGHT TO THE TOP OF THE GRIPPING SURFACE (NOT THE
 CENTER) - FBC A 609.4POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 19) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE GRAND STAIR
 BALCONY MEETING PLACES - FBC A 206.2.3 MULTI-STORY
 BUILDINGS AND FACILITIES.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT EACH STORY
 AND MEZZANINE IN MULTI-STORY BUILDINGS AND FACILITIES.
  
 20) PLEASE SHOW THE USE FOR THE TOWER ROOM AND THE
 ACCESSIBLE ROUTE - FBC A 206.2.3 MULTI-STORY BUILDINGS
 AND FACILITIES.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT EACH STORY
 AND MEZZANINE IN MULTI-STORY BUILDINGS AND FACILITIES.
  
 21) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE
 ACCESSIBLE PARKING AND SIDEWALKS TO THE ACCESSIBLE
 ENTRY - FBC 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-12 Cont ID  
Sent By rperdomo Date 2023-07-12 Time 16:23 Rev Time 0.00
Received By rperdomo Date 2023-07-12 Time 15:36 Sent To  
Notes
2023-07-12 16:23:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW
  
 1. SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WIRING.
  
 END OF COMMENTS
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-25 Cont ID  
Sent By rperdomo Date 2023-05-25 Time 16:12 Rev Time 0.00
Received By rperdomo Date 2023-05-25 Time 15:09 Sent To  
Notes
2023-05-25 16:14:15FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW
  
 1. SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WIRING.
  
 END OF COMMENTS
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By lquinone Date 2023-07-13 Time 10:21 Rev Time 0.00
Received By lquinone Date 2023-07-13 Time 10:21 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-05-11 Cont ID  
Sent By parking Date 2023-05-11 Time 15:30 Rev Time 0.00
Received By lquinone Date 2023-05-11 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-11 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-10 Cont ID  
Sent By pleduc Date 2023-05-10 Time   Rev Time 0.00
Received By pleduc Date 2023-05-02 Time 13:57 Sent To  
Notes
2023-05-09 14:24:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NUMEROUS STAIRS LOCATED THROUGHOUT THIS
 EDUCATIONAL OCCUPANCY.
  
 14.2.1 GENERAL.
  
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7 AND
 SECTION 14.2
  
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR FIRST GRADE STUDENTS SHALL BE LOCATED
 ON A LEVEL OF EXIT DISCHARGE, UNLESS OTH ERWISE
 PERMITTED BY 14.2.1.4.
  
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL NOT
 BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF EXIT
 DISCHARGE, UNLESS
 OTHERWISE PERMITTED BY 14.2.1.4
  
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS SPECIFIED
 IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED TO BE USED
 WHERE PROVIDED
 WITH INDEPENDENT MEANS OF EGRESS DEDICATED FOR USE BY
 THE PRESCHOOL,
 KINDERGARTEN, FIRST-GRADE, OR SECOND-GRADE STUDENTS
  
 HOW IS IT INSURED THAT STUDENTS OF CERTAIN AGES WILL
 NOT BE USING AREAS WITH STAIRS?
  
  
  
 2) SHEET LS 103 - THERE IS AN INDICATION OF A
 MEZZANINCE ROOM
  
 3.3.184 MEZZANINE. AN INTERMEDIATE LEVEL BETWEEN THE
 FLOOR AND THE
 CEILING OF ANY ROOM OR SPACE. (SAF-FIR)
  
 14.2.1 GENERAL.
  
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7 AND
 SECTION 14.2
  
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR FIRST GRADE
 STUDENTS SHALL BE LOCATED ON A LEVEL OF EXIT DISCHARGE,
 UNLESS OTH ERWISE PERMITTED BY 14.2.1.4.
  
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL NOT
 BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF EXIT
 DISCHARGE, UNLESS
 OTHERWISE PERMITTED BY 14.2.1.4
  
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS SPECIFIED
 IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED TO BE USED
 WHERE PROVIDED
 WITH INDEPENDENT MEANS OF EGRESS DEDICATED FOR USE BY
 THE PRESCHOOL,
 KINDERGARTEN, FIRST-GRADE, OR SECOND-GRADE STUDENTS.
  
 HOW IS IT INSURED THAT STUDENTS WILL NOT BE USING THESE
 SPACES?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET LS 103 - THERE IS AN INDICATION OF A
 MEZZANINCE ROOM WITH A SINGLE EXIT.
  
 PER NFPA 101
  
 7.4.1 GENERAL.
  
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE,
 STORY, OR PORTION THEREOF SHALL BE NOT LESS THAN TWO,
 EXCEPT UNDER ONE OF
 THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN
 CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR
 BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 14.2.5.3.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100
 FT (30 M) IN A
 BUILDING PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7
  
 PLEASE PROVIDE THE TRAVEL DISTANCE INDCATING COMPLIANCE
 WITH THE REQUERMENT.
  
  
  
 4) SHEET A 101 THRU 104 - THERE ARE INDICATIONS OF
 LIFTS, WHICH APPEAR TO BE ELEVATORS.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER'S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE OR
 JUSTIFY WITH SPECITICDETAILED NARRATIVE AND CODE
 REFERENCES
  
  
  
 5) LIFE SAFETY SHEETS - THERE ARE NO INDICATIONS OF
 AREAS OF REFUGE.
  
 AREAS OF REFUGE SHALL COMPLY WHERE APPLICABLE PER THE
 BUILDING CODE AND NFPA 101, CH 7, MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) LIFE SAFETY SHEETS - EMERGENCY RADIO SIGNAL STRENGTH
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH
 FIRE DEPARTMENT. TESTING SHALL BE DONE BY FIRE
 INSPECTOR PORTABLE RADIOS.
  
 IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL
 AMPLIFIED SYSTEM SHALL BE INSTALLED UNDER SEPARATE
 PERMIT WITH A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 ANY SYSTEM SHALL NOT BE INSTALLED WITHOUT CONTACTING
 AND COORDINATION WITH MARK FILLA, PALM BEACH COUNTY
 PUBLIC SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT TO
 COMPLY.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-07-13 Cont ID  
Sent By ccole Date 2023-07-13 Time 10:13 Rev Time 0.00
Received By ccole Date 2023-07-12 Time 15:50 Sent To  
Notes
2023-07-13 10:14:21GAS HAS BEEN REMOVED FROM THE PROJECT PER ARCHITECT'S
 LETTER.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By ccole Date 2023-05-22 Time 12:37 Rev Time 0.00
Received By ccole Date 2023-05-22 Time 07:31 Sent To  
Notes
2023-05-22 12:38:001ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23041184
 5/22/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2.1 & P3.1: PROVIDE A COMPLETE GAS RISER
 DRAWING AS REQUIRED BY SEC. 107.3.5.1.5 WPB. THE GAS
 RISER SHALL INCLUDE THE FOLLOWING INFORMATION PER SEC.
 402.2 FBC FG.
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS AND SHUTOFF VALVES, AND
 REGULATOR VENT PIPING DETAILS (IF APPLICABLE).
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 2) P3.1: SHOW THE LOCATIONS OF THE GAS APPLIANCES ON
 THE FLOOR PLAN AND ADD NOTES TO IDENTIFY THEM- SEC.
 107.2.1 WPB.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS
 APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SEC. 304.1 FBC FG.
  
 4) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE
 APPLIANCES INCLUDING A DIAGRAM SHOWING THE TYPES AND
 SIZES OF VENTS, VENT RUNS, AND TERMINATION LOCATIONS-
 SECS. 502.1 & 503.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-07-17 Cont ID  
Sent By fmittner Date 2023-07-17 Time 14:55 Rev Time 0.00
Received By fmittner Date 2023-07-17 Time 14:55 Sent To  
Notes
2023-07-17 14:58:16PERMIT FILED FOR INTERIOR WORK, YET DRAWINGS SHOW
 EXTERIOR WINDOW & DOOR CHANGES.
  
 PLEASE SPECIFY:
  
 - FARME & GLAZING COLOR FOR STOREFRONTS AND SKYLIGHTS
 - UNDER APPLICABLE CODES, PLEASE NOTE THIS IS A
 HISTORIC BUILDING AND FALLS UNDER THE HISTORIC
 PRESERVATION REGULATIONS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-18 Cont ID  
Sent By aoliver Date 2023-07-18 Time 08:10 Rev Time 0.00
Received By aoliver Date 2023-07-07 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-09 Cont ID  
Sent By hmoser Date 2023-06-09 Time 14:54 Rev Time 0.00
Received By hmoser Date 2023-04-28 Time 12:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-07-13 Cont ID  
Sent By hmoser Date 2023-07-13 Time 15:51 Rev Time 0.00
Received By hmoser Date 2023-07-13 Time 13:11 Sent To  
Notes
2023-07-13 15:51:35PLAN DENIED
 1) FUME HOODS REQUIRE SEPARATE APPLICATION, PLAN AND
 PERMIT
 SECTION 107 FBC
 2) PAGE M3.2 AND M.3.3 AER MISSING FROM PLAN. SECTION
 107 FBC
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-06-09 Cont ID  
Sent By hmoser Date 2023-06-09 Time 14:54 Rev Time 0.00
Received By hmoser Date 2023-06-09 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-07-13 Cont ID  
Sent By ccole Date 2023-07-13 Time 10:09 Rev Time 0.00
Received By ccole Date 2023-07-12 Time 15:50 Sent To  
Notes
2023-07-13 10:13:082ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23041184
 7/13/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #3, 3A, 13, & 15 ARE LISTED WITH ADDITIONAL NOTES FOR
 FURTHER CLARIFICATION. NEW COMMENTS LISTED ARE BASED ON
 DESIGN CHANGES TO THE ORIGINAL PLANS.
  
 3) FAILED. P1.0 WATER HEATER DETAIL: THE THERMOSTAT
 CONTROL ON THE WATER HEATER CANNOT BE THE LIMITING
 DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE A DETAIL
 FOR A LIMITING DEVICE SUCH AS A MASTER THERMOSTATIC
 MIXING VALVE FOR THE PURPOSE OF HOT WATER DELIVERY-
 SEC. 607.1.1 FBC P.
 REQUIRED MASTER THERMOSTATIC MIXING VALVES AT WATER
 HEATERS NOT PROVIDED.
  
 A) REFER TO SEC. 468.3.5.1.2 FBC B: POINT OF USE MIXING
 VALVES SHALL BE INSTALLED AT ALL HANDWASH SINKS AND
 LAVATORIES TO LIMIT THE HOT WATER DELIVERY TEMPERATURE
 TO 110 DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE
 VALVES SPECIFIED IN THE SCHEDULE.
 REQUIRED POINT OF USE MIXING VALVES AT SINKS NOT
 PROVIDED.
  
 16) FAILED. PROVIDE THE COMPLIANCE DATA FOR THE WATER
 HEATERS ON THE ENERGYGAUGE FORM- SEC. C101.5.1 FBC EC.
 REQUIRED COMPLIANCE DATA NOT PROVIDED.
  
 NEW COMMENTS
  
 1) SHEETS P1.0, A-101, A-101, A-104, & A-504: THE
 LEADING EDGES OF DRINKING FOUNTAINS ARE PROTRUDING INTO
 THE CIRCULATION PATHS.THE FOUNTAINS SHALL EITHER BE
 EQUIPPED WITH CANE APRONS, PROVIDED WITH BARRIERS ON
 THE SIDES, OR INSTALLED IN NICHES- SEC. 307.2 FBC ACC.
 A) PLEASE ACCURATELY SHOW THE SPOUT HEIGHTS OF THE
 WHEELCHAIR ACCESSIBLE FOUNTAIN AND THE FOUNTAIN FOR
 STANDING PERSONS- SECS. 602.4- 602.7 FBC ACC.
  
 2) A-102: THE REVISED FLOOR PLAN SHOWS NEW 5 CHEMISTRY
 SINKS IN THE SCIENCE CLASSROOM. PLEASE REFER TO SEC.
 212.3 FBC ACC- A MINIMUM OF ONE SINK SHALL BE
 ACCESSIBLE AND INSTALLED IN COMPLIANCE WITH SECS.
 606.2, 606.3, 606.4 & 606.5. PLEASE PROVIDE COMPLIANCE
 DETAILS ON THE PLANS.
  
 3) P-1.0, P-3.2, & P-5.1: CHEMICAL WASTE FROM THE
 CHEMISTRY SINKS SHALL NOT DISCHARGE INTO THE SANITARY
 SYSTEM UNTIL THE WASTE HAS EITHER BEEN THOROUGHLY
 DILUTED, NEUTRALIZED OR TREATED BY PASSING THROUGH AN
 APPROVED DILUTION OR NEUTRALIZING DEVICE- SECS. 803.1 &
 803.2 FBC P. PLEASE PROVIDE COMPLIANCE DERTILS ON THE
 PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By ccole Date 2023-05-22 Time 12:08 Rev Time 0.00
Received By ccole Date 2023-05-22 Time 07:31 Sent To  
Notes
2023-05-22 12:10:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23041184
 5/22/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A101: THE PLUMBING FIXTURE CALCULATIONS ON
 A-101 INDICATE 7 DRINKING FOUNTAINS PROVIDED HOWEVER
 THE PLUMBING PLANS ARE SHOWING ONLY SIX- TABLE 403.1
 FBC P. PLEASE NOTE THE ARCHITECTURAL AND LIFE SAFETY
 PLANS DO NOT SHOW THE DRINKING FOUNTAIN LOCATIONS ON
 THE FLOOR PLANS- SEC. 107.2.1 WPB.
  
 2) P1.0, P2.1, P2.2, P2.3: REFER TO 468.3.5.6 FBC B AND
 PROVIDE HOSE BIBS IN EACH MALE AND FEMALE GROUP TOILET
 ROOM.
  
 3) P1.0 WATER HEATER DETAIL: THE THERMOSTAT CONTROL ON
 THE WATER HEATER CANNOT BE THE LIMITING DEVICE FOR HOT
 WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING
 DEVICE SUCH AS A MASTER THERMOSTATIC MIXING VALVE FOR
 THE PURPOSE OF HOT WATER DELIVERY- SEC. 607.1.1 FBC P.
 A) REFER TO SEC. 468.3.5.1.2 FBC B: POINT OF USE MIXING
 VALVES SHALL BE INSTALLED AT ALL HANDWASH SINKS AND
 LAVATORIES TO LIMIT THE HOT WATER DELIVERY TEMPERATURE
 TO 110 DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE
 VALVES SPECIFIED IN THE SCHEDULE.
  
 4) P1.0: CORRECT THE SUMP INSTALLATION DETAIL SHOWING
 THE DRAINAGE TO THE STORM DRAIN. THE DRAINAGE SHALL
 DISCHARGE TO THE SANITARY AS SHOWN ON THE ISOMETRIC
 DRAWING- SEC. 712.1 FBC P. A) PLEASE NOTE AN OIL
 SEPARATOR SHALL BE INSTALLED FOR THE SUMP PUMP DRAINAGE
 UNLESS AN APPROVED ALARM SYSTEM IS PROVIDED- SEC.
 1003.4.
  
 5) P2.1, P2.2: PLEASE CONFIRM HOT WATER WILL NOT BE
 PROVIDED TO THE EMERGENCY SHOWER AND EYE WASH STATIONS.
 PLEASE NOTE IF HOT WATER IS PROVIDED AN ASSE 1071
 MIXING VALVE IS REQUIRED TO LIMIT THE HOT WATER
 TEMPERATURE TO ISEA Z358.1 SPECIFICATIONS- SEC. 411.1
 FBC P.
  
 6) P3.1: NOTE 1 SHOWS THE SANITARY DRAINAGE CONNECTING
 TO THE EXISTING LINE IN LIFT 110 SPACE. IS THIS A TYPO?
 PLEASE SHOW THE EXISTING LINE RUN ON THE DRAWING AND IN
 THE ISOMETRIC DRAWING ON P5.1- SEC. 107.2.1 WPB. A)
 PLEASE SHOW A NEW OR EXISTING SUMP PUMP AND PIT FOR
 LIFT 110 AND PROVIDE DRAINAGE DETAILS- SECS. 712.1 &
 1003.4 FBC P.
  
 7) P1.0 & P3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 NEUTRALIZER TANK AND SUBMIT MANUFACTURER SPECIFICATIONS
 AND INSTALLATION GUIDELINES- SEC. 803.1 FBC P.
  
 8) P3.1, P3.2, P3.3, P5.1: PLEASE PROVIDE DRAIN AND
 VENT PIPE SIZES- SECS. 710.1 & 901.2.1 FBC P.
  
 9) P4.1 & P5.1: PLEASE SHOW A MINIMUM OF ONE BUILDING
 DRAIN VENT PIPE EXTENDING TO THE OUTDOORS- SEC. 904.1
 FBC P.
  
 10) P5.1: PLEASE PROVIDE A WATER RISER DRAWING- SEC.
 107.3.5.1.3 WPB.
  
 11) A500: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE REQUIRED ACCESSIBLE URINAL- SECS.
 213.3.3 & 605.3 FBC ACC.
  
 12) A501: THE DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACES REQUIRED FOR THE WATER CLOSETS- SEC.
 603.2.3 FBC ACC. PLEASE SEE EXCEPTION 1 AND CORRECT THE
 PLAN.
  
 13) A502 & A504: PLEASE ACCURATELY SHOW THE CENTERLINES
 OF THE WATER CLOSETS FROM THE SIDE WALLS- SEC. 604.2
 FBC ACC- 16 INCHES MINIMUM 18 INCHES MAXIMUM.
  
 14) A504: SHOW THE CENTERLINES OF THE TOILET PAPER
 DISPENSERS MEASURED FROM THE FRONTS OF THE WATER
 CLOSETS- SEC. AND FIGURE 604.7 FBC ACC.
  
 15) A504: SHOW THE MOUNTING HEIGHTS OF GRAB BARS FOR
 THE WATER CLOSETS MEASURED TO THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4 FBC ACC.
  
 16) PROVIDE THE COMPLIANCE DATA FOR THE WATER HEATERS
 ON THE ENERGYGAUGE FORM- SEC. C101.5.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By rmcphers Date 2023-07-14 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2023-07-14 Time 08:13 Sent To  
Notes
2023-07-13 10:15:56PLUMBING PLAN SIGS PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-01 Cont ID  
Sent By rmcphers Date 2023-06-01 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2023-06-01 Time 11:30 Sent To  
Notes
2023-05-22 12:15:38PLUMBING SIGNATURES PASSED.

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By llouie Date 2023-07-13 Time   Rev Time 0.00
Received By llouie Date 2023-07-13 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-19 Cont ID  
Sent By llouie Date 2023-05-19 Time   Rev Time  
Received By llouie Date 2023-05-19 Time   Sent To  
Notes
2023-05-19 11:12:11** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) AN UPDATED SIGNED AND SEALED SURVEY IS REQUIRED.
 THE SURVEY PROVIDED IS OUTDATED.
  
 2.) A DEMOLITION PLAN IS REQUIRED TO SHOW WHAT CHANGES
 ARE BEING MADE TO THE EXISTING BUILDING. HISTORIC
 REVIEW WILL BE REQUIRED; A HISTORIC REVIEW STOP HAS
 BEEN ADDED TO THE PERMIT.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTATC LINDA LOUIE @ 561.822.1458 IF THERE ARE
 QUESTIONS.
  
 * Z = GC (GREENE SCHOOL - EMKO BUILDING).
  