Plan Review Details - Permit 23041044
Plan Review Stops For Permit 23041044
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-07-17 Cont ID  
Sent By jbrooks Date 2023-07-17 Time 14:21 Rev Time 0.00
Received By jbrooks Date 2023-07-17 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-10 Cont ID  
Sent By jbrooks Date 2023-07-10 Time 14:06 Rev Time 0.00
Received By jbrooks Date 2023-07-10 Time 08:07 Sent To  
Notes
2023-07-10 14:06:26JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL14083-R28 SYSTEM NO. SC-315 DOES NOT MEET
 THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF
 -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM
 THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS
 FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-30 Cont ID  
Sent By jbrooks Date 2023-06-30 Time 11:37 Rev Time 0.00
Received By jbrooks Date 2023-06-30 Time 07:58 Sent To  
Notes
2023-06-30 11:37:20JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 PLEASE ADDRESS PREVIOUS COMMENTS BELOW DATED 06/21/2023
 AND RESUBMIT.
  
 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR
 FLORIDA PRODUCT APPROVAL FL14083-R28 FOR THE PROPOSED
 FLAT ROOF RECOVER SYSTEM TO BE USED CORRESPONDING TO
 ENGINEERS MEMBRANE ATTACHMENT CALCULATIONS. EVALUATION
 REPORT PAGES #1-5, INSTALLATION INSTRUCTIONS FOR SYSTEM
 R-79 PAGE #97. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. SUBMITTED EVALUATION REPORT & INSTALLATION
 INSTRUCTIONS ARE FOR FL14083-R26.
 2. FBC R 301 FAC9N-3. PROVIDE REROOF SYSTEM NUMBER &
 INSTALLATION INSTRUCTIONS PAGE FOR THE MAIN CENTER ROOF
 & LOWER NORTH ROOF AREAS TO BE REMOVED AND REPLACED AS
 PER THE SUBMITTED ROOF MOISTURE REPORT. PROVIDE SIGNED
 AND SEALED CALCULATIONS IF SYSTEM SELECTED DOES NOT
 MEET MINIMUM DESIGN PRESSURE REQUIREMENTS. PLEASE NOTE:
 PRODUCT APPROVAL FL14083-R28 WAS REVISED TO FL14083-R29
 ON JUNE 20, 2023.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-21 Cont ID  
Sent By jbrooks Date 2023-06-21 Time 12:55 Rev Time 0.00
Received By jbrooks Date 2023-06-21 Time 08:00 Sent To  
Notes
2023-06-21 12:56:07JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR
 FLORIDA PRODUCT APPROVAL FL14083-R28 FOR THE PROPOSED
 FLAT ROOF RECOVER SYSTEM TO BE USED CORRESPONDING TO
 ENGINEERS MEMBRANE ATTACHMENT CALCULATIONS. EVALUATION
 REPORT PAGES #1-5, INSTALLATION INSTRUCTIONS FOR SYSTEM
 R-79 PAGE #97. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. SUBMITTED EVALUATION REPORT & INSTALLATION
 INSTRUCTIONS ARE FOR FL14083-R26.
 2. FBC R 301 FAC9N-3. PROVIDE REROOF SYSTEM NUMBER &
 INSTALLATION INSTRUCTIONS PAGE FOR THE MAIN CENTER ROOF
 & LOWER NORTH ROOF AREAS TO BE REMOVED AND REPLACED AS
 PER THE SUBMITTED ROOF MOISTURE REPORT. PROVIDE SIGNED
 AND SEALED CALCULATIONS IF SYSTEM SELECTED DOES NOT
 MEET MINIMUM DESIGN PRESSURE REQUIREMENTS. PLEASE NOTE:
 PRODUCT APPROVAL FL14083-R28 WAS REVISED TO FL14083-R29
 ON JUNE 20, 2023.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-02 Cont ID  
Sent By jbrooks Date 2023-06-02 Time 09:30 Rev Time 0.00
Received By jbrooks Date 2023-06-02 Time 07:54 Sent To  
Notes
2023-06-02 09:30:59JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL14083-R26 HAS BEEN
 REVISED TO FL14083-R28. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-5 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 2. FBC B 107.2.1. REVISE SUBMITTED MEMBRANE ATTACHMENT
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER TO UPDATE PRODUCT
 APPROVAL TO THE CURRENT APPROVED VERSION
 FL14083-R28; INCLUDE UPDATED SYSTEM/PAGE NUMBER TO BE
 USED.
 3. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE
 REPORT PREPARED BY A FLORIDA REGISTERED DESIGN
 PROFESSIONAL. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-08 Cont ID  
Sent By jbrooks Date 2023-05-08 Time 09:00 Rev Time 0.00
Received By jbrooks Date 2023-05-08 Time 07:44 Sent To  
Notes
2023-05-08 09:00:43JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16440-R24
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL14083-R28 (NON-HVHZ). PROVIDE THE
 FOLLOWING: COVER PAGE, EVALUATION REPORTS PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S) AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. SELECT SYSTEM THAT MEETS
 OR EXCEEDS EXPOSURE CATEGORY C MINIMUM DESIGN PRESSURE
 ZONE 3 REQUIREMENTS OF -108.17. SIGNED AND SEALED
 NAILING CALCULATIONS MAY BE REQUIRED.
 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH
 TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY
 LIMITATIONS 5.6.1 OF PRODUCT APPROVAL FL14083.
 3. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE
 REPORT PREPARED BY A FLORIDA REGISTERED DESIGN
 PROFESSIONAL.
 4. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF
 DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE
 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020
 FBC-PLUMBING.
 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 14:25 Rev Time 0.00
Received By lbond Date 2023-07-14 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-10 Cont ID  
Sent By jbrooks Date 2023-07-10 Time 14:06 Rev Time 0.00
Received By jbrooks Date 2023-07-06 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-30 Cont ID  
Sent By jbrooks Date 2023-06-30 Time 11:37 Rev Time 0.00
Received By jbrooks Date 2023-06-22 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-21 Cont ID  
Sent By jbrooks Date 2023-06-21 Time 12:56 Rev Time 0.00
Received By jbrooks Date 2023-06-09 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-02 Cont ID  
Sent By jbrooks Date 2023-06-02 Time 09:33 Rev Time 0.00
Received By jbrooks Date 2023-05-26 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-08 Cont ID  
Sent By jbrooks Date 2023-05-08 Time 09:00 Rev Time 0.00
Received By jbrooks Date 2023-05-05 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 14:25 Rev Time 0.00
Received By lbond Date 2023-07-17 Time 14:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-09 Cont ID  
Sent By mpeterso Date 2023-06-09 Time 09:04 Rev Time 0.00
Received By mpeterso Date 2023-06-09 Time 09:04 Sent To  
Notes
2023-06-09 09:06:466/9/23 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS PASSED
 AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-02 Cont ID  
Sent By jbrooks Date 2023-06-02 Time 09:33 Rev Time 0.00
Received By jbrooks Date 2023-06-02 Time 09:08 Sent To  
Notes
2023-06-02 09:33:33JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 PENDING REVISED MEMBRANE ATTACHMENT CALCULATIONS.
 DRAINAGE CALCS & PULL TEST SIGNATURES PASSED.
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  