Plan Review Details - Permit 23041007
Plan Review Stops For Permit 23041007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By lbond Date 2023-05-19 Time 10:35 Rev Time 0.00
Received By lbond Date 2023-05-19 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-08 Cont ID  
Sent By lbond Date 2023-05-08 Time 11:29 Rev Time 0.00
Received By lbond Date 2023-05-08 Time 11:29 Sent To  
Notes
2023-05-08 11:32:34 
 SHEET A.1
  
 2020 FBC ACESSIBILITY 7TH EDITION
  
 FIGURE 604.8.1.6WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT IN NEW CONSTRUCTION
  
 ROOM 203
 DOOR SHOULD SWING OUT.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE DO NOT
 HESITATE TO CONTACT US
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-09 Cont ID  
Sent By rperdomo Date 2023-05-09 Time 16:17 Rev Time 0.00
Received By rperdomo Date 2023-05-09 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By clfranci Date 2023-05-17 Time   Rev Time 0.00
Received By clfranci Date 2023-05-17 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-21 Cont ID  
Sent By clfranci Date 2023-04-21 Time   Rev Time 0.00
Received By clfranci Date 2023-04-21 Time   Sent To  
Notes
2023-04-21 09:46:22THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2023-05-27 Cont ID  
Sent By hmoser Date 2023-05-27 Time 10:05 Rev Time 0.00
Received By hmoser Date 2023-05-15 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-10 Cont ID  
Sent By lmarchan Date 2023-05-10 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2023-04-19 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-27 Cont ID  
Sent By hmoser Date 2023-05-27 Time 10:04 Rev Time 0.00
Received By hmoser Date 2023-05-27 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-05-03 Cont ID  
Sent By medwards Date 2023-05-03 Time 12:01 Rev Time 0.00
Received By medwards Date 2023-05-03 Time 12:01 Sent To  
Notes
2023-05-03 12:01:441ST REVIEW FMC
 PERMIT: 23041007
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRAWINGS SHOW THE EXISTING EXAM AND RESTROOM ARE
 TO BE REMOVED AND THE EXISTING WAITING ROOM IS TAKING
 THIS SQUARE FOOTAGE. PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THIS ENLARGED WAITING ROOM AND SHOW
 HOW THE ADDITIONAL OUTDOOR AIR IS TO BE INTRODUCED INTO
 THIS NEW AREA. FMC TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-04-24 Cont ID  
Sent By ccole Date 2023-04-24 Time 14:05 Rev Time 0.00
Received By ccole Date 2023-04-24 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By lbond Date 2023-05-16 Time 10:23 Rev Time 0.00
Received By lbond Date 2023-05-19 Time 10:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-08 Cont ID  
Sent By lbond Date 2023-05-08 Time 11:18 Rev Time 0.00
Received By lbond Date 2023-05-08 Time 11:18 Sent To  
Notes
***NONE***