Plan Review Details - Permit 23041073
Plan Review Stops For Permit 23041073
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-28 Cont ID  
Sent By lbond Date 2023-06-28 Time 09:33 Rev Time 0.00
Received By lbond Date 2023-06-28 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By lbond Date 2023-06-15 Time 13:53 Rev Time 0.00
Received By lbond Date 2023-06-15 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By lbond Date 2023-05-30 Time 11:04 Rev Time 0.00
Received By lbond Date 2023-05-30 Time 11:04 Sent To  
Notes
2023-05-30 11:19:58PROVIDE NOA OR FBC PRODUCT APPROVAL FOR ALL NEW WINDOWS
 AND DOORS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-21 Cont ID  
Sent By jcooley Date 2023-05-21 Time 08:38 Rev Time 0.00
Received By jcooley Date 2023-05-21 Time 08:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By rwbrown Date 2023-06-15 Time 15:24 Rev Time 0.00
Received By rwbrown Date 2023-06-15 Time 15:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 14:12 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 14:12 Sent To  
Notes
2023-05-30 14:14:521ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS
 RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING
 APPLICABLE ITEMS. LOCATION OF SHUT-OFFS, THE PIPING
 MATERIAL, GAS PIPE SIZING METHOD AND BTU LOADS, VENTING
 OF APPLIANCES, COMBUSTION AIR CALCULATIONS, CHIMNEYS
 AND VENTS, APPLIANCE SCHEDULE, THE TYPE OF GAS
 PROPOSED, FIREPLACES, AND LP TANK OR METER LOCATION
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-28 Cont ID  
Sent By lmarchan Date 2023-06-28 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2023-06-27 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-15 Cont ID  
Sent By rwbrown Date 2023-06-15 Time 15:24 Rev Time 0.00
Received By rwbrown Date 2023-06-13 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-31 Cont ID  
Sent By aoliver Date 2023-05-31 Time 08:14 Rev Time 0.00
Received By aoliver Date 2023-05-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By aoliver Date 2023-07-14 Time 09:08 Rev Time 0.00
Received By aoliver Date 2023-06-15 Time 15:28 Sent To  
Notes
2023-07-14 09:08:03NO IMPACT FEES DUE, SEE EMAIL UPLOADED
2023-06-15 15:28:52EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-05-26 Cont ID  
Sent By lbond Date 2023-05-26 Time 15:41 Rev Time 0.00
Received By lbond Date 2023-05-26 Time 15:41 Sent To  
Notes
2023-05-26 16:20:04IMPACT REVIEW: FAILED
  
 W.P.B. PERMIT: 23041073
  
 REVIEWED: 5.26.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-05-30 Cont ID  
Sent By   Date 2023-05-30 Time   Rev Time  
Received By   Date 2023-05-30 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By rwbrown Date 2023-06-15 Time 15:16 Rev Time 0.00
Received By rwbrown Date 2023-06-15 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-05-18 Cont ID  
Sent By rwbrown Date 2023-05-18 Time 06:47 Rev Time 0.00
Received By rwbrown Date 2023-05-18 Time 06:47 Sent To  
Notes
2023-05-18 07:08:171ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER NEEDS TO
 BE IN ISOMETRIC FORM. PLEASE SUBMIT AN ISOMETRIC RISER
 WITH FIXTURE TAGS ON EACH RISER.
 NOTE: SHOWING THE SECOND FLOOR DRAINAGE ON THE 1ST
 FLOOR PLAN MAKES IT DIFFICULT TO REVIEW. THE SECOND
 FLOOR DRAINS SHOULD BE SHOWN ON THE SECOND FLOOR PLAN
 IMPOSED UNDER THE FIXTURES THEY SERVE.
  
 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SUPPLIED
 DOES NOT MATCH THE CURRENT LAYOUT. THE FLOOR PLAN SHOWS
 TUB-LAV-SHOWER-LAV, AND THE RISER SHOWS
 LAV-TUB-SHOWER-LAV. THEY SHOULD MATCH.
  
 3. 2020 FRC P3108.2.1 - IT SHOULD BE NOTED THAT THE
 EXISTING IS SHOWN AS NOT BEING VENTED TO CODE. THE
 LAUNDRY IS NOT ALLOWED TO VENT THE BATHTUB AND WATER
 CLOSET.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2023-05-30 Cont ID  
Sent By lbond Date 2023-05-30 Time 11:04 Rev Time 0.00
Received By lbond Date 2023-05-30 Time 11:04 Sent To  
Notes
2023-05-30 11:13:00BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23041073
  
 REVIEWED: 5.30.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 ROOF COMMENTS: FAILED
  
 AS PER SECTION 107.2.1
  
 PROVIDE NOA FOR PROPOSED NEW FLAT ROOM MEMBRANES
 STUCTURAL CALCULATION INCLUDED IN SUPPORTIVE DOCUMENTS
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By lbond Date 2023-06-15 Time 13:53 Rev Time 0.00
Received By lbond Date 2023-06-15 Time 13:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By lbond Date 2023-05-26 Time 15:38 Rev Time 0.00
Received By lbond Date 2023-05-26 Time 15:38 Sent To  
Notes
2023-05-26 15:41:24BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23041073
  
 REVIEWED: 5.26.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 PLAN BY FL. LICENSES ENGINEERS THAT ARE SUBMITTED
 ELECTRONICALLY SHALL BEAR VERIFIABLE, ORIGINAL DIGITAL
 SIGNATURE AND SEALS- FL STATUTE 471.025 AND SEC
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
  
 1. ARCHITECTURE AND STRUCTURE SHEETS PASSED
  
  
 2. MEP SHEETS NEED TO BE DIGITALLY SIGNED AND SEALED
 VERIFIABLE WITH ADOBE OR BLUEBEAM REVUE SOFTWARE.
 FAILED
  
 M.00 PASSED
 P.00 PASSED
 E.00 PASSED
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-25 Cont ID  
Sent By lgelman Date 2023-05-25 Time 17:22 Rev Time 0.00
Received By lngelman Date 2023-05-25 Time 17:22 Sent To  
Notes
***NONE***