Plan Review Details - Permit 23041075
Plan Review Stops For Permit 23041075
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2023-07-11 Cont ID  
Sent By jgomez Date 2023-07-11 Time 13:39 Rev Time 0.00
Received By jgomez Date 2023-07-11 Time 13:38 Sent To  
Notes
2023-07-11 16:38:01IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE.
  
 NOTE: ALL ROOFING PRODUCT APPROVALS ARE REVIEWED UNDER
 SEPARATE ROOFING PERMITS. NO NEED TO RESUBMIT UNDER
 THIS REVISION TO AVOID CONFLICTS/DELAYS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-06-27 Cont ID  
Sent By jgomez Date 2023-06-27 Time 18:50 Rev Time 0.00
Received By jgomez Date 2023-06-26 Time 15:45 Sent To  
Notes
2023-06-27 18:51:15RESIDENTIAL(R3)REVISION. SIXTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR (MAIN HOUSE ONLY).
  
  
 IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE.
  
  
 1- SHUTTERS ARCHITECTURAL DRAWING SIGNED AND SEALED ON
 06/26/2023 SHOWS A FUNCTIONAL SHUTTER NOT A
 DECORATIVE-ONLY LOUVERED SHUTTERS. NEED TO PROVIDE A
 COMPLETE SHUTTERS INSTALLATION SCHEDULE (SEE CITY
 SAMPLE) ALONG WITH A KEY PLAN SHOWING THE OPENINGS
 WHERE THE SHUTTERS WILL BE INSTALLED.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
 THIS WAS DISCUSSED WITH ROBERT BROWN (BUILDING
 OFFICIAL). SHUTTERS ARE NOT DECORATIVE. THEY ARE
 FUNCTIONAL AND NEED COMPLETE INFORMATION.
  
 NOTE: THERE ARE TWO OPTIONS TO ADDRESS THIS COMMENT.
 ONE OPTION IS FOR CONTRACTOR TO SUBMIT SHUTTERS
 COMPLETE INSTALLATION SCHEDULE OR THE OTHER OPTION IS
 FOR SHUTTERS CONTRACTOR TO SUBMIT ALL THE INFORMATION
 UNDER A SEPARATE PERMIT. (PRODUCT APPROVAL, KEY PLAN
 AND COMPLETE INSTALLATION SCHEDULE).
 CONTRACTOR TO ADVICE IN WRITING HOW ADDRESSING THIS
 COMMENT. THE SEPARATE SHUTTERS PERMIT OPTION WILL HELP
 TO APPROVE THIS REVISION FASTER.
  
 2- NEW COLONIAL SHUTTERS PRODUCT APPROVAL DRAWING
 #15-2347 SUBMITTED IS INCOMPLETE. NEED TO PROVIDE
 COMPLETE FLORIDA PRODUCT APPROVAL REPORT, INCLUDING THE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 THE DRAWINGS SUBMITTED. FAC 61G20.3.001.
 NOTE: THE FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE
 IT SHOWS IF PRODUCT IS APPROVED AND CURRENT CODE IN
 EFFECT. CHAPTER 553 F.S.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) SHUTTERS PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- SHUTTER DRAWING SUBMITTED HAS A COPY OF THE
 ARCHITECT'S SEAL AND SIGNATURE.
 IT NEEDS THE ARCHITECT'S DIGITAL SIGNATURE AS DONE WITH
 ALL THE MASTER PERMIT DRAWINGS. ALL DOCUMENTS PREPARED
 BY A LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL
 VERIFIABLE DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD
 AS REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 NOTE: ALL ROOFING PRODUCT APPROVALS ARE REVIEWED UNDER
 SEPARATE ROOFING PERMITS. NO NEED TO RESUBMIT UNDER
 THIS REVISION TO AVOID CONFLICTS/DELAYS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 13:33 Rev Time 0.00
Received By jgomez Date 2023-06-21 Time 12:55 Sent To  
Notes
2023-06-21 13:33:14RESIDENTIAL(R3)REVISION. FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR (MAIN HOUSE ONLY).
  
 IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS,
 INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT.
  
 1- SHUTTERS PRODUCT APPROVALS SUBMITTED:
  
 PREVIOUS COMMENT:
 REPEAT COMMENT: SHUTTERS NOA 20-1102.06 WAS SUBMITTED
 BUT THE COMPLETE INSTALLATION SCHEDULE WAS NOT. PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
  
 RESPONSE:
 SHUTTERS COMPLETE INSTALLATION SCHEDULE WAS NOT
 SUBMITTED. ONLY SHUTTER DETAIL DRAWING DRAWN BY THE
 ARCHITECT WAS SUBMITTED. THIS DRAWING DOESN'T PROVIDE
 THE COMPLETE SHUTTERS INSTALLATION INFORMATION REQUIRED
 BY THE CITY FOR ALL SHUTTERS INSTALLATION. SEE CITY
 SAMPLE.
 NOTE: THERE ARE TWO OPTIONS TO ADDRESS THIS COMMENT.
 ONE OPTION IS FOR CONTRACTOR TO SUBMIT SHUTTERS
 COMPLETE INSTALLATION SCHEDULE NOW OR THE OTHER OPTION
 IS FOR SHUTTERS CONTRACTOR TO SUBMIT ALL THE
 INFORMATION UNDER A SEPARATE PERMIT. (PRODUCT APPROVAL
 AND COMPLETE INSTALLATION SCHEDULE).
 CONTRACTOR TO ADVICE IN WRITING HOW ADDRESSING THIS
 COMMENT. THE SEPARATE SHUTTERS PERMIT OPTION WILL HELP
 TO APPROVE THIS REVISION UNDER THIS CONDITION.
  
 2- SHUTTER DRAWING SUBMITTED WAS NOT SIGNED AND SEALED
 BY THE ARCHITECT.
 IT NEEDS THE ARCHITECT'S DIGITAL SIGNATURE AS DONE WITH
 ALL THE MASTER PERMIT DRAWINGS. ALL DOCUMENTS PREPARED
 BY A LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL
 VERIFIABLE DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD
 AS REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 NOTE: ALL ROOFING PRODUCT APPROVALS ARE REVIEWED UNDER
 SEPARATE ROOFING PERMITS. NO NEED TO RESUBMIT UNDER
 THIS REVISION TO AVOID CONFLICTS/DELAYS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-06 Cont ID  
Sent By jgomez Date 2023-06-06 Time 18:00 Rev Time 0.00
Received By jgomez Date 2023-06-06 Time 16:39 Sent To  
Notes
2023-06-06 18:00:59RESIDENTIAL(R3)REVISION. FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR
  
 IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS,
 INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT.
  
 1- PRODUCT APPROVALS SUBMITTED:
 C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 RESPONSE:
 REPEAT COMMENT: NOA 20-1102.06 WAS SUBMITTED BUT THE
 COMPLETE INSTALLATION SCHEDULE WAS NOT. PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
  
 NOTE: ALL ROOFING PRODUCT APPROVALS REVIEWED UNDER
 SEPARATE ROOFING PERMITS. NO NEED TO RESUBMIT UNDER
 THIS REVISION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-22 Cont ID  
Sent By jgomez Date 2023-05-22 Time 18:14 Rev Time 0.00
Received By jgomez Date 2023-05-22 Time 16:55 Sent To  
Notes
2023-05-22 18:14:55RESIDENTIAL(R3)REVISION. THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR
  
 IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS,
 INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT.
  
  
 1- PRODUCT APPROVALS SUBMITTED:
 C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 RESPONSE:
 PARTIALLY COMPLIED. NOA 20-1102.06 WAS SUBMITTED BUT
 THE COMPLETE INSTALLATION SCHEDULE WAS NOT. PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
  
  
 D)HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 RESPONSE:
 NOA 17-0821.21 SUBMITTED EXPIRED ON MAY 1, 2022. NEED
 TO PROVIDE CURRENT PRODUCT APPROVAL. ARCHITECT TO
 REVIEW NEW PRODUCT APPROVAL BEFORE SUBMITTAL.
  
  
 E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED
 FINISH FLOOR.
 RESPONSE:
 PARTIALLY COMPLIED. NOA 22-0706.09 SUBMITTED. SELECTED
 ASSEMBLY ON PAGE 27 OF 32 IS GOOD FOR -52.5PSF MAXIMUM
 DESIGN PRESSURES. NEED TO PROVIDE SIGNED AND SEALED RAS
 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7
 TO MEET THE DESIGN PRESSURES FOR ROOF ZONE #2 AND #3.
 SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
 ALSO, IDENTIFY WHICH FINISH PRODUCT FROM TABLE 4 OF
 SAME NOA IS GOING TO BE INSTALLED.
  
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 RESPONSE:
 ARCHITECT SPECIFIES PEEL & STICK WATERPROOFING ON SHEET
 A3.1. NOA 18-1109.03 SUBMITTED IS NOT A PEEL & STICK
 UNDERLAYMENT. PEEL AND STICK UNDERLAYMENT COMPLIES WITH
 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. IF USING
 OTHER TYPE OF UNDERLAYMENT, THEN ARCHITECT NEEDS TO
 REVISE PLANS SHOWING HOW COMPLYING WITH SEC. R905.1.1.1
 FBC-RESIDENTIAL. THERE ARE FIVE OPTIONS. CLEARLY
 SPECIFY WHICH ONE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-03 Cont ID  
Sent By jgomez Date 2023-05-03 Time 19:05 Rev Time 0.00
Received By jgomez Date 2023-05-03 Time 17:59 Sent To  
Notes
2023-05-03 19:05:1905/03/23 RESPONSE TO EMAIL FROM ELIZABETH TUKE (DATED
 WED 5/3/2023):
  
 HI JULIO,
 FOLLOWING UP ON PERMIT RESUBMISSION FOR 234 EDGEWOOD
 RE: A FEW THINGS THAT HAD PREVIOUSLY BEEN SUBMITTED.
 PLEASE TAKE A LOOK. THANK YOU!
  
 THE FOLLOWING PRODUCT APPROVALS REQUESTED ON PROVISO
 DATED 10/06/2022 ARE NOT SUBMITTED YET FOR REVIEW. NEED
 TO SUBMIT THEM TO AVOID CONFLICTS/DELAYS:
  
 PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS. TBD
  
 JULIO'S RESPONSE:
 OK. IT WILL BE SUBMITTED LATER.
  
 B)HURRICANE SHUTTERS IF DOORS DON'T HAVE IMPACT
 GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE. -- USING IMPACT WINDOWS & DOORS.
  
 JULIO'S RESPONSE:
 OK.
  
 C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 LOUVERED SHUTTER --
 HTTPS://WWW.ARCHITECTURALDEPOT.COM/CUSTOM-TFPLV.HTML
 PAINT COLOR TO MATCH EXTERIOR HOUSE COLOR
  
 JULIO'S RESPONSE:
 NEED TO SUBMIT ACTUAL COPY OF PRODUCT APPROVAL AND
 INSTALLATION SCHEDULE.
  
 D)HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 ATTACHED
  
 JULIO'S RESPONSE:
 ATTACHED INFORMATION IS NOT A PRODUCT APPROVAL. PLEASE
 COORDINATE WITH CONTRACTOR AND ARCHITECT.
  
 E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED
 FINISH FLOOR.
 THIS WAS SUBMITTED. RE-ATTACHED HERE
  
 JULIO'S RESPONSE:
 THERE ARE COMMENTS THAT NEED TO BE ADDRESSED REGARDING
 THIS PRODUCT APPROVAL. PLEASE SEE COMMENTS BELOW.
 PLEASE COORDINATE WITH CONTRACTOR AND ARCHITECT.
  
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. WILL RESEND.
  
 JULIO'S RESPONSE:
 IT WAS NOT SUBMITTED.
  
  
 NOTE: DESIGNER OF RECORD NEEDS TO APPROVE ALL PRODUCT
 APPROVALS IN WRTTING BEFORE SUBMITTAL.
  
  
 IMPORTANT:
 THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A
 SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS,
 INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT.
  
  
  
  
 RESIDENTIAL(R3)REVISION. BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR
  
 1- PRODUCT APPROVALS SUBMITTED:
 A)POLYGLASS MODIFIED BITUMEN NOA 22-0706.09 SUBMITTED:
 CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE
 INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 SEC. R301.2.1 FBC-RESIDENTIAL
  
 B)SINGLE HUNG WINDOWS NOA 20-0722.09.
 C)ROOF SHINGLES NOA 21-0518.04.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ABOVE PRODUCT APPROVALS
 SUBMITTED AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 IMPORTANT NOTE:
 THE FOLLOWING PRODUCT APPROVALS REQUESTED ON PROVISO
 DATED 10/06/2022 ARE NOT SUBMITTED YET FOR REVIEW. NEED
 TO SUBMIT THEM TO AVOID CONFLICTS/DELAYS:
  
 PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)HURRICANE SHUTTERS IF DOORS DON'T HAVE IMPACT
 GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
 C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 D)HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED
 FINISH FLOOR.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 NOTE: DESIGNER OF RECORD TO APPROVE ALL PRODUCT
 APPROVALS BEFORE SUBMITTAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-26 Cont ID  
Sent By jgomez Date 2023-04-26 Time 17:57 Rev Time 0.00
Received By jgomez Date 2023-04-26 Time 14:59 Sent To  
Notes
2023-04-26 17:57:42RESIDENTIAL(R3) REVISION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #23041075
 234 EDGEWOOD DR
  
 1- PRODUCT APPROVALS SUBMITTED:
 A)POLYGLASS MODIFIED BITUMEN NOA 22-0706.09 SUBMITTED:
 CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE
 INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 SEC. R301.2.1 FBC-RESIDENTIAL
  
 B)SINGLE HUNG WINDOWS NOA 20-0722.09.
 C)ROOF SHINGLES NOA 21-0518.04.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ABOVE PRODUCT APPROVALS
 SUBMITTED AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 IMPORTANT NOTE:
 THE FOLLOWING PRODUCT APPROVALS REQUESTED ON PROVISO
 DATED 10/06/2022 ARE NOT SUBMITTED YET FOR REVIEW. NEED
 TO SUBMIT THEM TO AVOID CONFLICTS/DELAYS:
  
 PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)HURRICANE SHUTTERS IF DOORS DON'T HAVE IMPACT
 GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
 C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
 D)HARDIE BOARD SIDING AS SPECIFIED ON PLANS.
 E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED
 FINISH FLOOR.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 NOTE: DESIGNER OF RECORD TO APPROVE ALL PRODUCT
 APPROVALS BEFORE SUBMITTAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By amhamilt Date 2023-07-17 Time 12:21 Rev Time 0.00
Received By amhamilt Date 2023-07-17 Time 12:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-05-24 Cont ID  
Sent By amhamilt Date 2023-05-24 Time 10:32 Rev Time 0.00
Received By vbroglia Date 2023-05-24 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-18 Cont ID  
Sent By aoliver Date 2023-07-18 Time 08:55 Rev Time 0.00
Received By aoliver Date 2023-06-02 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-24 Cont ID  
Sent By vbroglia Date 2023-05-24 Time 10:32 Rev Time 0.00
Received By vbroglia Date 2023-04-24 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-05-08 Cont ID  
Sent By medwards Date 2023-05-08 Time 05:58 Rev Time 0.00
Received By medwards Date 2023-05-08 Time 05:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-07-11 Cont ID  
Sent By jgomez Date 2023-07-11 Time 13:42 Rev Time 0.00
Received By jgomez Date 2023-07-11 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-27 Cont ID  
Sent By jgomez Date 2023-06-27 Time 18:56 Rev Time 0.00
Received By jgomez Date 2023-06-27 Time 18:56 Sent To  
Notes
2023-06-27 18:57:15SIGNATURE REVIEW:
  
 1- SHUTTER DRAWING SUBMITTED HAS A COPY OF THE
 ARCHITECT'S SEAL AND SIGNATURE.
 IT NEEDS THE ARCHITECT'S DIGITAL SIGNATURE AS DONE WITH
 ALL THE MASTER PERMIT DRAWINGS. ALL DOCUMENTS PREPARED
 BY A LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL
 VERIFIABLE DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD
 AS REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-06-21 Cont ID  
Sent By jgomez Date 2023-06-21 Time 13:27 Rev Time 0.00
Received By jgomez Date 2023-06-21 Time 13:27 Sent To  
Notes
2023-06-21 13:29:16SIGNATURE REVIEW:
  
 1-- SHUTTER DRAWING SUBMITTED WAS NOT SIGNED AND SEALED
 BY THE ARCHITECT.
 IT NEEDS THE ARCHITECT'S DIGITAL SIGNATURE AS DONE WITH
 ALL THE MASTER PERMIT DRAWINGS. ALL DOCUMENTS PREPARED
 BY A LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL
 VERIFIABLE DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD
 AS REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-26 Cont ID  
Sent By jgomez Date 2023-04-26 Time 18:16 Rev Time 0.00
Received By jgomez Date 2023-04-26 Time 18:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-24 Cont ID  
Sent By amhamilt Date 2023-05-24 Time 10:32 Rev Time 0.00
Received By vbroglia Date 2023-05-24 Time 10:32 Sent To  
Notes
***NONE***