Plan Review Details - Permit 23040992
Plan Review Stops For Permit 23040992
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-26 Cont ID  
Sent By rmcdouga Date 2023-05-26 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2023-05-26 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-04 Cont ID  
Sent By rmcdouga Date 2023-05-04 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2023-05-04 Time 14:28 Sent To  
Notes
2023-05-04 15:58:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 THE PRODUCT HAS TO BE TESTED WITH THE SAME SLAB
 THICKNESS AND CONDITIONS THAT EXIST AT THE LOCATION
 WHERE IT WILL BE INSTALLED.
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-11 Cont ID  
Sent By pleduc Date 2023-05-11 Time   Rev Time 0.00
Received By pleduc Date 2023-05-11 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By cwalker Date 2023-04-20 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-04-20 10:04:10FIRE REVIEW COMMENTS:
  
 PROVIDE TEST DATA FOR THE VINYL FLOOR FIRE PERFORMANCE
 TO INCLUDE THE CRITICAL RADIANT FLUX OF THE MATERIALS
 TO BE INSTALLED. NFPA 101, 10.2.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-26 Cont ID  
Sent By rmcdouga Date 2023-05-26 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2023-05-10 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-04 Cont ID  
Sent By rmcdouga Date 2023-05-04 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2023-04-19 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-05-04 Cont ID  
Sent By rmcdouga Date 2023-05-04 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2023-05-04 Time 14:28 Sent To  
Notes
***NONE***