Plan Review Details - Permit 23040991
Plan Review Stops For Permit 23040991
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-26 Cont ID  
Sent By cthroop Date 2023-07-26 Time 11:16 Rev Time 0.00
Received By cthroop Date 2023-07-26 Time 06:56 Sent To  
Notes
2023-07-26 11:16:37THE SITE PLAN AND ELECTRICAL/SITE DRAINAGE PLANS
 REQUIRE THE NAME AND SIGNATURE OF THE
 DESIGNER/CONTRACTOR. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-24 Cont ID  
Sent By cthroop Date 2023-05-24 Time 12:39 Rev Time 0.00
Received By cthroop Date 2023-05-24 Time 08:14 Sent To  
Notes
2023-05-24 12:43:191ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICED: PLAN PAGE SO (WIND LOAD DESIGN) AND ALL OTHER
 STRUCTURAL PLANS REQUIRE THE PRINTED NAME AND SIGNATURE
 OF THE DESIGNER.
  
 1.THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-07-10 Cont ID  
Sent By mpeterso Date 2023-07-10 Time 08:39 Rev Time 0.00
Received By mpeterso Date 2023-07-10 Time 08:39 Sent To  
Notes
2023-07-10 08:43:10ELECTRICAL REVIEW FAILED
  
 1) ELECTRICAL PLAN STILL DOES NOT DETAIL THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 WEST PALM BEACH AMENDMENT 107.2
  
 2) PLAN STILL DETAILS EQUIPMENT POWERED THROUGH AN
 ELECTRIC RECEPTACLE. STUXURE CONTROL BOX.
  
 NEC 400.12 USES NOT PERMITTED.
 UNLESS SPECIFICALLY PERMITTED IN 400.10, FLEXIBLE
 CABLES, FLEXIBLE CORD SETS, AND POWER SUPPLY CORDS
 SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
 .
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-05-19 Cont ID  
Sent By mpeterso Date 2023-05-19 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2023-05-19 Time 11:19 Sent To  
Notes
2023-05-19 12:50:00ELECTRICAL REVIEW FAILED
  
 1) ELECTRICAL PLAN IS REQUIRED TO BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 WEST PALM BEACH AMENDMENT 107.2
  
 2) PLAN DETAILS EQUIPMENT POWERED THROUGH AN ELECTRIC
 RECEPTACLE. EQUIPMENT.
 NEC 400.12 USES NOT PERMITTED.
 UNLESS SPECIFICALLY PERMITTED IN 400.10, FLEXIBLE
 CABLES, FLEXIBLE CORD SETS, AND POWER SUPPLY CORDS
 SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A
 STRUCTURE.
  
 3) PLEASE PROVIDE AN ELECTRICAL FLOOR/SITE PLAN
 LOCATING ALL EQUIPMENT SHOWN IN SCHEMATIC DRAWING. FBC
 107.2
  
 4) PLAN DETAILS AN NEW 225 AMP ELECTRIC PANEL. NOTES
 CONTAINED IN THIS PLAN INDICATE THIS PANEL TO BE
 INSTALLED BY OTHERS. PLEASE PROVIDE THE APPLICABLE
 PERMIT APPLICATION AND PLANS FOR NEW PANEL. FBC 107.2
  
 5) PLEASE PROVIDE DETAILS OF WIRE METHODS USED FOR ALL
 WIRING. NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-26 Cont ID  
Sent By cthroop Date 2023-07-26 Time 11:16 Rev Time 0.00
Received By cthroop Date 2023-07-03 Time 10:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-25 Cont ID  
Sent By aoliver Date 2023-05-25 Time 09:02 Rev Time 0.00
Received By aoliver Date 2023-05-24 Time 17:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-26 Cont ID  
Sent By cthroop Date 2023-07-26 Time 11:13 Rev Time 0.00
Received By cthroop Date 2023-07-26 Time 06:56 Sent To  
Notes
2023-07-26 11:16:21ALL PLAN PAGES WITH DESIGN PROFESSIONAL SIGNATURES AND
 SEALS HAVE VALID DIGITAL SIGNATURES.
 THE SITE PLAN AND ELECTRICAL/SITE DRAINAGE PLANS
 REQUIRES THE NAME AND SIGNATURE OF THE
 DESIGNER/CONTRACTOR. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-05-24 Cont ID  
Sent By cthroop Date 2023-05-24 Time 12:39 Rev Time 0.00
Received By cthroop Date 2023-05-24 Time 08:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-11 Cont ID  
Sent By lngelman Date 2023-07-11 Time 13:55 Rev Time 0.00
Received By lngelman Date 2023-07-11 Time 13:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-24 Cont ID  
Sent By lgelman Date 2023-05-24 Time 17:27 Rev Time 0.00
Received By lngelman Date 2023-05-24 Time 17:27 Sent To  
Notes
***NONE***