Plan Review Details - Permit 23041099
Plan Review Stops For Permit 23041099
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-25 Cont ID  
Sent By cpuell Date 2023-04-25 Time 07:48 Rev Time 0.00
Received By cpuell Date 2023-04-25 Time 07:48 Sent To  
Notes
2023-04-25 07:48:47ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time 09:32 Rev Time  
Received By lbond Date   Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time 13:39 Rev Time  
Received By lbond Date   Time 13:39 Sent To  
Notes
2023-06-08 13:51:11PROVISO
 WINDOWS AND DOOR INCLUDING GARAGE DOORS UNDER SEPERATE
 PERMIT
 SEE BUILIDNG COMMENT REVISION 1 RESPONSE WILL BE
 PROVIDE PRIOR TO INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By lbond Date   Time 14:30 Rev Time 0.00
Received By lbond Date   Time 14:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-09 Cont ID  
Sent By jleahy Date 2023-05-09 Time 14:49 Rev Time 0.00
Received By jleahy Date 2023-05-09 Time 14:28 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-06-09 Cont ID  
Sent By lquinone Date 2023-06-09 Time 08:34 Rev Time 0.00
Received By lquinone Date 2023-06-09 Time 08:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-04-28 Cont ID  
Sent By lquinone Date 2023-04-28 Time 14:58 Rev Time 0.00
Received By lquinone Date 2023-04-28 Time 14:58 Sent To  
Notes
2023-04-28 14:58:50PLEASE SHOW SANITARY SEWER LOCATION (EASEMENT) ON
 SURVEY.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-06-05 Cont ID  
Sent By rwbrown Date 2023-06-05 Time 06:09 Rev Time 0.00
Received By rwbrown Date 2023-06-05 Time 06:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-04-25 Cont ID  
Sent By rwbrown Date 2023-04-25 Time 09:20 Rev Time 0.00
Received By rwbrown Date 2023-04-25 Time 09:20 Sent To  
Notes
2023-04-25 09:38:571ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2413.4.1 - THE PIPE SIZING IS NOT CORRECT.
 IF USING THE LONGEST RUN METHOD, EACH "SYSTEM" CAN USE
 ONLY ONE CHART AND BASE THE CALCULATIONS BASED ON THE
 LONGEST RUN. IF THE LONGEST RUN IS 155 FEET, THE NEXT
 AVAILABLE LINE WOULD BE 175 FEET. YOU WOULD NEED TO USE
 THE 175 FEET LINE. YOU CANNOT USE 4 DIFFERENT TABLES.
 EACH "SYSTEM" IS BASED ON THE LINE PRESSURE BETWEEN
 REGULATORS.
  
 2. 2020 FRC G2413.4.1 - THE BTU LOAD ON THE FLOOR PLAN
 AND THE BTU LOAD ON THE ISOMETRIC DO NOT MATCH. THE
 GENERATOR IS SHOWN AS 604K ON THE ISO, AND 1202K ON THE
 FLOOR PLAN.
  
 3. 2020 FRC G2413.4.1 - THE ISO SHOWS 1" P.E. AFTER THE
 METER ON THE WAY TO THE GENERATOR/WH/RANGE/POOL HEATER
 AND THE FLOOR PLAN SHOWS 3/4". PLEASE FIX.
  
 4. 2020 FRC R303.5.1 - ALTHOUGH THE GENERATOR WILL
 REQUIRE ITS OWN SEPARATE PERMIT, THE GENERATOR WILL
 NEED TO BE 10 FEET FROM OPENINGS INTO THE STRUCTURE.
 PLEASE NOTE THAT THE GENERATOR WILL BE ON A SEPARATE
 PERMIT AND ADJUST ITS LOCATION TO BE 10 FEET FROM
 OPENINGS.
  
 5. 2020 FRC G2427.8 - THE POOL HEATER EXHAUST WILL NEED
 TO BE 4 FEET FROM OPENINGS. IT APPEARS TO BE DIRECTLY
 UNDER A BEDROOM WINDOW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-19 Cont ID  
Sent By rmcdouga Date 2023-07-19 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2023-07-03 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-22 Cont ID  
Sent By rmcdouga Date 2023-06-22 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2023-06-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-09 Cont ID  
Sent By jleahy Date 2023-05-09 Time 14:49 Rev Time 0.00
Received By jleahy Date 2023-04-21 Time 13:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-07-25 Cont ID  
Sent By lmarchan Date 2023-07-25 Time 12:58 Rev Time 0.00
Received By lmarchan Date 2023-07-19 Time 10:47 Sent To  
Notes
2023-07-20 10:50:33RECEIPT MU-2023-031842-0000 - $475.63 PAID
2023-07-19 10:47:137/19/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 14:32 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 14:32 Sent To  
Notes
2023-04-24 14:32:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23041099
  
 REVIEWED: 4.24.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-16 Cont ID  
Sent By cmontell Date 2023-06-16 Time 15:36 Rev Time 0.00
Received By cmontell Date 2023-06-16 Time 15:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-05-05 Cont ID  
Sent By medwards Date 2023-05-05 Time 13:37 Rev Time 0.00
Received By medwards Date 2023-05-05 Time 13:37 Sent To  
Notes
2023-05-05 13:37:241ST REVIEW FMC
 PERMIT: 23041099
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) APPLIANCES IN A FLOOD ZONE WILL NEED TO COMPLY WITH
 FRC M1401.5
  
 2) PROVIDE AN EXHAUST FAN FOR THE SHOWER/BATHTUB AREA
 OF THE PRIMARY BATH. FRC R303.3
  
 3) PROVIDE THE RETURN AIR PATH FROM THE LIVING ROOM
 BACK TO AHU-1. FRC M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By rmcdouga Date 2023-07-19 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2023-07-19 Time 09:27 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2023-06-22 Cont ID  
Sent By rmcdouga Date 2023-06-22 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2023-06-22 Time 10:23 Sent To  
Notes
2023-06-22 11:01:17NFIP REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN ITEM A9 C) THE TOTAL NET OPENING FOR THE
 ENGINEERED FLOOD VENTS SHOULD BE 800 SQUARE INCHES
 WHICH IS EQUILALENT TO THE 800 SQUARE FEET OF AREA THE
 ENGINEERED VENTS ARE RATED FOR. SEE FEMA NFIP TECHNICAL
 BULLETIN 1 SECTION 9.3.5
  
 2) THE ATTACHMENT BOX SHOULD BE CHECKED IN SECTION D
 AND THE EVALUATION REPORTS FOR THE ENGINEERED FLOOD
 VENTS SHOULD BE ATTACHED. THE EVALUATIONS NEED TO
 SPECIFY THE COVERAGE AREA RATING OF THE VENTS. NOTE:
 THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT.
  
 3) THE COMMENT AREA OF SECTION D NEEDS TO INCLUDE THE
 ENGINEERED FLOOD VENTS MODEL NUMBERS AND COVERAGE AREA
 CAPACITY. IT SHOULD BE NOTED THAT THE INTERIOR GRADE
 ELEVATION OF THE GARAGE WAS USED TO DETERMINE THE
 ELEVATION OF THE THE ENGINEERED FLOOD VENTS. SEE THE
 ELEVATION CERTIFICATE INSTRUCTIONS AND NOTES ON THE
 FLOOR PLAN.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-05 Cont ID  
Sent By rwbrown Date 2023-06-05 Time 06:09 Rev Time 0.00
Received By rwbrown Date 2023-06-05 Time 06:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-04-25 Cont ID  
Sent By rwbrown Date 2023-04-25 Time 09:48 Rev Time 0.00
Received By rwbrown Date 2023-04-25 Time 09:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2023-06-08 Cont ID  
Sent By lbond Date 2023-06-08 Time 13:42 Rev Time 0.00
Received By lbond Date 2023-06-08 Time 13:42 Sent To  
Notes
2023-06-08 13:43:54ROOF NOA/PRODUCT APPROVAL UNDER SEPERATE PERMIT SEE
 COVER SHEET NOTE REVISION 1
 ROOFING UNDER SEPERATE PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 14:52 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 14:52 Sent To  
Notes
2023-04-24 15:26:25BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23041099
  
 REVIEWED: 4.24.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 ROOF PLAN REVIEW: FAILED
 SHEET A-3.1
  
 AS PER SECTION 107.2.1
  
 PROVIDE FBC PRODUCT APPROVAL FOR ROOF ASSEMBLY.
  
  
 UPLOAD ALL STRUCTURAL SHEETS
 MENTIONED IN THE INDEX
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-05 Cont ID  
Sent By lbond Date 2023-07-05 Time 08:42 Rev Time 0.00
Received By lbond Date 2023-07-05 Time 08:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-08 Cont ID  
Sent By lbond Date 2023-06-08 Time 13:39 Rev Time 0.00
Received By lbond Date 2023-06-08 Time 13:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 14:15 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-13 Cont ID  
Sent By asangele Date 2023-07-13 Time 12:15 Rev Time 0.00
Received By asangele Date 2023-07-13 Time 12:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-06-13 Cont ID  
Sent By asangele Date 2023-06-13 Time 10:01 Rev Time 0.00
Received By asangele Date 2023-06-13 Time 10:01 Sent To  
Notes
2023-06-13 10:01:39FAILED
 6/13/2023
  
 NEW CONSTRUCTIONS ARE REQUIRED TO ALSO HAVE A LANDSCAPE
 PERMITIN THE SYSTEM
  
  
  
 SEPARATE PERMIT REQUIRED FOR
  
 DRIVEWAY/PATIO
  
 POOL/POOL EQUIPMENT
  
 GENERATOR
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-04 Cont ID  
Sent By asangele Date 2023-05-04 Time 12:27 Rev Time 0.00
Received By asangele Date 2023-05-04 Time 12:27 Sent To  
Notes
2023-05-04 12:33:07FAILED
 5/4/2023
  
 NEW CONSTRUCTIONS ARE REQUIRED TO ALSO HAVE A LANDSCAPE
 PERMITIN THE SYSTEM
  
  
  
 SEPARATE PERMIT REQUIRED FOR
  
 DRIVEWAY/PATIO
  
 POOL/POOL EQUIPMENT
  
 GENERATOR
  
  
 ALEXIS SANGELEER
 PLANNER